Airmark GAW18 Installation & Operating Instructions Manual Download Page 3

 

 

 

 

 

IO-123084-GAW-063017 

- 3 - 

©2017 AirMark 

 

the secondary to keep droplets out but allow 
trapped condensate into secondary fittings.  
 

CAUTION

  Since coil is upstream of the 

blower; all drains 

MUST

  be trapped or sealed. 

Failure to do so will result in condensate overflow 
from the drain pan. Airmark will 

NOT

  be 

responsible for any damages resulting from failure 
to follow these instructions.   

 

 

2" MINIMUM

3" MINIMU

FLEXIBLE

TUBING-HOSE

OR PIPE

A POSITIVE

LIQUID SEAL IS

REQUIRED

DRAIN

CONNECTION

 

 
Fig.1. Typical drain line trap set up 

 

Ductwork 

Duct systems should be installed in accordance 
with standards for air-conditioning systems, 
National Fire Protection Association Pamphlet No. 
90A or 90B. They should be sized in accordance 
with National Environmental System Contractors 
Association Manual K, or whichever is applicable. 

 

On any job, non-flammable flexible collars should 
be used for the return air and discharge 
connections to prevent transmission of vibration. 
Although these units have been specially designed 
for quiet vibration-free operation, air ducts can act 
as soundboards can, if poorly installed, amplify the 
slightest vibration to the annoyance level. 

 

All main supply and return air drops should be 
properly sized  as determined by the designer of 
the duct system and should not necessarily be the 
size of the duct flange openings of the unit. 
 
These models have a bottom or front return. 
Discard the drain access panel in the bottom of 
the unit if this is a bottom return application. In 
case of a front return application, the front access 
panel should be removed and discarded. If an 
accessory grill as shown in Fig 2. is being used; 
the front access panel should be removed and 
discarded.  

A filter rack is provided for 

"

20

"

20

"

1

×

×

nominal 

size filter. Inspect and clean or replace fliter every 
month. A blocked filter can reduce air flow to the 
coil and hinder the performance of the system.  
 
It is recommended that wherever supply and 
return air sheet metal duct pass through 
unconditioned areas, they be insulated to prevent 
excessive heat loss during heating operation. 
When applied in conjunction with summer air 
conditioning, sheet metal duct routed through 
unconditioned areas should be insulated and have 
an outside vapor barrier to prevent formation of 
condensation. 

 

Fig.2. GAW air handler grill and drain connections  

 

Installation  

 

CAUTION

  Ensure that the unit is adequately 

sized. The tonnage of the outdoor unit should 
never exceed the tonnage of this unit.  

 

WARNING

  The coil was manufactured with 

dry nitrogen pre-charge. Release the pressure 
through the Schrader valve test port prior to 
installation. If holding pressure is not present, 
return coil to distributor for exchange.   

Summary of Contents for GAW18

Page 1: ..._________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE _________________________________________ T...

Page 2: ...modification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s re...

Page 3: ...determined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit These models have a bottom or front return Discard the drain access panel...

Page 4: ...poor system performance and possible compressor damage During some installations a piston change may be required If so the installer MUST change the piston As stated earlier use piston sizes recommend...

Page 5: ...tion of the TXV bulb has a major influence on the system performance CAUTION Ensure that the TXV bulb is in direct contact with the suction vapor line Gaps between the bulb and tube should be avoided...

Page 6: ...box and note the location of the inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw...

Page 7: ...10 kW are arranged for multi circuit protection Fig 7 shows the typical electrical connections required for the air handler unit Fig 7 Typical electrical connections required System Charging CAUTION...

Page 8: ...et and outlet For outlet measure temperature of each main trunk at a location far enough away to avoid heater radiation and read the average temperatures Table 3 below shows the CFM that should be ach...

Page 9: ...current protection in the form of circuit breakers Have your contractor identify the circuits and the location of over current protection so that you will be in a position to make inspections or repla...

Page 10: ...IO 123084 GAW 020113 2013 AirMark WARNING HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lead to safety hazard Wiring diagram for GAW models...

Reviews: