CAUTION

  Pay close attention to the piston 

orientation. The pointed end of the piston 

MUST

 go into the distributor body/towards the 

coil. Failure to ensure this orientation will 
cause the piston to be bypassed during 
operation which might damage the outdoor 
unit. 

 

6)  Assemble the two halves correctly and 

ensure that the white Teflon O-ring is 
present between the two halves. 

7)  Slide the 13/16 nut onto the distributor 

body. 

8)  Tighten the nut to a torque of 

approximately 10-30 ft-lbs. Do 

NOT

 

over 

tighten the nut. This will hamper the piston 
movement during operation.  

9)  Slide the grommet back to position to 

prevent air leakage. 

 

 
 
TXV Coils: 

 

WARNING

  The sensing bulb and TXV body 

MUST

  be protected from overheating during 

brazing. The sensing bulb and TXV body must be 
covered using a quench cloth or wet cloth when 
brazing. Pointing the brazing flame away from the 
valve and sensing bulb provide partial protection 
only.  

 

 

CAUTION

  Ensure that the TXV selected is 

compatible with the refrigerant used in the outdoor 
system (R22 or R410A). TXV caps are painted 
green for R22 or pink for R410A. In absence of 
color, the caps will be marked with the compatible 
refrigerant. 

 

 

CAUTION

  The valves should be sized 

according to the capacity of the outdoor unit. 
Failure to install the right valve can lead to poor 
performance and possible compressor damage.  

 

TXV Bulb Mounting 

 

The orientation and location of the TXV bulb has a 
major influence on the system performance.  

 

CAUTION

  Ensure that the TXV bulb is in 

direct contact with the suction/vapor line. Gaps 
between the bulb and tube should be avoided. 

Failure to eliminate gaps will impair the proper 
functioning of the TXV valve.  

 

It is recommended that the TXV bulb be installed 
parallel to the ground (in a horizontal plane). The 
bulb position should be above and between 4 
o’clock and 8 o’clock. Fig. 4 shows the 
recommended position for the TXV bulb 
installation in the horizontal plane. 

 

The TXV sensing bulb 

SHOULD

  be mounted 

using the metal clamp provided. In order to obtain 
a good temperature reading and correct superheat 
control, the TXV sensing bulb must conform to 
ALL of the following criteria: 

 

1)  The sensing bulb 

MUST

  be in direct and 

continuous contact with the suction line 

2)  The sensing bulb should be mounted 

horizontally on the suction line. 

3)  The sensing bulb must be mounted above 

and between the 4 and 8 o’clock position 
on the circumference of the suction line. 

4)  The sensing bulb 

MUST

 be insulated from 

outside air. 

 

TXV BULB POSITION
4 O'CLOCK OR
8 O'CLOCK 

METAL STRAP

SUCTION/VAPOR LINE

 

 

Fig.4. Recommended  location of the TXV bulb in a 
horizontal orientation 
 

The mounting location and insulation guards the 
sensing bulb from false reading due to hot outside 
air or liquid refrigerant formed inside the 
suction/vapor line. 
 
As recommended earlier, the TXV sensing bulb 
should be mounted in a horizontal plane in relation 
to the suction/vapor line. However, in case such a 
mounting is not feasible and the sensing bulb has 

Summary of Contents for GAW18

Page 1: ..._________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE _________________________________________ T...

Page 2: ...modification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s re...

Page 3: ...determined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit These models have a bottom or front return Discard the drain access panel...

Page 4: ...poor system performance and possible compressor damage During some installations a piston change may be required If so the installer MUST change the piston As stated earlier use piston sizes recommend...

Page 5: ...tion of the TXV bulb has a major influence on the system performance CAUTION Ensure that the TXV bulb is in direct contact with the suction vapor line Gaps between the bulb and tube should be avoided...

Page 6: ...box and note the location of the inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw...

Page 7: ...10 kW are arranged for multi circuit protection Fig 7 shows the typical electrical connections required for the air handler unit Fig 7 Typical electrical connections required System Charging CAUTION...

Page 8: ...et and outlet For outlet measure temperature of each main trunk at a location far enough away to avoid heater radiation and read the average temperatures Table 3 below shows the CFM that should be ach...

Page 9: ...current protection in the form of circuit breakers Have your contractor identify the circuits and the location of over current protection so that you will be in a position to make inspections or repla...

Page 10: ...IO 123084 GAW 020113 2013 AirMark WARNING HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lead to safety hazard Wiring diagram for GAW models...

Reviews: