6. Maintenance/Adjustment
6
-
4
Symptom Cause Counter
measures
Even when operated
at a rated speed, no
voltage or too low
voltage generated.
(1) Faulty voltmeter
(2) Poor tightening of terminals
(3) Broken or short-circuited winding of
generator main unit
(4) Faulty AVR
(5) Faulty silicon rectifier (mounted on
generator main unit rotor)
(6) Faulty exciter
(7) Broken or short-circuited circuit to
exciter field winding
(8) Function circuit protector (CP) for AVR
protection
Check/change
Check/repair
Check/repair
Check/change
Check/change
Check/repair
Check/repair
Reset
Too high voltage
generated when set
at the rated
frequency
(50Hz/60Hz),
Voltage will not
drop even when the
voltage regulator
controlling knob is
turned.
(1) Loosened or disconnected wiring, or
connector to AVR
(2) Faulty AVR
(3) Broken wire or poor contact of AVR
variable resistor
Check/repair
Check/change
Repair or change
Unstable voltage
generation
(1) Poor tightening of each terminal
(2) Faulty AVR
(3) Function circuit protector (CP) for AVR
protection
Check/repair
Check/change
Reset
Please contact your nearest dealer if you find it difficult to repair by yourselves.
Please refer to the engine operation manual for troubles concerning the engine.
Summary of Contents for SDG45S-3A8
Page 1: ......
Page 3: ......
Page 11: ......
Page 15: ......
Page 19: ......
Page 32: ......
Page 34: ......
Page 35: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ...10 Piping Diagram 10 1 10 1 Fuel piping A080458E...
Page 62: ......
Page 63: ......