4. Operation
4
-
9
4.4.2 How to connect single phase load
The method of connection of 3 phase 4 wire single phase load is as follows.
The allowable current limit shall not exceed the values in the following table.
Conditions of Load
Allowable Current Limit
Conditions
In case of three phases
Allowable current limit up to
the rated current.
Adjust the load capacity so
that each current value of
each phase (U,V,W) may not
be more unbalanced than
50%.
In case of using 2 phas
es
In case of using single phase
Type
Permissible
current value
50Hz/200V 107A
60Hz/220V 118A
50Hz/380V 56.2A
50Hz/400V 53.4A
60Hz/440V 59.0A
Allowable current limit up to
the rate current.
But voltage change becomes
larger due to the unbalance
of each phase.
In case of three phases
Allowable current limit up to
the rated current.
Adjust the load capacity, so
that each current value of
each phase (U,V,W) may not
be more unbalanced than
50%.
3 phase 4 w
ire typ
e
In case of using O phas
e
In case of using single phase
Type
Permissible
current value
50Hz/115V
(200V)
107A
60Hz/127V
(220V)
118A
50Hz/219V
(380V)
56.2A
50Hz/231V
(400V)
53.4A
60Hz/254V
(440V)
59.0A
Allowable current limit up to
the rated current.
Bur the voltage change
becomes larger due to the
unbalance of each phase.
Summary of Contents for SDG45S-3A8
Page 1: ......
Page 3: ......
Page 11: ......
Page 15: ......
Page 19: ......
Page 32: ......
Page 34: ......
Page 35: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ...10 Piping Diagram 10 1 10 1 Fuel piping A080458E...
Page 62: ......
Page 63: ......