AirKing DL4S Important Instructions Manual Download Page 3

1b.  Internal Wire Compartment: If the motor is already installed in the housing, remove the 

two screws holding the blower assembly in place. Lift up on the assembly and slide it 

out of the tabs on the housing 

(Figure 6)

. Remove the wire compartment cover screw 

and place the cover in a secure place 

(Figure 7).

NOTE:

 If the fan motor plug is connected to the fan housing receptacle, unplug so the blower 

assembly can be completely removed.

Standard and Motion Sensing Models

2. 

Connect the White wire of the fan to the White (Neutral) wire from the power source. 

Connect the ground wire from the house to the green wire from the fan housing. Using 

a properly grounded three function switch (not included) connect the Black wire from 

the supply to the switch. Connect the Black wire (fan) from the fan housing to one of the 

terminals on the switch. Connect the Red wire (light) from the fan housing to a separate 

terminal on the switch. Connect the Purple wire (night light) from the fan housing to a 

separate terminal on the switch 

(Figure 8).

 Use approved methods for all connections.

www.airkinglimited.com

6727902 Rev. D 10-16

3 of 12

 

NOTE:

 There may be more than one white wire to be connected present.

NOTE:

 The fan’s receptacle wires might need to be pulled outside compartment for connection. 

Only pull the five loose wires outside of compartment. Additional wires will be present.

NOTE:

 Unit must be grounded according to all local and national codes.

Humidity Sensing Models

3a.  For proper operation the humidity sensing fan will require a 3 way switch (not included). 

Run wiring between the fan and the switch location. Make sure you leave enough wiring 

in each box to make the connections. At the switch box connect the black wire from the 

house to the common terminal of the switch. Connect the black wire from the fan to one 

of the switched terminals on the switch. This position will energize the automatic mode 

and the fan will energize upon a rise in humidity. Connect the yellow wire from the fan 

to the other switched terminal on the switch. This position will activate the Manual On 

feature and energize the fan. Properly connect the ground and neutral (if applicable) 

mount the switch and the cover.

 

NOTE:

 The yellow wire may contain a wire crimp nut which will have to be cut off and 

the wire stripped.

3b. 

Wiring the Fan: 

From where you have chosen to access the fan’s junction box, connect 

the white wire from the house to the white wire from the fan. Connect the wire from the 

automatic position on the wall switch to the black wire from the fan, connect the wire 

from the manual On position on the switch to the yellow wire from the fan. Connect the 

ground wire from the house to the green wire from the fan housing 

(Figure 10).

 Use 

approved methods for all connections.

 

NOTE:

 The yellow wire may contain a wire crimp nut which will have to be cut off and 

the wire stripped.

3c. 

Wiring the Lights:

 Using a properly grounded standard wall switch, connect the black 

wire from the supply to one side of the switch. Connect the Red wire (light) from the fan 

housing to one of the terminals on the switch. Connect the Purple wire (night light) from 

the fan housing to a separate terminal on the switch. 

(Figure 9). 

Use approved methods 

for all connections.

4. 

Carefully tuck wire back inside wire compartment and replace wire compartment cover 

securing with the screw that was removed earlier.

NOTE:

 The fan’s receptacle wires might need to be pulled outside compartment for connection. 

Only pull the five loose wires outside of compartment. Additional wires will be present.

NOTE:

 Unit must be grounded according to all local and national codes.

SECTION 6

Completing the Installation

1. 

Use a sealant appropriate for contact with the building materials present and for the 

temperature requirements of the installation to prevent air leakage from unconditioned 

spaces is recommended. If gaps between unit housing and ceiling are great, additional 

material (backing rod, ceiling material) may be required.

NOTE: 

This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan 

be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.

2. 

If the fan’s blower assembly was removed during the wiring process, reinstall the 

blower by reversing the directions in 

Section 5

 (Wiring), 

Step 1b.

 

Figure 5

Screw

Wire 

Compartment 

Cover

Screw

Wire Compartment 

Cover

Figure 7

NOTE:

 Wire compartment configuration 

will be dependent on model.

Figure 9

Supply from house

Black

Neutral (White)

Ground (Green or Bare)

Fan

Black

Neutral (White)

Green

Switch

Black

Purple

Red

Switch

Yellow

Figure 8

Supply from house

Black

Neutral (White)

Ground (Green or Bare)

Fan

Neutral (White)

Green

Switch

Black

Purple

Red

Tabs

Screws

Figure 6

34

5

6

7

8 9

101112

13
OFF

(x10)

Summary of Contents for DL4S

Page 1: ...bustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those pub...

Page 2: ...in the previously cut hole so that it is flush with the finished ceiling Secure the ends of the rails to the joists Figure 1 www airkinglimited com 6727902 Rev D 10 16 2 of 12 SECTION 4 Ducting NOTE...

Page 3: ...stripped 3b Wiring the Fan From where you have chosen to access the fan s junction box connect the white wire from the house to the white wire from the fan Connect the wire from the automatic positio...

Page 4: ...the button the number of times that corresponds with the amount of time you desire for instance 3 times sets the delay to 5 minutes see numbers in Step 1 The sensor will then flash the number of time...

Page 5: ...ITY SHALL TERMINATE UPON THE EXPIRATION OF THE WARRANTY PERIOD Some states and provinces do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or...

Page 6: ...Qty Description Replacement Part 7 1 Grill Assembly 5S1250105 8 1 Wire Compartment Assembly 5S1250105 Specific to Model DL4SG Qty Description Replacement Part 7 1 Grill Assembly 5S1250106 9 1 Wire Com...

Page 7: ...quipement de br lage au combustible pour pr venir un refoulement Suivre les directives du fabricant de l quipement de chauffage et les normes de s curit telles que celles publi es par la National Fire...

Page 8: ...ez avoir 1 Grille 1 Ensemble de clapet attach 4 Supports de montage 1 Bride de montage 1 Ampoule de type LED 1 Feuillet d instructions s curit 2 Choisir un emplacement pour votre ventilateur Pour gara...

Page 9: ...endroit o vous avez choisi d acc der la bo te de jonction du ventilateur connectez le fil blanc de la maison au fil blanc du ventilateur Connectez le fil de la position automatique sur l interrupteur...

Page 10: ...ui correspond la quantit de temps que vous d sirez par exemple 3 fois d finit le d lai de 5 minutes voir les num ros l tape 1 Le capteur clignote alors le nombre de fois pour le nouveau param tre 3 fo...

Page 11: ...s de la p riode de garantie ou l exclusion ou la restriction des dommages accidentels ou indirects et par cons quent les pr sentes restrictions ne peuvent pas s appliquer La pr sente garantie vous don...

Page 12: ...0105 Particularit s de mod le DL4SG Qt Description de pi ce de remplacement 7 1 Assembl e de Grille 5S1250106 9 1 Assembl e du compartiment du fil 5S1250108 Particularit s de mod le DL4SH Qt Descripti...

Reviews: