AirKing DL4S Important Instructions Manual Download Page 2

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Exhaust Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

exhaust fan you should have:

 

 

1 - Grill

 

 

1 - Damper Assembly (attached)

 

 

4 - Mounting Rails

 

 

1 - Mounting Flange

 

 

1 - LED Lamp

 

 

1 - Instruction/Safety Sheet   

2. 

Choose the location for your fan. To ensure the best air and sound performance, it is 

recommended that the length of ducting and the number of elbows be kept to a minimum, 

the radius of each elbow be as large as possible for the installation, and that insulated 

hard ducting be used. Larger duct sizes will reduce noise and airflow restrictions. This 

fan will require at least 10

 of clearance in the ceiling or wall, and will mount through 

drywall up to 3/4

 thick.

3. 

No additional vibration deadening materials are needed for this fan.

SECTION 2

New Construction

NOTE:

 If the mounting flange is installed on the fan housing, remove the two screws that 

connect the ceiling mounting flange to the housing and set aside 

(Figure 12).

1. 

Install the rails into the mounting channel on the housing. Center the mounting channel in 

the slots on the housing, then from inside the housing tighten the mounting channel nuts 

so the channel is securely in place. Position the housing next to the joist. Line up housing 

so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or 

nails (not included) to the joists and slide the housing into the final position 

(Figure 1).

SECTION 3

Existing Construction

NOTE:

 If the mounting flange is installed on the fan housing, remove the two screws that 

connect the ceiling mounting flange to the housing and set aside 

(Figure 12).

1. 

Set housing in position between the joist and trace an outline onto the ceiling material 

(Figure 2).

 Set housing aside and cut opening, being careful not to cut or damage any 

electrical or other hidden utilities. Install the rails into the mounting channel on the 

housing. Center the mounting channel in the slots on the housing, then from inside the 

housing tighten the mounting channel nuts so the channel is securely in place. Position 

the housing in the previously cut hole so that it is flush with the finished ceiling. Secure 

the ends of the rails to the joists 

(Figure 1).

www.airkinglimited.com

6727902 Rev. D 10-16

2 of 12

SECTION 4

Ducting

NOTE: 6" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND 

NATIONAL BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible 

for best performance, and avoid installing the fan with smaller ducts than recommended. 

Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed 

with existing ducts may not achieve their rated air flow.
1. 

Connect the ducting to the fan’s duct collar 

(Figure 3).

 Secure in place using tape 

or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is 

recommended that low restriction termination fittings be used.

2. 

Ensure duct joints and exterior penetrations are sealed with caulk or other similar 

material to create an air-tight path to minimize building heat loss or gain and to reduce 

the potential for condensation. Place/wrap insulation around duct and/or fan to in order 

to minimize possible condensation buildup within the duct, as well as building heat loss 

or gain 

(Figure 4).

SECTION 5

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE 

MADE IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR 

NATIONAL ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING 

ELECTRICAL WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.

NOTE:

 This unit includes a side access panel for wiring that does not require the removal of the 

fan’s blower assembly. If you choose to wire the unit from the inside, you will need to remove 

the blower assembly and internal wiring compartment. Both methods are equally effective.

1a.  External Wire Compartment: Remove the wire compartment cover screw and place 

cover in a secure place 

(Figure 5).

Ducting

Duct 

Collar

Figure 3

Figure 2

Joist

Housing

Joist

Mounting Rails

Figure 1

Figure 4

Insulation* 

(place around and 

over Fan Housing

Fan Housing

Power Cable*

Seal gaps 

around Housing

Round 

Duct*

Seal duct joints 

with tape

Round 

Elbows*

Wall Cap*

Roof Cap* 

(with built-in 

damper)

Keep duct 

runs short

*Purchase separately

or

Summary of Contents for DL4S

Page 1: ...bustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those pub...

Page 2: ...in the previously cut hole so that it is flush with the finished ceiling Secure the ends of the rails to the joists Figure 1 www airkinglimited com 6727902 Rev D 10 16 2 of 12 SECTION 4 Ducting NOTE...

Page 3: ...stripped 3b Wiring the Fan From where you have chosen to access the fan s junction box connect the white wire from the house to the white wire from the fan Connect the wire from the automatic positio...

Page 4: ...the button the number of times that corresponds with the amount of time you desire for instance 3 times sets the delay to 5 minutes see numbers in Step 1 The sensor will then flash the number of time...

Page 5: ...ITY SHALL TERMINATE UPON THE EXPIRATION OF THE WARRANTY PERIOD Some states and provinces do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or...

Page 6: ...Qty Description Replacement Part 7 1 Grill Assembly 5S1250105 8 1 Wire Compartment Assembly 5S1250105 Specific to Model DL4SG Qty Description Replacement Part 7 1 Grill Assembly 5S1250106 9 1 Wire Com...

Page 7: ...quipement de br lage au combustible pour pr venir un refoulement Suivre les directives du fabricant de l quipement de chauffage et les normes de s curit telles que celles publi es par la National Fire...

Page 8: ...ez avoir 1 Grille 1 Ensemble de clapet attach 4 Supports de montage 1 Bride de montage 1 Ampoule de type LED 1 Feuillet d instructions s curit 2 Choisir un emplacement pour votre ventilateur Pour gara...

Page 9: ...endroit o vous avez choisi d acc der la bo te de jonction du ventilateur connectez le fil blanc de la maison au fil blanc du ventilateur Connectez le fil de la position automatique sur l interrupteur...

Page 10: ...ui correspond la quantit de temps que vous d sirez par exemple 3 fois d finit le d lai de 5 minutes voir les num ros l tape 1 Le capteur clignote alors le nombre de fois pour le nouveau param tre 3 fo...

Page 11: ...s de la p riode de garantie ou l exclusion ou la restriction des dommages accidentels ou indirects et par cons quent les pr sentes restrictions ne peuvent pas s appliquer La pr sente garantie vous don...

Page 12: ...0105 Particularit s de mod le DL4SG Qt Description de pi ce de remplacement 7 1 Assembl e de Grille 5S1250106 9 1 Assembl e du compartiment du fil 5S1250108 Particularit s de mod le DL4SH Qt Descripti...

Reviews: