4.0  Installation overview soffit element

Installation requirements soffit element:

1. Wall thickness of uncovered wall: min. 240 mm to max. 480 mm

2. Insulation panel thickness: min. 100 mm

3. Horizontal distance from core drilling hole to soffit (ready-mix plaster): min. 220 mm to max. 500 mm (see Fig. 6)

4. Vertical distance from core drilling hole to window lintel: min. 300 mm

5. Note the installation instructions for shutters and blinds in Figure 4!

6. Can be used for fire protection class B1 (flame resistant)

CHAPTER 4 

POSITIONING/

ASSEMBLY

 m 

NOTE

ò

Length of wall installation sleeve

Max.: 500 mm

Min.: 300 mm
The  length  of  the  wall  installation  sleeve 

comprises the thickness of the uncovered 

wall with internal ready-mix plaster, the height 

of the feet (

ä

) of the soffit channel and the 

immersion depth (

ù

) in the soffit channel 

(see Fig. 4 & 5).

NOTE:

 The length of the wall installation 

sleeve should be adjusted so that there are 

no collisions in the area of the shutter rail.

ù

Immersion depth of the wall installation

sleeve in the soffit element

Length: 20 mm

NOTE:

 The wall installation sleeve must 

not

 be cut off flush with the wall on the outside!

ä

Soffit channel feet

Max.: 40 mm

Min.: 0 mm
The soffit channel feet determine how far it 

sits from the uncovered wall. The height of 

the feet and the height of the soffit channel 

of 100 mm corresponds to the min. insulation 

thickness.  If  necessary,  the  feet  can  be 

underpinned .

ë

Distance from core drilling hole (centre)

to the end of the soffit channel

Max.: 480 mm

Min.: 200 mm
The 

adjustable

  length  of  the  channel  must 

be  selected  depending  on  the  distance 

between the core drilling hole (centre) to the 

ready-mix plaster in the window soffit. This 

distance minus the height of the shortened 
plaster frame (

ö

) provides the length of the 

shortenable area 

ë

 .

ö

Height of the plaster frame

Max.: 35 mm

Min.: 15 mm
The height of the plaster frame bridges the 

distance  between  the  soffit  channel  and 

the wall grille. The height must be selected 

depending on the thickness of the window 

soffit insulation and the ready-mix plaster. 

The  plaster  frame  allows  for  tolerance 

compensation.

A minimum height of 20 mm is recommended 

for the plaster frame.

Fig.4

Soffit channel 

(adjustable)

Window

Ready mix plaster

 Wall insulation sleeve 

( min. 300 )

(adjustable area)

 min. 280 

 200 

 20 ± 3 

 120 

 Uncovered wall+ready mix plaster 

Soffit channel

 100

 74 

 Insulation thickness 

(adjustable area)

 15 - 35 

 0 - 280 

 18 

 320 

Over-insulation

Insulation Ready mix 

plaster

Wall grille with 

condensation 

drain

 Plaster frame (shortened)

Ready 

mix 
plaster 

Insulation window soffit

Summary of Contents for 8QRKDE

Page 1: ...t Kit Installation and Operating Instructions Airflow we reserve the right to make changes without prior notice External wall insulation vent kit 8QR KDE WHUQDO ZDOO LQVXODWLRQ YHQW NLW INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ... Contr oller kit Unoh ab CTRL kit flush Part No 90000994 Uno hab CTRL kit DIN rail Part No 90000995 Switching power supply Uno hab PSF Part No 90000996 included in Uno hab CTRL SET Uno hab PSD Part No 90000996 included in Uno hab CTRL DIN MAX 8 units Attention if necessary additional power supply required Output 12 V control line Output 12 V control line Input 230 V optional Additional power suppl...

Page 3: ...on of liability Page 5 2 1 Certificates Guidelines Page 5 2 2 Shipping Page 5 2 3 Receipt Page 5 2 4 Driving rain impermeability of the stainless steel wall grille Page 5 2 5 Limits of use stainless steel Page 5 CHAPTER 3 SCOPE OF DELIVERY Page 6 3 0 Scope of delivery Page 6 3 1 Dimensions Page 6 CHAPTER 4 POSITIONING ASSEMBLY Page 74 0 Installation overview soffit element Page 7 4 1 Positioning c...

Page 4: ...unit Depending on the overall ventilation requirement of the residential unit more than 2 units are normally installed and the individual volume flows are automatically adjusted by means of the central control unit The standard equipment allows installation and use in frost free rooms 5 C When operating under difficult conditions such as high levels of humidity long standstill periods excessive lo...

Page 5: ... in the original packaging 2 3 Receipt The shipment Uno hab Ext Wall Ins Vent Kit part number 90001002 must be checked for damage and correctness immediately upon delivery If there is any damage promptly report the damage with the assistance of the transport company If complaints are not made within the agreed period any claims could be lost 2 4 Driving rain impermeability of the stainless steel w...

Page 6: ...with labelling middle bottom ä EPP soffit channel ë EPP plaster frame ö Condensate discharge plate ü Wall grille incl seal for wall connection Å Fixing material 2x Insulation fixing 2x Stainless steel screw Ø 4 5 x 50 mm 4x Stainless steel screw Ø 5 x 100 mm 4x Stainless steel screw Ø 6 4 mm î Protective cover 2x for inside and outside Ø EPP fixing wedges 3 1 Dimensions fig 1 CHAPTER 3 SCOPE OF DE...

Page 7: ...rail ù Immersion depth of the wall installation sleeve in the soffit element Length 20 mm m NOTE The wall installation sleeve must not be cut off flush with the wall on the outside ä Soffit channel feet Max 40 mm Min 0 mm The soffit channel feet determine how far it sits from the uncovered wall The height of the feet and the height of the soffit channel of 100 mm corresponds to the min insulation ...

Page 8: ... with gradient to outside is required for the unit installation or Ø 172 mm horizontal with condensate wedge Include the empty conduit for the electr control cable in the installation wall NOTE The empty conduit must be placed below the unit installation position 1 Determine the position of the core drilling hole for the soffit element see Fig 6 2 Execute core drilling 3 Provide empty conduit for ...

Page 9: ...ll annular gap inside and outside with non pressurised installation foam Fig 9 10 9 After a sufficient drying time remove the protruding fixing wedges and excess installation foam If necessary remove EPP material lower front wedge and any installation foam residue for cable entry Fig 9 10 Create diffusion tight seal on annular gap Fig 10 11 Place protective cover on the wall installation sleeve In...

Page 10: ...ore drilling points for the soffit channel and remove the soffit channel 6 Drill the drilling holes and insert dowels not included 7 Connect soffit channel to the wall sleeve and screw in Fig 13 washers and screws are included 8 Apply thin glue sealing beads to the plaster frame Fig 14 9 Connect plaster frame to the soffit element and screw in with the enclosed insulation fixings Fig 14 15 10 Back...

Page 11: ...thout prior notice 11 Attach surrounding insulation panels Fig 16 12 Attach any plaster corner rails 13 Plaster the soffit channel and plaster frame 14 Remove any protruding plaster frame with multitool Fig 17 15 Insert condensate pan Fig 18 16 Mount wall grille Fig 19 The screws are included Fig 18 Fig 19 Fig 16 Fig 17 ...

Page 12: ...g periods condensation can form in the heat accumulator due to the process of heat recovery The condensation water must be able to drain from the unit A condensate drain gradient of 1 2 is ensured during installation by the EPP front wedge which is pre mounted to the wall installation sleeve TheprotrusionofthecondensatedraininthelowerEPPhalfshellallowsfreecondensatedrainageinthesoffitchannel from ...

Page 13: ...Uno hab Ext Wall Ins Vent Kit Installation and Operating Instructions 13 Airflow we reserve the right to make changes without prior notice Notes ...

Page 14: ...Uno hab Ext Wall Ins Vent Kit Installation and Operating Instructions 14 Airflow we reserve the right to make changes without prior notice Notes ...

Page 15: ...Uno hab Ext Wall Ins Vent Kit Installation and Operating Instructions 15 Airflow we reserve the right to make changes without prior notice Notes ...

Page 16: ...cations without prior notice All orders are accepted subject to our conditions of sale which are available on request Certificate No EMS 569454 BS EN 1SO 14001 2015 Certificate No FM 00152 BS EN 1SO 9001 2015 Airflow Developments Limited Aidelle House Lancaster Road Cressex Business Park High Wycombe Buckinghamshire United Kingdom HP12 3QP Call 01494 525252 Visit airflow com 80000782 Issue 2 09 20...

Reviews: