Uno hab Ext. Wall Ins. Vent Kit
Installation and Operating Instructions
7
© Airflow
-
we reserve the right to make changes without prior notice
4.0 Installation overview soffit element
Installation requirements soffit element:
1. Wall thickness of uncovered wall: min. 240 mm to max. 480 mm
2. Insulation panel thickness: min. 100 mm
3. Horizontal distance from core drilling hole to soffit (ready-mix plaster): min. 220 mm to max. 500 mm (see Fig. 6)
4. Vertical distance from core drilling hole to window lintel: min. 300 mm
5. Note the installation instructions for shutters and blinds in Figure 4!
6. Can be used for fire protection class B1 (flame resistant)
CHAPTER 4
POSITIONING/
ASSEMBLY
m
NOTE
ò
Length of wall installation sleeve
Max.: 500 mm
Min.: 300 mm
The length of the wall installation sleeve
comprises the thickness of the uncovered
wall with internal ready-mix plaster, the height
of the feet (
ä
) of the soffit channel and the
immersion depth (
ù
) in the soffit channel
(see Fig. 4 & 5).
m
NOTE:
The length of the wall installation
sleeve should be adjusted so that there are
no collisions in the area of the shutter rail.
ù
Immersion depth of the wall installation
sleeve in the soffit element
Length: 20 mm
m
NOTE:
The wall installation sleeve must
not
be cut off flush with the wall on the outside!
ä
Soffit channel feet
Max.: 40 mm
Min.: 0 mm
The soffit channel feet determine how far it
sits from the uncovered wall. The height of
the feet and the height of the soffit channel
of 100 mm corresponds to the min. insulation
thickness. If necessary, the feet can be
underpinned .
ë
Distance from core drilling hole (centre)
to the end of the soffit channel
Max.: 480 mm
Min.: 200 mm
The
adjustable
length of the channel must
be selected depending on the distance
between the core drilling hole (centre) to the
ready-mix plaster in the window soffit. This
distance minus the height of the shortened
plaster frame (
ö
) provides the length of the
shortenable area
ë
.
ö
Height of the plaster frame
Max.: 35 mm
Min.: 15 mm
The height of the plaster frame bridges the
distance between the soffit channel and
the wall grille. The height must be selected
depending on the thickness of the window
soffit insulation and the ready-mix plaster.
The plaster frame allows for tolerance
compensation.
A minimum height of 20 mm is recommended
for the plaster frame.
Fig.4
Soffit channel
(adjustable)
Window
Ready mix plaster
Wall insulation sleeve
( min. 300 )
(adjustable area)
min. 280
200
20 ± 3
120
Uncovered wall+ready mix plaster
Soffit channel
100
74
Insulation thickness
(adjustable area)
15 - 35
0 - 280
18
320
Over-insulation
Insulation Ready mix
plaster
Wall grille with
condensation
drain
Plaster frame (shortened)
Ready
mix
plaster
Insulation window soffit