Chillers
ULTIMA FREECOOL
Chillers
Installation & Maintenance Manual : 903-125 IM E 05/04/A
21
Installation Data
ELECTRICAL DATA
Model
UFC350D-10
UFC400D-10
UFC450D-12 UFC500D-12
UFC575D-14
Unit Data
(1)
Nominal Run Amps
(2) A
212
236
275
308
347
Maximum Start Amps
A
432
456
531
564
643
Permanent Supply
VAC
230V 1PH 50Hz
Mains Supply
VAC
400V 3PH 50Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Rec Mains Fuse Size
A
315
355
400
400
450
Max Permanent Incoming Cable
Size
mm² 4mm²
Terminal
Max Mains Incoming Cable Size mm²
Direct to Bus Bar
Control Circuit
VAC
24V / 230VAC
Evaporator
Trace Heater Rating
W
250
250
250
250
250
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Condenser Fan - Per Fan
Full Load Amps
A
2.60
2.60
2.60
2.60
2.60
Locked Rotor Amps
A
15.00
15.00
15.00
15.00
15.00
Motor Rating
kW
1.70
1.70
1.70
1.70
1.70
Compressor - Per Compressor
Motor Rating
kW
62 + 48
62 + 62
81 + 62
81 + 81
109 + 81
Nominal Run Amps
(2) A
105 + 81
105 + 105
138 + 105
138 + 138
173 + 138
Crankcase Heater Rating
W
150
150
150
150
150
Start Amps
(3)
325 + 234
325 + 325
394 + 325
394 + 394
469 + 394
Type Of Start
Star / Delta
QUIET DQ
UFC350DQ-12
UFC400DQ-12
UFC450DQ-14
UFC500DQ-14
UFC575DQ-16
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
1.75
1.75
1.75
1.75
1.75
Locked Rotor Amps
A
6.20
6.20
6.20
6.20
6.20
Motor Rating
kW
0.98
0.98
0.98
0.98
0.98
SUPER QUIET DSQ
UFC350DSQ-14 UFC400DSQ-14 UFC450DSQ-16
UFC500DSQ-16 UFC575DSQ-18
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
1.15
1.15
1.15
1.15
1.15
Locked Rotor Amps
A
2.10
2.10
2.10
2.10
2.10
Motor Rating
kW
0.70
0.70
0.70
0.70
0.70
OPTIONAL EXTRAS -
Fitted to standard D models - for data on DQ & DSQ please refer to Airedale.
Power Factor Correction
Nominal Run Amps
(2) A
192
214
249
278
314
Maximum Start Amps
(3) A
432
456
531
564
643
Recommended Mains
Fuse
A
315
315
355
400
400
Compressor Nominal
Run Amps - Per
Compressor
A
94 + 72
94 + 94
123 + 94
123 + 123
155 + 123
Closed Transition
Nominal Run Amps
(2) A
212
236
275
308
347
Maximum Start Amps
A
432
456
531
564
643
Recommended Mains
Fuse
A
315
355
400
400
450
Compressor Nominal
Run Amps - Per
Compressor
A
105 + 81
105 + 105
138 + 105
138 + 138
173 + 138
(1)
Refers to standard speed fans.
(2)
Based at 12/7°C water and 30°C ambient
(3)
Starting amps refers to the Star connection only.