AIREDALE AIR 1-550.30 Installation And Service Manual Download Page 9

9

lbs. 

STEAM

60° ENT. AIR

STEAM PERFORMANCE DATA - LOW OUTLET TEMPERATURE MODELS

j

Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold. 

k

 CFM for horizontal types is entering CFM. CFM for vertical and “Power-Throw” types is leaving CFM.

l

 WVC and WPC models have copper tubes, WVN and WPN models have 90/10 cupro-nickel tubes.

m

 Requires Solid State Motor Speed Controller. 

AIR 1-550.29

Table 9.2 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 

2 lb. Steam and 60°F Entering Air Reduced Motor Speed 

Table 9.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of  

2 lb. Steam and 60°F Entering Air High Motor Speed

Type

Model No.

Btu/hr

Sq. Ft. 

EDR

Air Data

Motor Data

Maximum 

Mounting 

Height (ft.)



Heat Throw  

or Spread @ 

Max. Height 



CFM

‚

Outlet 

Velocity 

(Fpm)

Final Air 

Temp. 

(°F)

Condensate 

lb/hr

Hp

Approx. 

RPM

Horizontal 

Delivery

WTC/WSC 18L

15,900

66

9

20

364

655

100

16

1/60

1,550

WTC/WSC 24L

19,300

80

11

21

435

795

100

20

1/25

1,550

WTC/WSC 33L

29,500

123

12

24

695

745

99

31

1/25

1,550

WTC/WSC 47L

32,000

133

14

32

855

910

94

33

1/12

1,550

WTC/WSC 63L

52,500

219

16

33

1,170

710

101

54

1/12

1,550

WTC/WSC 86L

61,500

256

17

36

1,510

910

97

64

1/8

1,625

WTC/WSC 108L

86,500

360

19

36

2,150

825

97

90

1/8

1,625

WTC/WSC 121L

88,000

367

18

29

2,070

800

98

91

1/5

1,075

WTC/WSC 165L

143,000

596

21

45

3,480

930

97

148

1/3

1,075

WTC/WSC 258L

190,000

792

22

51

4,655

750

98

197

1/2

1,075

WTC/WSC 290L

207,000

863

23

53

5,040

805

94

214

1/2

1,075

WTC/WSC 340L

255,000

1,063

23

53

5,575

775

102

264

1/2

1,075

Power- 

Throw™

ƒ

WPC/WPN 610L

470,000

1,958

22

154

2,400

2,445

97

486

1 1/2

1,140

Vertical

Delivery

ƒ

WVC 42L

33,000

138

13

17

20

13

960

835

94

34

1/30

1,050

WVC 59L

44,000

183

16

22

24

16

1,190

1,035

96

45

1/30

1,050

WVC 78L

62,000

258

19

26

29

19

1,740

1,070

95

65

1/15

1,050

WVC 95L

71,000

296

19

26

29

19

1,760

1,180

99

73

1/15

1,050

WVC/WVN 139L

103,000

429

23

31

35

23

2,860

1,380

95

106

1/6

1,075

WVC/WVN 161L

127,000

529

26

35

39

26

3,400

1,640

96

132

1/3

1,075

WVC/WVN 193L

149,000

621

27

36

41

27

3,710

1,790

99

154

1/3

1,075

WVC/WVN 212L

163,000

679

27

36

41

27

3,830

1,845

102

169

1/3

1,075

WVC/WVN 247L

190,000

792

32

42

48

32

5,110

2,030

96

197

1/2

1,075

WVC/WVN 279L

215,000

896

36

45

54

36

5,790

2,300

96

222

1/2

1,075

WVC/WVN 333L

256,000

1,067

36

45

54

36

6,340

2,300

100

265

3/4

1,140

WVC/WVN 385L

296,000

1,233

36

43

54

36

8,140

1,970

95

307

1

1,140

WVC/WVN 500L

385,000

1,604

45

54

68

45

11,000

2,670

94

400

1 1/2

1,140

WVC/WVN 610L

470,000

1,958

44

52

66

44

12,400

2,445

97

485

1 1/2

1,140

WVC 952L

733,000

3,055

45

 

68

 

12,940

2,450

115

759

2

1,140

Type

Model No.

Btu/hr

Sq. Ft. 

EDR

 Air Data

Motor Data

Maximum 

Mounting 

Height (ft.)



Heat Throw  

or Spread @ 

Max. Height 



CFM

‚

Outlet 

Velocity 

(Fpm)

Final Air 

Temp. 

(°F)

Condensate 

lb/hr

Hp

Approx. 

RPM

Horizontal 

Delivery

WTC/WSC 18L

12,000

51

9

12

230

425

108

12

1/60

1,000

WTC/WSC 24L

14,400

60

11

13

265

490

109

15

1/25

1,000

WTC/WSC 33L

22,000

92

12

14

430

470

107

23

1/25

1,000

WTC/WSC 47L

24,300

101

14

19

540

580

101

25

1/12

1,000

WTC/WSC 63L

39,500

164

16

20

725

445

109

41

1/12

1,000

WTC/WSC 86L

46,000

192

17

22

925

565

105

48

1/8

1,000

WTC/WSC 108L

65,000

270

19

22

1,330

520

104

67

1/8

1,000

Summary of Contents for AIR 1-550.30

Page 1: ... rating for national electric code ignition temperature rating T3B for grain dust Motors are designed for continuous duty They can operate in a maximum ambient temperature of 104 F 40 C The unit heaters are listed by the Canadian Standards Association as certified and Canadian Registered heat exchangers CRN OH 9234 5C Does not apply to WVC WPC 952 Steam horizontal and vertical delivery unit heater...

Page 2: ... atmosphere WARNING 1 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 2 All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance Any wiring different from the wiring diagram could result in a hazard to persons and property 3 Any original factory wiring that requires replacement must be replaced wi...

Page 3: ...re listed in Table 4 1 and the height dimensions are shown in Figures 4 3 through 4 7 Maximum mounting heights for vertical models are given for units with or without optional air deflectors The data in Table 4 1 is based on operating conditions of 2 lbs steam or 220 F entering water with 60 F entering air When operating conditions are other than those above refer to Figure 4 2 for maximum mountin...

Page 4: ...m pressures other than 2 pounds or with water at other than average temperature of 220 F Table 4 1 Maximum Mounting Heights UNIT MOUNTING Figure 4 2 Maximum Mounting Heights Correction Factors H Figure 4 6 Vertical Truncone Horizontal Type Power Throw Type Vertical Type with Deflectors No Deflector Cone Jet Truncone Louvers Model No Height ft Model No Height ft Model No Height ft Height ft Height ...

Page 5: ...5 greater than the rated voltage 5 CAUTION 1 Do not install units below 8 feet measured from the bottom of the unit to the floor 2 Do not reuse any electrical component which has been wet Replace component 3 Ensure that the supply voltage to the appliance as indicated on the serial plate is not 5 less than the rated voltage Piping See Figure 6 1 1 Branch piping to and from unit heater should inclu...

Page 6: ...nd must be connected according to wiring diagram with each controller Prior to Operation 1 Make sure fuses are installed in fused disconnect switches 2 Check all electrical connections to assure they are secure 3 Check rigidity of unit mounting Tighten all fasteners if necessary 4 Inspect piping strainers traps fittings etc Initial Start Up 1 Set thermostat to lowest position 2 Turn on power suppl...

Page 7: ...ptional Casings Electrostatically applied gray green polyester powder coat paint finish is applied over rust and corrosion treated steel for long life Motor Cooling Cone Shields motor from coil heat prolongs life of insulation windings and lubricant Prolongs motor life Coil Aluminum fins mechanically bonded to tubes for maximum heat transfer All steam and water carrying passages between heavy stee...

Page 8: ...15 112 631 1 1 2 1 140 WPC 952 952 000 3 967 21 145 12 170 2 321 139 985 2 1 140 Vertical Delivery WVC WVN 42 42 000 175 11 15 17 11 950 825 103 43 1 30 1 050 WVC WVN 59 59 000 246 14 19 21 14 1 155 1 005 111 61 1 30 1 050 WVC WVN 78 78 000 325 15 20 23 15 1 590 1 065 109 81 1 15 1 050 WVC WVN 95 95 000 396 15 20 23 15 1 665 1 120 118 98 1 15 1 050 WVC WVN 139 139 000 579 18 24 27 18 2 660 1 285 1...

Page 9: ... 53 5 040 805 94 214 1 2 1 075 WTC WSC 340L 255 000 1 063 23 53 5 575 775 102 264 1 2 1 075 Power Throw WPC WPN 610L 470 000 1 958 22 154 2 400 2 445 97 486 1 1 2 1 140 Vertical Delivery WVC 42L 33 000 138 13 17 20 13 960 835 94 34 1 30 1 050 WVC 59L 44 000 183 16 22 24 16 1 190 1 035 96 45 1 30 1 050 WVC 78L 62 000 258 19 26 29 19 1 740 1 070 95 65 1 15 1 050 WVC 95L 71 000 296 19 26 29 19 1 760 ...

Page 10: ... 279 192 300 20 0 0 2 4 5 60 0 17 108 5 460 2 165 94 1 2 1 075 WPC WPN 333 238 500 24 8 0 4 4 5 100 0 18 117 5 980 2 165 99 3 4 1 140 WPC WPN 385 276 100 28 8 0 6 4 5 100 0 18 124 7 680 1 860 95 1 1 140 WPC WPN 500 358 000 37 3 0 5 6 0 100 0 19 138 10 390 2 520 93 1 1 2 1 140 WPC WPN 610 450 400 46 9 1 0 6 0 100 0 22 151 11 750 2 315 97 1 1 2 1 140 WPC 952 721 600 75 2 1 1 14 0 200 0 23 150 12 166...

Page 11: ... 89 1 2 1 075 WTC WSC 290L 161 100 16 8 3 7 2 5 70 0 25 57 5 040 800 89 1 2 1 075 WTC WSC 340L 200 900 20 9 6 6 2 5 70 0 25 57 5 575 760 93 1 2 1 075 Power Throw WPC WPN 610L 344 900 35 9 0 6 6 0 100 0 24 158 12 400 2 445 86 1 1 2 1 140 Vertical Delivery WVC 42L 23 000 2 4 0 4 0 5 10 0 14 18 21 14 960 835 83 1 30 1 050 WVC 59L 32 600 3 4 0 3 0 8 15 0 17 23 25 17 1 190 1 035 86 1 30 1 050 WVC 78L 4...

Page 12: ... 34 WSC 47 15 17 1 2 8 3 4 8 12 1 4 11 3 5 8 6 10 3 4 12 35 WSC 63 18 1 2 21 1 2 8 3 4 8 12 3 4 15 3 5 8 6 14 3 4 12 48 WSC 86 18 1 2 21 1 2 8 3 4 9 12 3 4 15 3 5 8 6 14 3 4 14 52 WSC 108 22 1 2 25 1 2 9 1 2 8 11 1 2 18 3 5 8 6 3 8 18 3 4 18 74 WSC 121 22 1 2 25 1 2 9 1 2 7 1 2 11 18 3 5 8 6 3 8 18 3 4 18 76 WSC 165 26 1 2 29 1 2 9 1 4 9 1 2 14 21 1 4 3 5 8 6 3 8 22 3 4 22 92 WSC 193 30 1 2 32 1 2...

Page 13: ... 1 1 2 1 70 WVC WVN 161 34 3 4 8 3 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 80 WVC WVN 193 34 3 4 9 7 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 86 WVC WVN 212 34 3 4 12 7 8 18 3 8 2 1 2 3 19 1 2 19 2 1 1 4 94 WVC WVN 247 34 3 4 12 7 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 108 WVC WVN 279 34 3 4 14 3 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 112 WVC WVN 333 43 1 4 14 5 8 31 1 2 2 7 8 3 1 8 22 1 2 18 1 5 22 2 1 2 1 1 2 166 ...

Page 14: ...otor damage Check plant voltage conditions A separate manual starter with thermal overload protection device is recommended for those units that do not have motors with built in overload protection Coils 1 Clean coil at least once a year more often under unfavorable conditions Unless coil is kept reasonably free of dirt lint and grease its original heating capacity will be reduced possibly to a se...

Page 15: ...ing in too high air temperature 6 Restricted air flow due to clogged coil or closed louvers 7 Fan out of balance 8 Unbalanced voltage on 3φ power Coil Failure Unit Leaks 1 Severe internal corrosion from feedwater 2 Type of boiler treatment 3 Entrained air causing water hammer 4 Continuous operation above 150 PSI 375 F steam systems 5 Loose connection Table 15 1 Troubleshooting Replacement Parts Wh...

Page 16: ...UIPMENT MANUFACTURED BY BUYER BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER FOR GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the origin...