AIREDALE AIR 1-550.30 Installation And Service Manual Download Page 15

AIR 1-550.30

15

SERVICE / TROUBLESHOOTING

Fails to Maintain Temperature

1. Undersized unit heater, boiler, pump or piping.

2.  Unit heater operating at low speed when sized for high speed.

3.  Unit heater mounted too high — heated air not delivered to floor. 

4. Thermostat — improper location or setting, or not  functioning.

5. Dirty or clogged coil.

Unit Blows Cold Air

1. Manual shut-off valve closed.

2. Insufficient steam pressure of lack of hot water.

3. Aquastat not functioning.

4. Improper venting.

5. Steam trap not functioning.

6. Drip leg too short (steam system).

7. Return line plugged (steam system).

8. Pump undersized or not operating (hot water system).

Does Not Operate When Heat Needed

1. Defective motor or electrical connections.

2. Thermostat, aquastat or pressure limit control not functioning.

Fails to Deliver Heat to Floor

1. Units mounted too high.

2. Operating on low speed.

3. Final air temperature too high.

4. Louvers not adjusted properly.

5. Wrong type of diffuser (on verticals).

6. Undersized unit heater (insufficient air delivery).

7. Wrong type of unit (may require vertical delivery).

8. Cross ventilation or drafts.

9. Obstructions to air flow.

Noisy Unit

1. Loose bolts or screws.

2. Fan blade bent, out of balance.

3. Dirt accumulation on fan blades.

4. Fan hub or blade rivets loose.

5. Motor shaft bearing worn.

6. Motor mounting bent, fan not positioned properly in venturi.

7. Conduit too rigid, transmits vibration noise.

8. BX cable touching unit heater, chatters as casing vibrates.

Employees Complain of Hot Blast

1. Air stream aimed directly at employees.

2. Louvers not adjusted properly.

3. Wrong type of diffuser (on verticals).

4. Excessive final air temperature.

Unit Operates Too Long

1. Thermostat installed on cold wall or other improper location.

2. Aquastat or pressure limit control not functioning properly.

3. Unit is undersized.

Frequent Motor Failure

1. Voltage fluctuations too high or too low.

2. Excessive or insufficient lubrication.

3. Wiring to motor undersized.

4. Improper electrical connections.

5. Motor operating in too high air temperature.

6.  Restricted air flow due to clogged coil or closed louvers.

7. Fan out of balance.

8. Unbalanced voltage on 3

φ

 power.

Coil Failure/Unit Leaks

1. Severe internal corrosion from feedwater.

2. Type of boiler treatment.

3. Entrained air causing water hammer.

4. Continuous operation above 150 PSI (375°F)(steam systems).

5. Loose connection.

Table 15.1 - Troubleshooting

Replacement Parts

When requesting parts please contact your local representative. 

Please have full model and serial number available. See  

Figure 15.1.

2.  For thorough cleaning of coil, remove motor and fan and 

spray a mild alkaline cleaning solution over the coil. After a 

few minutes, follow by a hot water rinse. (A steam gun can be 

used for spraying cleaning solution and hot water.)

3.  Coils subjected to corrosive fumes should be checked and 

cleaned frequently.

4.  Provide controlled water treatment — don’t use excess of 

boiler compounds. Contact your boiler compound supplier for 

proper usage or the services of a water treatment laboratory.

5.  Periodic internal flushing of the coils is recommended in 

areas where water supply is suspected of causing scale. Use 

an alkaline-chelant solution and introduce it at the main pump 

of the hydronic system. Flush thoroughly.

WARNING: 

USING INORGANIC OR MINERAL ACIDS SUCH 

AS MURIATIC (HYDROCHLORIC) ACID, EVEN THOUGH 

INHIBITED, MAY LEAD TO SEVERE DAMAGE, INCLUDING 

CORROSION AND LEAKAGE.
6.  De-aerate boiler feed-water (particularly if large amount of 

new water is used).

7.  Insure rapid continuous and adequate condensate drainage 

by properly sized and installed traps and piping. Check traps 

for sticking. Clean strainers ahead of traps. (When traps 

don’t work, condensate accumulates in unit heater coil; water 

hammer results.)

8.  Adequately vent each unit.
9.  Use low pressure steam when possible. 

Casings

1.  

Periodic cleaning of casings is recommended to remove 

dirt, grease and corrosive substances that may injure finish. 

Rusted or corroded spots should be cleaned and repainted.

2.  

Tighten fan guard and motor bracket. Check fan for proper 

clearance, free rotation and firm connection to shaft.

   When servicing is complete, tag unit to indicate date of 

inspection, lubrication and cleaning. 

Summary of Contents for AIR 1-550.30

Page 1: ... rating for national electric code ignition temperature rating T3B for grain dust Motors are designed for continuous duty They can operate in a maximum ambient temperature of 104 F 40 C The unit heaters are listed by the Canadian Standards Association as certified and Canadian Registered heat exchangers CRN OH 9234 5C Does not apply to WVC WPC 952 Steam horizontal and vertical delivery unit heater...

Page 2: ... atmosphere WARNING 1 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 2 All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance Any wiring different from the wiring diagram could result in a hazard to persons and property 3 Any original factory wiring that requires replacement must be replaced wi...

Page 3: ...re listed in Table 4 1 and the height dimensions are shown in Figures 4 3 through 4 7 Maximum mounting heights for vertical models are given for units with or without optional air deflectors The data in Table 4 1 is based on operating conditions of 2 lbs steam or 220 F entering water with 60 F entering air When operating conditions are other than those above refer to Figure 4 2 for maximum mountin...

Page 4: ...m pressures other than 2 pounds or with water at other than average temperature of 220 F Table 4 1 Maximum Mounting Heights UNIT MOUNTING Figure 4 2 Maximum Mounting Heights Correction Factors H Figure 4 6 Vertical Truncone Horizontal Type Power Throw Type Vertical Type with Deflectors No Deflector Cone Jet Truncone Louvers Model No Height ft Model No Height ft Model No Height ft Height ft Height ...

Page 5: ...5 greater than the rated voltage 5 CAUTION 1 Do not install units below 8 feet measured from the bottom of the unit to the floor 2 Do not reuse any electrical component which has been wet Replace component 3 Ensure that the supply voltage to the appliance as indicated on the serial plate is not 5 less than the rated voltage Piping See Figure 6 1 1 Branch piping to and from unit heater should inclu...

Page 6: ...nd must be connected according to wiring diagram with each controller Prior to Operation 1 Make sure fuses are installed in fused disconnect switches 2 Check all electrical connections to assure they are secure 3 Check rigidity of unit mounting Tighten all fasteners if necessary 4 Inspect piping strainers traps fittings etc Initial Start Up 1 Set thermostat to lowest position 2 Turn on power suppl...

Page 7: ...ptional Casings Electrostatically applied gray green polyester powder coat paint finish is applied over rust and corrosion treated steel for long life Motor Cooling Cone Shields motor from coil heat prolongs life of insulation windings and lubricant Prolongs motor life Coil Aluminum fins mechanically bonded to tubes for maximum heat transfer All steam and water carrying passages between heavy stee...

Page 8: ...15 112 631 1 1 2 1 140 WPC 952 952 000 3 967 21 145 12 170 2 321 139 985 2 1 140 Vertical Delivery WVC WVN 42 42 000 175 11 15 17 11 950 825 103 43 1 30 1 050 WVC WVN 59 59 000 246 14 19 21 14 1 155 1 005 111 61 1 30 1 050 WVC WVN 78 78 000 325 15 20 23 15 1 590 1 065 109 81 1 15 1 050 WVC WVN 95 95 000 396 15 20 23 15 1 665 1 120 118 98 1 15 1 050 WVC WVN 139 139 000 579 18 24 27 18 2 660 1 285 1...

Page 9: ... 53 5 040 805 94 214 1 2 1 075 WTC WSC 340L 255 000 1 063 23 53 5 575 775 102 264 1 2 1 075 Power Throw WPC WPN 610L 470 000 1 958 22 154 2 400 2 445 97 486 1 1 2 1 140 Vertical Delivery WVC 42L 33 000 138 13 17 20 13 960 835 94 34 1 30 1 050 WVC 59L 44 000 183 16 22 24 16 1 190 1 035 96 45 1 30 1 050 WVC 78L 62 000 258 19 26 29 19 1 740 1 070 95 65 1 15 1 050 WVC 95L 71 000 296 19 26 29 19 1 760 ...

Page 10: ... 279 192 300 20 0 0 2 4 5 60 0 17 108 5 460 2 165 94 1 2 1 075 WPC WPN 333 238 500 24 8 0 4 4 5 100 0 18 117 5 980 2 165 99 3 4 1 140 WPC WPN 385 276 100 28 8 0 6 4 5 100 0 18 124 7 680 1 860 95 1 1 140 WPC WPN 500 358 000 37 3 0 5 6 0 100 0 19 138 10 390 2 520 93 1 1 2 1 140 WPC WPN 610 450 400 46 9 1 0 6 0 100 0 22 151 11 750 2 315 97 1 1 2 1 140 WPC 952 721 600 75 2 1 1 14 0 200 0 23 150 12 166...

Page 11: ... 89 1 2 1 075 WTC WSC 290L 161 100 16 8 3 7 2 5 70 0 25 57 5 040 800 89 1 2 1 075 WTC WSC 340L 200 900 20 9 6 6 2 5 70 0 25 57 5 575 760 93 1 2 1 075 Power Throw WPC WPN 610L 344 900 35 9 0 6 6 0 100 0 24 158 12 400 2 445 86 1 1 2 1 140 Vertical Delivery WVC 42L 23 000 2 4 0 4 0 5 10 0 14 18 21 14 960 835 83 1 30 1 050 WVC 59L 32 600 3 4 0 3 0 8 15 0 17 23 25 17 1 190 1 035 86 1 30 1 050 WVC 78L 4...

Page 12: ... 34 WSC 47 15 17 1 2 8 3 4 8 12 1 4 11 3 5 8 6 10 3 4 12 35 WSC 63 18 1 2 21 1 2 8 3 4 8 12 3 4 15 3 5 8 6 14 3 4 12 48 WSC 86 18 1 2 21 1 2 8 3 4 9 12 3 4 15 3 5 8 6 14 3 4 14 52 WSC 108 22 1 2 25 1 2 9 1 2 8 11 1 2 18 3 5 8 6 3 8 18 3 4 18 74 WSC 121 22 1 2 25 1 2 9 1 2 7 1 2 11 18 3 5 8 6 3 8 18 3 4 18 76 WSC 165 26 1 2 29 1 2 9 1 4 9 1 2 14 21 1 4 3 5 8 6 3 8 22 3 4 22 92 WSC 193 30 1 2 32 1 2...

Page 13: ... 1 1 2 1 70 WVC WVN 161 34 3 4 8 3 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 80 WVC WVN 193 34 3 4 9 7 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 86 WVC WVN 212 34 3 4 12 7 8 18 3 8 2 1 2 3 19 1 2 19 2 1 1 4 94 WVC WVN 247 34 3 4 12 7 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 108 WVC WVN 279 34 3 4 14 3 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 112 WVC WVN 333 43 1 4 14 5 8 31 1 2 2 7 8 3 1 8 22 1 2 18 1 5 22 2 1 2 1 1 2 166 ...

Page 14: ...otor damage Check plant voltage conditions A separate manual starter with thermal overload protection device is recommended for those units that do not have motors with built in overload protection Coils 1 Clean coil at least once a year more often under unfavorable conditions Unless coil is kept reasonably free of dirt lint and grease its original heating capacity will be reduced possibly to a se...

Page 15: ...ing in too high air temperature 6 Restricted air flow due to clogged coil or closed louvers 7 Fan out of balance 8 Unbalanced voltage on 3φ power Coil Failure Unit Leaks 1 Severe internal corrosion from feedwater 2 Type of boiler treatment 3 Entrained air causing water hammer 4 Continuous operation above 150 PSI 375 F steam systems 5 Loose connection Table 15 1 Troubleshooting Replacement Parts Wh...

Page 16: ...UIPMENT MANUFACTURED BY BUYER BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER FOR GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the origin...

Reviews: