Figure 6.1 - Suggested Piping Arrangements 

Steam Systems

Unit Heater Connection for High Pressure Steam

Horizontal Unit Heater Connected to

Overhead Hot Water Mains

Vertical Unit Heater Connected to

Lower Hot Water Mains

Unit Heater Connection for Low-Pressure Steam 

Open Gravity or Vacuum Return System

INSTALLATION / OPERATION

Hot Water Systems

Electrical Connections (Cont.)

2.   Electric wiring must be sized to carry the full load amp draw   

of the motor, starter, and any controls that are used with  

 

the unit heater. All units with power codes 04, 05, 09, or  

10 (polyphase motors) must be provided with suitable  

 

overcurrent protection in circuit supplying heater at  

 

installation. Overcurrent protectors should be sized based    

on motor current rating shown on the unit serial plate, and    

applicable national electric code procedures.

  All units are provided with an electrical junction box.  

 

  Junction boxes are either integral to the motor or attached    

  to the unit casing. Units with explosion-proof motors have    

  an explosion-proof junction box attached to the motor.
  Any damage to or failure of Modine units caused by  

 

  incorrect wiring of the units is not covered by Modine’s  

 

  standard warranty.
3.  Location of room thermostat, when supplied, should be in    

  the natural circulating path of room air. Mount thermostat    

  about five feet above floor level where it will not be affected   

  by heat from the unit or other sources of drafts that would    

  prevent it from properly controlling room temperature. See    

  instructions packed with the thermostat.
4.  Speed controllers furnished with specified unit heater fan    

  motors, are packed separately and must be connected  

 

  according to wiring diagram with each controller.    

Prior to Operation

1.  Make sure fuses are installed in fused disconnect switches.

2.  Check all electrical connections to assure they are secure.

3.  Check rigidity of unit mounting. Tighten all fasteners, 

if necessary.

4.  Inspect piping, strainers, traps, fittings, etc.

Initial Start-Up

1.  Set thermostat to lowest position.

2.  Turn on power supply to unit.

3.  Open return gate valve, and then open supply gate valve  

to unit.

4.  Raise thermostat setting to desired position.

5.  Adjust louvers (if provided) for desired heat distribution.

6.  To ensure proper sequence of operation, cycle unit on and 

off a few times by raising and lowering thermostat setting.

7.  Check for proper rotation of fan. All fans must rotate in a 

counterclockwise direction when viewed from the back 

(WTC/WSC, WPC/WPN) or top (WVC/WVN) of the unit 

heater.

Automatic Control Operations

Install one of the following operating systems for continuous 

automatic control.

Intermittent Fan Operation — Hot Coil

A room thermostat starts and stops the fan motor. An aquastat 

is sometimes strapped to the return piping to prevent fan 

operation when heat is not being supplied to the unit heater.

Continuous Fan Operation — Intermittent Hot/Cold Coil

A room thermostat controls a valve which opens to allow steam 

or hot water to supply the unit and closes to shut off the supply 

when the thermostat is satisfied.

OPERATION

➀  

Arrangements shown are recommendations only. Where horizontal units are shown, vertical units can be substituted or vice versa. For modifications to piping 

suggestions shown, refer to your local plumbing authority.

Model WSC

Side Connections

Model WTC

Top and Bottom Connections

Model WTC

Top and Bottom Connections

Model WSC

Side Connections

Model WTC

Side Connections

Model WSC

Top and Bottom Connections

Summary of Contents for AIR 1-550.30

Page 1: ... rating for national electric code ignition temperature rating T3B for grain dust Motors are designed for continuous duty They can operate in a maximum ambient temperature of 104 F 40 C The unit heaters are listed by the Canadian Standards Association as certified and Canadian Registered heat exchangers CRN OH 9234 5C Does not apply to WVC WPC 952 Steam horizontal and vertical delivery unit heater...

Page 2: ... atmosphere WARNING 1 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 2 All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance Any wiring different from the wiring diagram could result in a hazard to persons and property 3 Any original factory wiring that requires replacement must be replaced wi...

Page 3: ...re listed in Table 4 1 and the height dimensions are shown in Figures 4 3 through 4 7 Maximum mounting heights for vertical models are given for units with or without optional air deflectors The data in Table 4 1 is based on operating conditions of 2 lbs steam or 220 F entering water with 60 F entering air When operating conditions are other than those above refer to Figure 4 2 for maximum mountin...

Page 4: ...m pressures other than 2 pounds or with water at other than average temperature of 220 F Table 4 1 Maximum Mounting Heights UNIT MOUNTING Figure 4 2 Maximum Mounting Heights Correction Factors H Figure 4 6 Vertical Truncone Horizontal Type Power Throw Type Vertical Type with Deflectors No Deflector Cone Jet Truncone Louvers Model No Height ft Model No Height ft Model No Height ft Height ft Height ...

Page 5: ...5 greater than the rated voltage 5 CAUTION 1 Do not install units below 8 feet measured from the bottom of the unit to the floor 2 Do not reuse any electrical component which has been wet Replace component 3 Ensure that the supply voltage to the appliance as indicated on the serial plate is not 5 less than the rated voltage Piping See Figure 6 1 1 Branch piping to and from unit heater should inclu...

Page 6: ...nd must be connected according to wiring diagram with each controller Prior to Operation 1 Make sure fuses are installed in fused disconnect switches 2 Check all electrical connections to assure they are secure 3 Check rigidity of unit mounting Tighten all fasteners if necessary 4 Inspect piping strainers traps fittings etc Initial Start Up 1 Set thermostat to lowest position 2 Turn on power suppl...

Page 7: ...ptional Casings Electrostatically applied gray green polyester powder coat paint finish is applied over rust and corrosion treated steel for long life Motor Cooling Cone Shields motor from coil heat prolongs life of insulation windings and lubricant Prolongs motor life Coil Aluminum fins mechanically bonded to tubes for maximum heat transfer All steam and water carrying passages between heavy stee...

Page 8: ...15 112 631 1 1 2 1 140 WPC 952 952 000 3 967 21 145 12 170 2 321 139 985 2 1 140 Vertical Delivery WVC WVN 42 42 000 175 11 15 17 11 950 825 103 43 1 30 1 050 WVC WVN 59 59 000 246 14 19 21 14 1 155 1 005 111 61 1 30 1 050 WVC WVN 78 78 000 325 15 20 23 15 1 590 1 065 109 81 1 15 1 050 WVC WVN 95 95 000 396 15 20 23 15 1 665 1 120 118 98 1 15 1 050 WVC WVN 139 139 000 579 18 24 27 18 2 660 1 285 1...

Page 9: ... 53 5 040 805 94 214 1 2 1 075 WTC WSC 340L 255 000 1 063 23 53 5 575 775 102 264 1 2 1 075 Power Throw WPC WPN 610L 470 000 1 958 22 154 2 400 2 445 97 486 1 1 2 1 140 Vertical Delivery WVC 42L 33 000 138 13 17 20 13 960 835 94 34 1 30 1 050 WVC 59L 44 000 183 16 22 24 16 1 190 1 035 96 45 1 30 1 050 WVC 78L 62 000 258 19 26 29 19 1 740 1 070 95 65 1 15 1 050 WVC 95L 71 000 296 19 26 29 19 1 760 ...

Page 10: ... 279 192 300 20 0 0 2 4 5 60 0 17 108 5 460 2 165 94 1 2 1 075 WPC WPN 333 238 500 24 8 0 4 4 5 100 0 18 117 5 980 2 165 99 3 4 1 140 WPC WPN 385 276 100 28 8 0 6 4 5 100 0 18 124 7 680 1 860 95 1 1 140 WPC WPN 500 358 000 37 3 0 5 6 0 100 0 19 138 10 390 2 520 93 1 1 2 1 140 WPC WPN 610 450 400 46 9 1 0 6 0 100 0 22 151 11 750 2 315 97 1 1 2 1 140 WPC 952 721 600 75 2 1 1 14 0 200 0 23 150 12 166...

Page 11: ... 89 1 2 1 075 WTC WSC 290L 161 100 16 8 3 7 2 5 70 0 25 57 5 040 800 89 1 2 1 075 WTC WSC 340L 200 900 20 9 6 6 2 5 70 0 25 57 5 575 760 93 1 2 1 075 Power Throw WPC WPN 610L 344 900 35 9 0 6 6 0 100 0 24 158 12 400 2 445 86 1 1 2 1 140 Vertical Delivery WVC 42L 23 000 2 4 0 4 0 5 10 0 14 18 21 14 960 835 83 1 30 1 050 WVC 59L 32 600 3 4 0 3 0 8 15 0 17 23 25 17 1 190 1 035 86 1 30 1 050 WVC 78L 4...

Page 12: ... 34 WSC 47 15 17 1 2 8 3 4 8 12 1 4 11 3 5 8 6 10 3 4 12 35 WSC 63 18 1 2 21 1 2 8 3 4 8 12 3 4 15 3 5 8 6 14 3 4 12 48 WSC 86 18 1 2 21 1 2 8 3 4 9 12 3 4 15 3 5 8 6 14 3 4 14 52 WSC 108 22 1 2 25 1 2 9 1 2 8 11 1 2 18 3 5 8 6 3 8 18 3 4 18 74 WSC 121 22 1 2 25 1 2 9 1 2 7 1 2 11 18 3 5 8 6 3 8 18 3 4 18 76 WSC 165 26 1 2 29 1 2 9 1 4 9 1 2 14 21 1 4 3 5 8 6 3 8 22 3 4 22 92 WSC 193 30 1 2 32 1 2...

Page 13: ... 1 1 2 1 70 WVC WVN 161 34 3 4 8 3 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 80 WVC WVN 193 34 3 4 9 7 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 86 WVC WVN 212 34 3 4 12 7 8 18 3 8 2 1 2 3 19 1 2 19 2 1 1 4 94 WVC WVN 247 34 3 4 12 7 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 108 WVC WVN 279 34 3 4 14 3 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 112 WVC WVN 333 43 1 4 14 5 8 31 1 2 2 7 8 3 1 8 22 1 2 18 1 5 22 2 1 2 1 1 2 166 ...

Page 14: ...otor damage Check plant voltage conditions A separate manual starter with thermal overload protection device is recommended for those units that do not have motors with built in overload protection Coils 1 Clean coil at least once a year more often under unfavorable conditions Unless coil is kept reasonably free of dirt lint and grease its original heating capacity will be reduced possibly to a se...

Page 15: ...ing in too high air temperature 6 Restricted air flow due to clogged coil or closed louvers 7 Fan out of balance 8 Unbalanced voltage on 3φ power Coil Failure Unit Leaks 1 Severe internal corrosion from feedwater 2 Type of boiler treatment 3 Entrained air causing water hammer 4 Continuous operation above 150 PSI 375 F steam systems 5 Loose connection Table 15 1 Troubleshooting Replacement Parts Wh...

Page 16: ...UIPMENT MANUFACTURED BY BUYER BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER FOR GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the origin...

Reviews: