SELECTING YOUR COMPONENT EQUIPMENT

AIR HANDLER

The 2012 IECC requires the central blower used with the AirCycler g2 to use an electronically commutated motor. 

EXHAUST FAN

The AirCycler® g2, when used with the optional FanConnect™ switch, can be configured to rely on the exhaust fan 

for supplemental ventilation. If used in this configuration, the exhaust fan must be capable of a flow rate equal to or 

greater than the continuous whole building mechanical ventilation rate.

The bathroom exhaust fan should have a sound rating of 1.0 sone or less. This recommendation is a requirement if the 

home is certified as an ENERGY STAR V3 home, if the home is located in California (per California Title 24, Part 6), or if 

the home is otherwise required to comply with ASHRAE 62.2. 

The 2012 IECC code requires the exhaust fan have an efficacy of 1.4 cfm/W if less than 90 cfm or 2.8 cfm/W if equal to 

or greater than 90 cfm. 

Note:

The AirCycler® g2 will only control 

one 

exhaust fan. We recommend using our SmartExhaust® bath fan/light  switch/

ventilation controller for additional bathrooms requiring ventilation.

Summary of Contents for g2

Page 1: ...AirCycler g2 g2 k Installation User s Guide VENTILATION MADE BREEZY a breeze to install a breeze to use Ventilation Products...

Page 2: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may result in personal injury or product and property damage INSTALLAT...

Page 3: ...e building mechanical ventilation rate The bathroom exhaust fan should have a sound rating of 1 0 sone or less This recommendation is a requirement if the home is certified as an ENERGY STAR V3 home i...

Page 4: ...rough in either direction although it is recommended to install with the crimped end as the outlet Use care to avoid distorting the damper housing and provide adequate support CHOOSE A FRESH AIR LOCAT...

Page 5: ...N icons will show If the exhaust bath fan is on the EXH icon will show If the outside fresh air damper is open the OA icon will show If the EXH fan is running its set delay time after the FanConnect h...

Page 6: ...f Factory default is 10 minutes Press MODE to save all settings and return to normal operation 2 1 5 CALCULATED FLOW SETUP IS COMPLETE Set up is complete The AirCycler g2 will now return to normal ope...

Page 7: ...enter YES the AirCycler g2 will prompt you to enter the hour you would like the ventilation to begin and the hour you want it to end followed by the current time Set the hour you want the ventilation...

Page 8: ...been open with the central fan running 3 1 3 EXHAUST RUN TIME This shows the elapsed run time of the exhaust fan for this time period 3 1 4 EXHAUST DELAY TIME This shows the exhaust delay time set 3...

Page 9: ...RRENT TIME By pressing the MODE key you will cycle through current time of day and will be able to change it if needed APPENDIX A ASHRAE 62 2 REFERENCE CHART CFM Required 7 5 CFM N 1 A 0 01 N No of Be...

Page 10: ...the motorized damper does not cycle Confirm 1 The AirCycler g2 is providing a 24 VAC signal to the motorized damper 2 The 24 VAC motorized damper is operational by powering directly with a 24 VAC sign...

Reviews: