AC DOC 8.5

REV 11/21/2014

INTRODUCTION

If the AirCycler® g2 was installed in your home as a ventilation controller, DO NOT DISABLE IT.

In the past, homes depended on natural leaks for ventilation. Today, energy efficient homes are built to reduce natural 

ventilation and leaks.   Inadequate ventilation can increase indoor air pollutants to harmful levels.  Indoor air quality is 

typically 5 to 10 times more polluted than outside air. Controlled ventilation provides adequate air flow to the home 

without compromising its efficiency.

SAFETY CONSIDERATIONS

Read and follow manufacturer’s instructions carefully. Follow all local electrical codes during installation. All wiring 

must conform to local and national electrical codes.  Improper wiring or installation may result in personal injury or 

product and property damage.

INSTALLATION CONSIDERATIONS

The AirCycler® g2 requires 24VAC (R and C terminals) to be connected for proper operation.  The controller will not 

operate without these two connections.

The  wires  (R, C, &  W )  from  the  air  handler  to  the thermostat can run parallel with the wiring from the AirCycler® 

g2 to the air handler. The fan wire (G) must be interrupted by the AirCycler® g2.  Some thermostats do not require a 

common (C) connection.  The AirCycler® g2 requires this for power, which must be wired to the furnace.

KEY

Vnc - Normal Closed Vent

R - 24VAC Power

W - Heating

Gt - Fan From Thermostat

Gf - Fan to Furnace

C - Common

V - Vent

Ex - Exhaust Fan

Wiring Diagram

Summary of Contents for g2

Page 1: ...AirCycler g2 g2 k Installation User s Guide VENTILATION MADE BREEZY a breeze to install a breeze to use Ventilation Products...

Page 2: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may result in personal injury or product and property damage INSTALLAT...

Page 3: ...e building mechanical ventilation rate The bathroom exhaust fan should have a sound rating of 1 0 sone or less This recommendation is a requirement if the home is certified as an ENERGY STAR V3 home i...

Page 4: ...rough in either direction although it is recommended to install with the crimped end as the outlet Use care to avoid distorting the damper housing and provide adequate support CHOOSE A FRESH AIR LOCAT...

Page 5: ...N icons will show If the exhaust bath fan is on the EXH icon will show If the outside fresh air damper is open the OA icon will show If the EXH fan is running its set delay time after the FanConnect h...

Page 6: ...f Factory default is 10 minutes Press MODE to save all settings and return to normal operation 2 1 5 CALCULATED FLOW SETUP IS COMPLETE Set up is complete The AirCycler g2 will now return to normal ope...

Page 7: ...enter YES the AirCycler g2 will prompt you to enter the hour you would like the ventilation to begin and the hour you want it to end followed by the current time Set the hour you want the ventilation...

Page 8: ...been open with the central fan running 3 1 3 EXHAUST RUN TIME This shows the elapsed run time of the exhaust fan for this time period 3 1 4 EXHAUST DELAY TIME This shows the exhaust delay time set 3...

Page 9: ...RRENT TIME By pressing the MODE key you will cycle through current time of day and will be able to change it if needed APPENDIX A ASHRAE 62 2 REFERENCE CHART CFM Required 7 5 CFM N 1 A 0 01 N No of Be...

Page 10: ...the motorized damper does not cycle Confirm 1 The AirCycler g2 is providing a 24 VAC signal to the motorized damper 2 The 24 VAC motorized damper is operational by powering directly with a 24 VAC sign...