1050 Hopper Ave, Santa Rosa, CA 95403 • Tel (800) AIRFLOW • www.airmonitor.com [email protected]
ELECTRA-flo G5 Transmitter Thermal Airflow & Temperature Measurement System 1015-3 - 07/18
24
Sensor Alert Scan
Displays alert codes for expected sensors. Sensors operating
properly will display
NoAlert
.
Other Alert Codes
ALERT CODE TYPE
DESCRIPTION
CORRECTIVE ACTION
Missing
ALERT Transmitter cannot communicate with Sensor Power cycle system and recheck.
SensAOOR
or
SensBOOR
ALERT Sensor fault
Replace sensor. Contact Air Monitor.
DeltaOOR
ALERT Sensor Delta Temperature out of range
Contact Air Monitor.
TempOOR
RANGE Temperature measurement out of range
(-20 to 140° F)
Verify application temperature is not
outside -20 to 140° F. If ELECTRA-flo G5
appears to be reporting incorrectly, contact
Air Monitor.
Disabled
ALERT
Sensor resets abnormally
Power cycle system and recheck.
VelOOR
RANGE Average velocity exceeds 5000 FPM for
ducted and 10,000 FPM for Fan Inlet
Verify factory set-up information is correct.
If application velocity exceeds 5000 FPM,
contact Air Monitor.
3.7 START-UP / OPERATION
After power and signal wiring has been verified in accordance with
section 3.5, activate the external 24 VAC / 24 VDC power source.
Sensor Alert Scan
ESC - Leave UP/DN - Scroll
Sensor 1: Disabled
SENSOR
ALERT CODE
FREQ
1
Disabled
41
2
NoAlert
1. Press the power button located on the bottom left corner of the
front cover to turn the system ON.
2. The display will show a loading bar. After reaching 100%, the
display will indicate which sensors have been discovered for
approximately 2 seconds. Then the normal operating screen
will be displayed.
ELECTRAflo
Total Flow
520 ACFM
417.1 AFPM
Velocity
72.71 F
Temperature
The default normal operating screen will display
Total Flow
on the first process line,
Velocity
(average
of all enabled sensors) on the second process line and
Temperature
(average of all enabled sensors) on
the third process line. Application tagging information is at the bottom of the screen and is customer
configurable.