1050 Hopper Ave, Santa Rosa, CA 95403 • Tel (800) AIRFLOW • www.airmonitor.com [email protected]
ELECTRA-flo G5 Transmitter Thermal Airflow & Temperature Measurement System 1015-3 - 07/18
14
Transceiver: 2-wire, half-duplex (1/3 unit load)
Baud Rate(s): 9600, 19200, 38400, 56700, 76800, 115200 (Default: 38400) unless specified by the
end user
MS/TP MAC Address (“Address” in menu) range: 1 – 255. Starts at 1, incremented for each
transmitter in the system, unless specified by the end user
BACnet Device ID (“ID” in menu) range: 0 – 4,194,303. Same as the Device Address, unless
specified by the end user
Max Masters: 1 – 127 (Default: 127) unless specified by the end user
Termination: 120 Ohms or none (Default: None)
Biasing: 549 Ohms or none (Default: None)
Flow control: None
The Custom ID field provides the Device Description property over BACnet and on the display.
To change the Device Description, either go to the Service Menu - >
Custom ID and modify the
field or do this remotely over BACnet.
BACnet OBJECT TYPES
BACnet Object Type and number of Objects implemented:
Device: 1
Analog Input - Reports the average temperature or average flow. Also, reports individual sensor
velocity or sensor temperature. See below for more details.
PROTOCOL IMPLEMENTATION STATEMENT
BACnet Protocol Revision: 12
Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 56700, 76800, 115200
Device Address Binding: No
BBMD support registration by Foreign Devices: No
Character Set Supported: ANSI X3.4
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing – Read Property-B (DS-RP-B)
Data Sharing – Read Property Multiple-B (DS-RPM-B)
Data Sharing – Write Property-B (DS-WP-B)
Device Management – Dynamic Device Binding-B (DM-DDB-B)
Device Management – Dynamic Object Binding-B (DM-DOB-B)
Device Management – Device Communication Control-B (DM-DCC-B)
Device Management – Reinitialize Device-B (DM-RD-B)