ELECTRA-flo
Air Monitor Corporation
116-053-00.P65 (7/06)
ELECTRA-flo
- IO&M Manual
6.2 – SENSOR MANAGEMENT (con't)
5. Press . Display will indicate:
Ping Sensor
Selection
6. Press . Display will indicate:
Ping Sensor
|
7. Use and to scroll to desired sensor.
8. Once desired sensor # is displayed, press and display will indicate either:
Ping Sensor
Ping Sensor
|
|
Sensor Is Active
SENSOR NOT FOUND
9. Use and to scroll to all desired sensors, and press to view results.
10. Either scroll to exit (after #32) or press to return to previous menu (see Step 5).
11. Press and display will indicate:
Enable Sensor
Selection
12. Press . Display will indicate:
Enable Sensor: 1
1 8 16 24 32
Enabled Sensors: 8
This display will indicate which active sensors are enabled.
Only enabled sensors will be indicated on bar graph by darkened area under their respective #, and total number
of enabled sensors will be displayed at the bottom.
If any active sensors have been previously disabled, they can be enabled by scrolling (using and )
their # and pressing .
13. Press to return to previous menu (see Step 11).
14. Press and display will indicate.
Disable Sensor
Selection
UP
ENT
Þ
UP
ENT
DN
ENT
UP
DN
ENT
ESC
UP
Þ
or
UP
DN
ENT
ESC
UP
Þ
SECTION 6 – CALIBRATION
27