ELECTRA-flo
Air Monitor Corporation
116-053-00.P65 (7/06)
ELECTRA-flo
- IO&M Manual
SECTION 5 – OPERATION
19
5.11 – LOW PASS FILTER
Allows selection of level of Process filtering applied to the output. Levels are 0 to 10, with 0 representing no filtering and
10 representing maximum filtering. Display Filter is an additional filter selection applied only to the display.
This filtering affects all subsequent outputs and displays.
1. While in Operator Menu, use or to scroll to:
Low Pass Filter
Selection
2. Press and display will indicate current setting of Process filter; (
0 (none) to 10 (maximum
).
3. Use or to change setting. Once desired setting is displayed, press . New setting will be stored
in memory and display will return as in Step 1.
Note: If user desires not to change the setting and return to Output 2 Parameter menu, press . Unit will
remain programmed as it was originally.
5.12 – TRANSMITTER OUTPUT CALIBRATION
Allows for the calibration of the ELECTRA-flo analog outputs.
Note: Unit is supplied Factory calibrated.
This section can be accomplished with the ELECTRA-flo mounted in its operating location or at a test bench in a
calibration lab.
Required Equipment.
1. Digital Multimeter
Preparation.
1. Turn Power switch OFF on the ELECTRA-flo (see Figure 4.1).
2. Open cover of the ELECTRA-flo.
3. Remove all wires connected to terminals 1 through 4 (see Figure 4.2).
4. Turn Power switch ON.
UP
®
ENT
DN
UP
DN
ENT
ESC
- Output 1 Zero Selection
- Output 1 Span Selection
- Output 2 Zero Selection
- Output 2 Span Selection
- Return to MAIN MENU
See Calibration
Instructions
- Low Pass Filter Selection
→
Transmitter Output Calib.
- K-Factor Configuration
Operator Menu
Transmitter Output Calib.
- Output 2 Parameter Selection
→
Low Pass Filter Selection
- Transmitter Output Calib
Low Pass Filter
1 (Minimum)
0 (None) to
10 (Maximum)
Default selection shown.
Available selections:
Operator Menu