
41
Fan AUTO or
ON
Setting 7
•
Press “Settings” button to advance to
Setting 7.
•
Press the “Up” or “Down” arrow buttons
to adjust number to the desired set
point. Factory default is zero (0).
Zero (0) = Auto
–fan only turns on when
there is a call for cooling or heating
One (1) = Fan On
–fan remains on
continuously
Compressor
anti-short
cycling
Setting 8
•
Press “Settings” button to advance to
Setting 8.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired time in one-
minute increments. Maximum is 10
minutes; minimum is 3 minutes. Factory
default is 5 minutes.
Compressor anti-short cycling time is
the amount of allowable time between
compressor stop and restart. Rapid
start/stop of compressors can cause
premature failure.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER
THAN FACTORY DEFAULT.
Defrost
sensor
enable/disable
Setting 9
•
Press “Settings” button to advance to
Setting 9.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint.
1 will equal enabled and a 0 (zero) will
equal disabled.
Defrost cut-in
temperature
Setting 10
•
Press "Settings" button to advance to
Setting 10.
•
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 25°F to 40°F.
Factory default is 39°F.
There must be at least a 1°F difference
between defrost cut-in and cut-out set
points.
Summary of Contents for WINE GUARDIAN DS025
Page 13: ...13 Overview of the Evaporator Fig 1...
Page 14: ...14 Overview of the Condenser Fig 2...
Page 15: ...15 Refrigeration Illustration Fig 3...
Page 16: ...16 Wiring Diagram for DS025 WGS40 Fig 4...
Page 17: ...17 Wiring Diagram for DS025 WGS40 cont Fig 5...
Page 18: ...18 Wiring Diagram for DS025 WGS40 cont Fig 6...