2
3
SAFETY CONSIDERATIONS
WARNING
Never expose eyes or skin to UVC light from any source.
• Looking directly at the UVC light may cause permanent eye damage
or blindness.
• Never operate the Air+Health™ Haven Plus out of the plenum.
• Designed for a closed duct system. Do not mount near a supply or a
return air opening.
• All duct openings in direct line of site of the UV light must be sealed
with aluminum tape or equivalent sealing methods.
• Wear supplied safety glasses during installation.
WARNING
UVC light will break down plastic materials not rated for UV exposure:
(Examples: wire insulation, flex duct, drain pans and humidifiers)
• The unit must be mounted at least 30” from the above stated type
of materials.
• If it is necessary to mount the unit in direct line of sight of these
types of materials, they must be shielded with aluminum foil,
aluminum foil tape, or sheet metal.
WARNING
DO NOT mount this unit outdoors.
• This product is designed for indoor installation only (i.e. Attics, crawl
spaces, basements, etc.).
WARNING
Never touch broken lamp or internal contents of lamp. The lamp
contains mercury.
• After opening the carton, unpack and inspect the unit and lamp for
damage. Do not install this unit if any damage is noticeable. If lamp
is damaged, cracked or broken, do not touch lamp or other contents
in carton. Close carton and return to seller immediately.
• In case of accidental exposure to internal contents of lamp, wash
hands and any other affected skin area with mild detergent.
Remove affected clothing immediately. If skin surface is pierced,
seek medical attention immediately.
NOTE:
If you touch the glass of the lamp, you should wipe the glass clean
with isopropyl alcohol and a lint free wipe. If the lamp is not cleaned, the film
of hand oils causes a reduction in the light intensity.
WARNING
Before installing or servicing a humidifier, air filter, heat system, this unit,
etc., always turn all power OFF and have unit unplugged. Electrical shock can
cause personal injury or death. Never expose eyes or skin to direct UVC light
from any source.
WARNING
To prevent water damage or electric shock, do not mount unit under
a humidifier.
WARNING
This product is designed for indoor installation only (i.e. attics, crawl spaces,
basements, etc.). For use on gas fired, oil fired, electric and split system heat
pump forced air systems
*
. This product is NOT designed to be mounted
outside on gas fired or heat pump packaged units
**
.
*
Split system heat pumps are systems where the air handler and the air
conditioning compressor are separate units.
**
Packaged units are systems where the air handler and the air conditioning
compressor are built together and are installed outside of the building.
Safety Considerations
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.