INSTALLATION & MAINTENANCE INSTRUCTIONS
PREMA
CEILING VOID ENERGY RECOVERY VENTILATION UNITS
21
Shows values for each parameter
Use
or
to view parameters
Press ESC to go back to the previous menu
Allows selection of the fan status method (normally FACTORY SET)
Press OK to enter
Value is flashing: use
or
to choose
Press OK to select
Available settings are:
Tacho
The fan(s) has a tacho output (open-collector - hall sensor)
connected to RPM-GND. The running status is indicated by the
presence of the RPM signal
Relay
The fan(s) healthy signal
Allows adjustment of the global gain for applications to be
fine-tuned / adjusted beyond P05
Press OK to enter
Value is flashing: Use
or
to choose
Press OK to select
Any change from default setting will drive P05 to CUSTOM
Available settings are:
Default
Min
Max
Min value change
0.5
0.1
1
0.1
Service Menu
S01: Parameter Summary
Service Menu
S02: Fan Status Signal
Service Menu
S03: Global Gain
Service Menu Functions
Service Menu on CTRL-DSP
To enter the main menu press OK for 3 seconds
To exit the main menu press ESC or wait approx. 60 seconds
Service Menu
S01: Parameter Summary
S02: Fan Status Signal
S03: Custom PID - Global Gain
S04: Custom PID - Proportional Band
S05: Custom PID - Integration Time (Pressure)
S06: Custom PID - Derivation Time (Pressure)
Debug Page
Control Debug Page
Shows the extended functional parameters of the unit
Press OK to enter
Press ESC to go back to the previous menu