INSTALLATION & MAINTENANCE INSTRUCTIONS
PREMA
CEILING VOID ENERGY RECOVERY VENTILATION UNITS
23
BOOST:
When BST input is closed, fans run at full speed 10V. It overrides all other control inputs.
Shows the internal control parameters of the unit
Press OK to enter
Press ESC to go back to the previous menu
Selected Application
(e.g. temperature)
Set
Setpoint
(e.g. 20°C)
Meas
Measured
Parameter
(e.g. 17.9°C)
Err
Error
The difference between the setpoint and measured
parameter (e.g. -2.1°C)
Kp
Proportional Gain
A parameter of the PID controller, calculated from
Global Gain and Proportional Band parameters
(Service Menu)
Ki
Integral Gain
A parameter of the PID controller (used only in
Pressure application), calculated from Kp and
Integration Time (service menu)
Kd
Derivative Gain
A parameter of the PID controller (used only in
Pressure application), calculated from Kp and
Derivation Time (Service Menu)
Service Menu
Control Debug Page