16
Item
Range
Default
Value
Access Level
Description
Voltage
Up/ Down for
More
Installer/
Service
Press UP or DOWN buttons to access
additional temperature measure-
ments.
Voltage
View Only – VAC
---
Installer/
Service
Displays the 24VAC voltage as meas-
ured by the control board.
Coil Temp
View Only –
degrees F or C
Installer/
Service
Displays the coil temperature sensor
value – used for defrost operation.
Amb Temp
View Only –
degrees F or C
Installer/
Service
Displays the ambient temperature
sensor value – used for Outside
Lockout operation and defrost.
Suct Temp
View Only –
degrees F or C
Installer/
Service
Displays the suction line temperature
sensor value – used for EXV opera-
tion ONLY. Will not be shown if EXV
Disabled is selected.
EXV Temp
View Only –
degrees F or C
Installer/
Service
Displays the EXV temperature sensor
value – ONLY available with EXV
Enabled AND EXV Temp Sensor uti-
lized. NOTE: This is ONLY utilized
when the pressure transducer is NOT
used.
Sat Temp
View Only –
degrees F or C
Installer/
Service
Displays the pressure transducer con-
verted to a temperature. It is
displayed whenever EXV is enabled.
Water Temp
View Only –
degrees F or C
Installer/
Service
Displays the water temperature sen-
sor value – used for temperature
operation
Installer Menu
Yes or No
No
Select YES and press the MENU but-
ton to gain access to additional
programming selections in this
Installer/Service Sub-menu. Select
No and the next MENU button press
returns to the Set Current Time
screen.
Pump Operation
4-Speed Enabled,
Variable Enabled,
Disabled
Disabled
Installer/
Service Sub-
menu
If pump control through the HPPH is
desired, select the appropriate pump
mode – 4-Speed Enabled for discrete
speed control or Variable Enabled for
PWM control of pump.
Pump Heat
Installer/
Service Sub-
menu
This feature selects the Digital input
(pump speed) for the pump to operate
during HPPH operation.
Valve Operation
Enabled, Disabled
Disabled
Installer/
Service Sub-
menu
This feature allows control of 3-way
valves. Disabled is the default.
When Enabled, the control will seek
information as to whether the Return
and Suction valves should be posi-
tions for Pool or Spa positions for
each pump period.
Return Valve
Position 1 =
Pool/Spa
Pool
Suction Valve
Position 1 =
Pool/Spa
Pool
AUX Mode
AUX OFF, AUX
OUTPUT, REMOTE
OUT, EXT HEAT
AUX OFF
Installer/
Service Sub-
menu
See description of auxiliary mode
operation on page 19.
Summary of Contents for 9350HC
Page 8: ...8 Fig 2 Hurricane Tie Down Instructions ...
Page 31: ...31 Fig 9 Pool Piping for Heat Pump Pool Heater and Gas Pool Heater ...
Page 34: ...34 Wiring Diagram 208V 230V Three Phase Digital Models ...
Page 35: ...35 Wiring Diagram 460V Three Phase Digital Models 460V 3PH 60 Hz ...
Page 36: ...36 Wiring Diagram 380V Three Phase Digital Models ...
Page 39: ...39 ...