(NOTE 1)  The bypass is activated by the reversal of the 4-way valve only if at least one compressor 

is on

(NOTE 2)  The alarm is enabled only if the associated resource (e.g. a given compressor or pump) 

is active

(NOTE 3)  The alarm is enabled only if the associated resource (e.g. specific compressor or specific 

pump) is active only in heating mode.

(NOTE 4)  The alarm is enabled only if the associated resource (e.g. specific compressor or specific 

pump) is active only in heating mode. Low pressure digital alarm related to dedicated 

circuit is not active if Pump-down valve of the relavant circuit is active (valve closed, 

Pump-down ongoing, and after CP33 time after desactivation)

(NOTE 1)  If No. trips = 1, the alarm is always manual reset type.

(NOTE 2)  Alarm bypass is active in heating mode only.

(NOTE 3)  An offset of 6°C (value cannot be changed) is added to the activation setpoint AL51 

during the defrost stage.

Alar

m c

ode

Name of alar

m

Bypass ac

tiv

ation

ev

en

t

Bypass time

Aut

oma

tic alar

ac

tiv

ation time

Manual alar

m

ac

tiv

ation time

Exit alar

m

deac

tiv

ation time

Number of in

ter

ven

tions

 

per sample time

E022

Primary circuit 

pump 2 thermal 

switch

None

Not 

present

Not

present

Not

present

Not

present

AL26

E026

Disposable circuit 

pump thermal 

switch

None

Not 

present

Not

present

Not

present

Not

present

AL27

E050

Primary exchanger 

electric heater 1 

thermal switch

None

Not

present

Not

present

Not

present

Not

present

Not

present

E051

Primary exchanger 

electric heater 2

None

Not

present

Not

present

Not

present

Not

present

Not

present

E056

Auxiliary output 

alarm

None

Not

present

Not

present

Not

present

Not

present

Not

present

2.4 

Alarms Table

Alar

m c

ode

Name of alar

m

Bypass ac

tiv

ation ev

en

t

Bypass time

SET

 ac

tiv

ation

Hyst

eresis

Aut

oma

tic alar

m time

(NO

TE

 1)

No

. of tr

ips

Con

trol P

robe

E003

Circuit 1 

analogue

high pressure 

alarm

None

None

AL40

AL41 Not present

AL42

Circuit 1

high pressure 

probe

E004

Circuit 1 

analogue

high pressure 

alarm

None

None

AL40

AL41 Not present

AL42

Circuit 1

high pressure 

probe

E007

Circuit 1 

analogue

low pressure 

alarm

A circuit 1 

compressor

is switched on

or reversal of 

the 4-way 

valve

AL43

AL44

AL45 Not present

A46

Circuit 1

low pressure 

probe

E008

Circuit 2 

analogue

low pressure 

alarm

A circuit 2 

compressor

is switched on

or reversal of 

the 4-way 

valve

AL43

AL44

AL45 Not present

A46

Circuit 2

low pressure 

probe

E030

Primary circuit 

antifreeze

On/Off (local or 

remote), input 

in heat mode

(NOTE 2)

AL50

AL51

(NOTA 3) AL52 Not present

A53

Internal 

exchanger 

water/air outlet 

temperature

E031

External circuit 

antifreeze

On/Off (local or 

remote), input 

in heat mode

(NOTE 2)

AL54

AL55

AL56 Not present

A57

External 

exchanger 

outlet water 

temperature

E032

“Vacuum” 

circuit 1

None

None

AL59

AL60

AL58

manual reset Low pressure 

input circuit 1

Alar

m c

ode

Name of alar

m

Bypass ac

tiv

ation ev

en

t

Bypass time

SET

 ac

tiv

ation

Hyst

eresis

Aut

oma

tic alar

m time

(NO

TE

 1)

No

. of tr

ips

Con

trol P

robe

E033

“Vacuum” 

circuit 2

None

None

AL59

AL60

AL58

manual reset Low pressure 

input circuit 2

E035

High 

temperature

None

None

AL47

AL48

AL49

Automatic 

reset

Internal 

exchanger 

water/air outlet 

temperature

•   The alarm signal consists of a code, the format being “E0nn” (nn is a 2-figure number iden-

tifying the type of alarm, e.g. E000, E025, E039...).

•  In the case of multiple simultaneous alarms only the one with the lowest code will be displa-

yed (e.g. simultaneous alarms E000 and E001). The display will show only E000 alternated 

with the main display page

•  If the measurement on the main display is incorrect, in the event of an alarm, the alternate 

alarm code will alternate with “----”.

All possible alarms are listed in the table below with their respective codes and the relative utilities 

blocked:

2.4.1 Alarms table key

column

Alarm code

NOTA:

the codes are shown in ascending order (E000, E001) but there may be 

some gaps (there is no E006)

Name of alarm

Notes

CMP 1/2

Compressor 1/power step 2

PUMP 1/2

Pump1/2

Alarm

D

Digital

A

Input

Reset

AUTO

Automatic

UTILITY

OFF COMP1

OFF compressor 1

OFF COMP2

OFF compressor 2

OFF COMP3

OFF compressor 3

OFF COMP4

OFF compressor 4

OFF (1)

When used for temperature control

OFF (2)

When used for temperature control and/or antifreeze

OFF RES1

OFF heater 1

OFF RES2

OFF heater 2

2.3 

Analogue alarms

Summary of Contents for ENERGY FLEX SKP 20

Page 1: ...SKP 20 LCDTerminals User manual for ENERGY FLEX english ...

Page 2: ...SKP 20 ...

Page 3: ...tpoweron 6 1 3 1 Accesstofolders menustructure 6 1 3 2 MaindisplayMenu 6 1 3 3 OperatingMode Menu 7 1 3 4 Settingtheclock CL 7 1 3 5 AlarmDisplay AL 8 1 3 6 Exampleofhowtosetthesetpoint SP 8 1 3 7 Resetcompressor pumptime 9 1 3 8 Parameters folderPAr 9 1 3 9 Settingapassword Par PASSfolder 10 1 3 10 Alarmevents Par EUfolder 10 DIAGNOSTICS 2 1 Alarms 12 2 1 1 Automaticreset 12 2 1 2 Manualreset 12 ...

Page 4: ...d with utilities are all configurable From the factory device is set to the table Key Press once press and release Longpress pressandholdforabout3seconds 1 Increaseavalue Gotonextlabel See also F1 Activate manual defrost See the Functions menu folder FnC 2 Decreaseavalue Gotopreviouslabel See also F3 Machine active OFF OFF machine active See Local On OFF section See also Functions menu FnC folder ...

Page 5: ...ICON 2 Manual defrost Icons are associated with menu navigation and manual defrost The factory settings of the controller are listed in the table 1 1 5 DoubleLCD Whichwewillrefertoasfollows The double display has 26 icons States and operating modes 9 icons o Browse menu manual defrost 2 icons Values and units of measure 4 icons Utilities 7 icons Fans 4 icons Read outs can have up to Display A 4 di...

Page 6: ...NU label Parameters PAr CL CL00 CF CF01 AL ALOO Functions FnC dEF tA St OFF ON CC UL dL Fr EUr Password PASS EU EU When Energy SKW22 L is powered on for the first time a lamp test is carried out to check its state and operation The LampTest lasts for just a few seconds During this short time all icons and digits flash at the same time After the lamp test the following are displayed depending on th...

Page 7: ... press the set key to confirm You will be automatically returned to the preconfigured main display In this case AiL1 with a value of 7 5 C For example let s say you want to change from StbY to COOL mode To change operating mode press and hold the esc key for at least 2 seconds A blinking menu will open containing the values StbY standby HEAt heat and COOL cool that you can scroll using the DOWN ke...

Page 8: ...roceed in the same way by first changing the device s mode from COOL to HEAT See Operating Mode Menu chapter To change the setpoint on your machine press the UP or DOWN key in the main display Label Ai appears on the display Use the UP and DOWN keys to scroll the other labels until you find the SP label Press the set key to open the SP menu The first display will be COOL mode and then scrolling wi...

Page 9: ... key to change the value of the parameter CL01 in this case Press the up and down keys to change the value of the parameter CL01 in this case On selecting a value press the set key To exit this display and return to the previous level press the esc key N B pressing the set key confirms the modified value pressing the esc key returns you to the previous level without saving the new value entered Ex...

Page 10: ...8 in this example Alarm start date 20 May in this example Alarm stop time HO alarm still active in this case Alarm stop date dO alarm still active in this case Type of alarm tY automatic AUtO or alternatively manual ManU To view the PASS folder in the main display press the Esc and Set keys at the same time esc set Pressing the two keys will open the menu containing the list of folders Use the up ...

Page 11: ...11 SKP 20 ...

Page 12: ...A 4 Not present Not present Not present AL12 Alarm code Name of alarm Bypass activation event Bypass time Automatic alarm activation time Manual alarm activation time Exit alarm deactivation time Number of interventions per sample time E006 NOTA 4 Circuit 2 low pressure alarm Circuit compressor activated or reversal of 4 way valve NOTE 1 NOTE 4 AL11 NOTA 4 Not present Not present Not present AL12 ...

Page 13: ...ue lowpressure alarm Acircuit1 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit1 lowpressure probe E008 Circuit2 analogue lowpressure alarm Acircuit2 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit2 lowpressure probe E030 Primarycircuit antifreeze On Off localor remote input inheatmode NOTE2 AL50 AL51 NOTA3 AL52 Not...

Page 14: ... CMP4 D Events OFFCOMP4 E015 Compressor1oilpressureswitch CMP1 D Events OFFCOMP1 E016 Compressor2oilpressureswitch CMP2 D Events OFFCOMP2 E017 Compressor3oilpressureswitch CMP3 D Events OFFCOMP3 E018 Compressor4oilpressureswitch CMP4 D Events OFFCOMP4 E020 Primarycircuitflowswitch D Time OFFformanual resetalarm OFF OFF OFFfor manual reset alarm OFF OFF E021 Primarycircuitpump1thermalswitch D Event...

Page 15: ...aultydisposableexchangerwaterorairinput temperatureprobe AUTO SeeProbeErrorsTable E064 Faultydisposableexchangerwaterorairoutput temperatureprobe AUTO SeeProbeErrorsTable E065 Faultyambienttemperatureprobe AUTO SeeProbeErrorsTable E066 Sanitarywatertemperatureprobefaulty AUTO SeeProbeErrorsTable E067 Faultydisplayprobe temperature pressure AUTO SeeProbeErrorsTable E068 Faultyexternaltemperaturepro...

Page 16: ...Serie SKP20 Issue Supersedese 02 15 Catalogue M 204b The data indicated in this manual is purely indicative The manufacturer reserves the right to modify the data whenever it is considered necessary ...

Reviews: