background image

12

SKP 20

2. Diagnostics

2.1

Alarms

2.2

Digital alarm

2.3

Analog alarms

2.4

Alarm table

 Preliminary precautions

•  The control panel allows you to make all the necessary adjustments to the chiller operation and to view the values   of the 

main parameters and alarms. The control panel is located on the front panel of the electrical board.

The “Energy SBA600” performs full installation diagnostics and reports a variety of alarms.

Parameters for alarm activation and resetting can be viewed and configured in folder
AL (parameters AL00…AL82) (see User Interface and Parameters section).

2.1.1 Automatic reset

For automatic reset alarms, normal operation is restored as soon as the cause of the alarm has been 

removed.

2.1.2 Manual reset

Alarms can be manually reset by pressing and releasing the [UP + DOWN] keys

Normal operation can only be reset

•  by pressing a key on the instrument keyboard and

•  only if the cause of the alarm has been removed.

2.1.3 Alarm mute

Alarms can be acknowledged by pressing any key.

  acknowledging an alarm has no effect on the alarm generated other than on the alarm 

LED, which goes from fixed to flashing.

An alarm has two effects:

•  It blocks the services concerned

•  Message on the keyboard display alternates with a message on the main display.

The next two sections summarize alarms grouped by type (digital or analogue).

Alarm code and alarm parameters are in bold (folder PAr/AL)

2.1 Alarms

Alar

m c

ode

Name of alar

m

Bypass ac

tiv

ation

ev

en

t

Bypass time

Aut

oma

tic alar

ac

tiv

ation time

Manual alar

m

ac

tiv

ation time

Exit alar

m

deac

tiv

ation time

Number of in

ter

ven

tions

 

per sample time

E001

Circuit 1

high pressure 

alarm

None

Not 

present

Not

present

Not

present

Not

present

AL10

E002

Circuit 2

high pressure 

alarm

None

Not 

present

Not

present

Not

present

Not

present

AL10

E005

(NOTA 4)

Circuit 1

low pressure 

alarm

Circuit 

compressor 

activated

or reversal

of 4-way valve

(NOTE 1)

(NOTE 4)

AL11

(NOTA 4)

Not

present

Not

present

Not

present

AL12

Alar

m c

ode

Name of alar

m

Bypass ac

tiv

ation

ev

en

t

Bypass time

Aut

oma

tic alar

ac

tiv

ation time

Manual alar

m

ac

tiv

ation time

Exit alar

m

deac

tiv

ation time

Number of in

ter

ven

tions

 

per sample time

E006

(NOTA 4)

Circuit 2

low pressure 

alarm

Circuit 

compressor 

activated

or reversal

of 4-way valve

(NOTE 1)

(NOTE 4)

AL11

(NOTA 4)

Not

present

Not

present

Not

present

AL12

E020

(NOTA 2)

Primary circuit 

flow switch 

alarm

Internal circuit 

pump activation

(One of the two 

pumps)

AL14

AL15

AL16

AL15

Not

present

E025

(NOTA 3)

Primary circuit 

pump thermal 

switch alarm

External circuit 

pump activation AL17

AL18

AL19

AL18

Not

present

E010

Compressor 1 

thermal switch

Compressor 1 

switched on

AL20

Not

present

Not

present

Not

present

AL21

E011

Compressor 2 

thermal switch

Compressor 2 

switched on

AL20

Not

present

Not

present

Not

present

AL21

E012

Compressor 3 

thermal switch

Compressor 3 

switched on

AL20

Not

present

Not

present

Not

present

AL21

E013

Compressor 4 

thermal switch

Compressor 4 

switched on

AL20

Not

present

Not

present

Not

present

AL21

E015

(NOTE 2)

Compressor 1 oil 

pressure switch

Compressor 1 

switched on

AL22

Not

present

Not

present

Not

present

AL23

E016

(NOTE 2)

Compressor 2 oil 

pressure switch

Compressor 2 

switched on

AL22

Not

present

Not

present

Not

present

AL23

E017

(NOTE 2)

Compressor 3 oil 

pressure switch

Compressor 3 

switched on

AL22

Not

present

Not

present

Not

present

AL23

E018

(NOTE 2)

Compressor 4 oil 

pressure switch

Compressor 4 

switched on

AL22

Not

present

Not

present

Not

present

AL23

Er40

Primary exchanger 

fan thermal switch

None

Not

present

Not

present

Not

present

Not

present

AL24

Er41

External exchanger 

fan thermal switch

Circuit 1

None

Not

present

Not

present

Not

present

Not

present

AL25

Er42

External exchanger 

fan thermal switch

Circuit 2

None

Not

present

Not

present

Not

present

Not

present

AL25

E021

Primary circuit 

pump 1 thermal 

switch

None

Not

present

Not

present

Not

present

Not

present

AL26

2.2 

Digital alarms

Summary of Contents for ENERGY FLEX SKP 20

Page 1: ...SKP 20 LCDTerminals User manual for ENERGY FLEX english ...

Page 2: ...SKP 20 ...

Page 3: ...tpoweron 6 1 3 1 Accesstofolders menustructure 6 1 3 2 MaindisplayMenu 6 1 3 3 OperatingMode Menu 7 1 3 4 Settingtheclock CL 7 1 3 5 AlarmDisplay AL 8 1 3 6 Exampleofhowtosetthesetpoint SP 8 1 3 7 Resetcompressor pumptime 9 1 3 8 Parameters folderPAr 9 1 3 9 Settingapassword Par PASSfolder 10 1 3 10 Alarmevents Par EUfolder 10 DIAGNOSTICS 2 1 Alarms 12 2 1 1 Automaticreset 12 2 1 2 Manualreset 12 ...

Page 4: ...d with utilities are all configurable From the factory device is set to the table Key Press once press and release Longpress pressandholdforabout3seconds 1 Increaseavalue Gotonextlabel See also F1 Activate manual defrost See the Functions menu folder FnC 2 Decreaseavalue Gotopreviouslabel See also F3 Machine active OFF OFF machine active See Local On OFF section See also Functions menu FnC folder ...

Page 5: ...ICON 2 Manual defrost Icons are associated with menu navigation and manual defrost The factory settings of the controller are listed in the table 1 1 5 DoubleLCD Whichwewillrefertoasfollows The double display has 26 icons States and operating modes 9 icons o Browse menu manual defrost 2 icons Values and units of measure 4 icons Utilities 7 icons Fans 4 icons Read outs can have up to Display A 4 di...

Page 6: ...NU label Parameters PAr CL CL00 CF CF01 AL ALOO Functions FnC dEF tA St OFF ON CC UL dL Fr EUr Password PASS EU EU When Energy SKW22 L is powered on for the first time a lamp test is carried out to check its state and operation The LampTest lasts for just a few seconds During this short time all icons and digits flash at the same time After the lamp test the following are displayed depending on th...

Page 7: ... press the set key to confirm You will be automatically returned to the preconfigured main display In this case AiL1 with a value of 7 5 C For example let s say you want to change from StbY to COOL mode To change operating mode press and hold the esc key for at least 2 seconds A blinking menu will open containing the values StbY standby HEAt heat and COOL cool that you can scroll using the DOWN ke...

Page 8: ...roceed in the same way by first changing the device s mode from COOL to HEAT See Operating Mode Menu chapter To change the setpoint on your machine press the UP or DOWN key in the main display Label Ai appears on the display Use the UP and DOWN keys to scroll the other labels until you find the SP label Press the set key to open the SP menu The first display will be COOL mode and then scrolling wi...

Page 9: ... key to change the value of the parameter CL01 in this case Press the up and down keys to change the value of the parameter CL01 in this case On selecting a value press the set key To exit this display and return to the previous level press the esc key N B pressing the set key confirms the modified value pressing the esc key returns you to the previous level without saving the new value entered Ex...

Page 10: ...8 in this example Alarm start date 20 May in this example Alarm stop time HO alarm still active in this case Alarm stop date dO alarm still active in this case Type of alarm tY automatic AUtO or alternatively manual ManU To view the PASS folder in the main display press the Esc and Set keys at the same time esc set Pressing the two keys will open the menu containing the list of folders Use the up ...

Page 11: ...11 SKP 20 ...

Page 12: ...A 4 Not present Not present Not present AL12 Alarm code Name of alarm Bypass activation event Bypass time Automatic alarm activation time Manual alarm activation time Exit alarm deactivation time Number of interventions per sample time E006 NOTA 4 Circuit 2 low pressure alarm Circuit compressor activated or reversal of 4 way valve NOTE 1 NOTE 4 AL11 NOTA 4 Not present Not present Not present AL12 ...

Page 13: ...ue lowpressure alarm Acircuit1 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit1 lowpressure probe E008 Circuit2 analogue lowpressure alarm Acircuit2 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit2 lowpressure probe E030 Primarycircuit antifreeze On Off localor remote input inheatmode NOTE2 AL50 AL51 NOTA3 AL52 Not...

Page 14: ... CMP4 D Events OFFCOMP4 E015 Compressor1oilpressureswitch CMP1 D Events OFFCOMP1 E016 Compressor2oilpressureswitch CMP2 D Events OFFCOMP2 E017 Compressor3oilpressureswitch CMP3 D Events OFFCOMP3 E018 Compressor4oilpressureswitch CMP4 D Events OFFCOMP4 E020 Primarycircuitflowswitch D Time OFFformanual resetalarm OFF OFF OFFfor manual reset alarm OFF OFF E021 Primarycircuitpump1thermalswitch D Event...

Page 15: ...aultydisposableexchangerwaterorairinput temperatureprobe AUTO SeeProbeErrorsTable E064 Faultydisposableexchangerwaterorairoutput temperatureprobe AUTO SeeProbeErrorsTable E065 Faultyambienttemperatureprobe AUTO SeeProbeErrorsTable E066 Sanitarywatertemperatureprobefaulty AUTO SeeProbeErrorsTable E067 Faultydisplayprobe temperature pressure AUTO SeeProbeErrorsTable E068 Faultyexternaltemperaturepro...

Page 16: ...Serie SKP20 Issue Supersedese 02 15 Catalogue M 204b The data indicated in this manual is purely indicative The manufacturer reserves the right to modify the data whenever it is considered necessary ...

Reviews: