  6. Interface elements

Termi-

nals 

P0/1

Relay

P2/3

Relay

P4/5

Analog 

(option)

P6/7

Analog 

(option)

P8/9

Trigger

y1

R1 normally closed (NC) 
(option)

R3 normally closed 
(option)

(option)

(option)

U+

y2

R1 common

R3 common

AO5 +

AO7 +

TR9+

y3

R1 normally open (NO)

R3 normally open

AO5  -

AO7  -

TR9 -

x3

R0 normally open

R2 normally open

AO4  -

AO6  -

TR8 -

x2

R0 common

R2 common

AO4 +

AO6 +

TR8+

x1

R0 normally closed (option) R2 normally closed (option)

U-

7. Commissioning

1. Connect the relay adapter to socket A2 on the ALMEMO

®

 device; the integrated

interface elements are then available as port P20 to P29. 

2. Switch the ALMEMO

®

 device ON; see 5.

3. Connect the peripheral equipment to the clamp connectors and on the relay

adapter to the appropriate port sockets; see 6.4.

4. All the following programming functions can be performed via the device

keypad in the "output modules" menu (if available) or using the AMR-Control

software or by means of a terminal command. 

Application Summated alarm :

1. For critical measuring points program limit values on the ALMEMO

®

 device.

2. With ALMEMO

®

 device program the first relay port to variant 0 ´Summated

alarm´ using command ´

i20 f9 k0

´ (see Manual 6.10.9.2).

3. In the event of any limit value being overshot the associated relay is acti-

vated. 

4. If it is intended that the relay should drop out in the event of an alarm it can be

programmed to operate inversely. 

Application Monitoring a measuring point :

1. Program the limit value for the critical measuring point xx on the ALMEMO

®

 de-

vice. 

2. Program relay yy as limit value action (special function) : 

Limit value maximum, command : ´

Exx

 

ipp f2 Ryy

´,

Limit value minimum, command : ´

Exx

 

ipp f3 Ryy

´,

The relay is configured automatically to the ´assigned´ variant.

3. If it is intended that the relay should drop out in the event of an alarm it can be

programmed to operate inversely. 

Application Driving via the interface :

1. With ALMEMO

®

 device in the output modules menu program the relay port

pp to variant 8 ´driven´ using command ´

ipp f9 k8

´.

2. If it is intended that the relay should drop out in the event of activation it can

be programmed to operate inversely - using the command ´

ipp f9 k-8

´.

 6       ALMEMO 8006-RTA3   

Summary of Contents for ALMEMO 8006-RTA3

Page 1: ...____________________________ Operating instructions Relay trigger adapter analog ALMEMO 8006 RTA3 V2 4 18 03 2014 www ahlborn com...

Page 2: ...uts TR8 TR9 2 DC socket Mains adapter ZA1312 NA1 12V 0 2A 3 LCD graphics display 7 rows for functions 1 line for softkeys F1 F2 Shown in brackets MENU 4 Operating keys TR8 9 Trigger keys softkeys P Po...

Page 3: ...4 Connecting peripheral equipment 5 6 COMMISSIONING 6 7 DISPLAY AND OPERATING CONTROLS 7 7 1 Main menu 7 7 2 Showing all elements 7 7 3 Showing single elements 7 7 4 Device configuration 8 7 5 Messag...

Page 4: ...maximum supply current on the measuring instrument must take the sensors into consideration If the maximum supply current is exceeded a mains adapter e g ZA1312 NA1 should be connected at the DC socke...

Page 5: ...with electrically iso lated analog outputs offering the following signals Option Output signal Gain OA 8000 R2 0 000 to 10 000 V 0 5 mV digit or 0 000 to 20 000 mA 1 A digit The output value normally...

Page 6: ...uring points program limit values on the ALMEMO device 2 With ALMEMO device program the first relay port to variant 0 Summated alarm using command i20 f9 k0 see Manual 6 10 9 2 3 In the event of any l...

Page 7: ...appro priate measuring point see Manual 6 10 3 8 Display and operating controls The adapter incorporates a graphics display that can show exactly all states affecting the interface elements This is c...

Page 8: ...desired function can be selected by means of keys PROG and Programming is by means of the softkeys ON OFF or SET and input is by means of keys PROG PROG Illumination To switch display illumination ON...

Page 9: ...Watchdog Duration s o Duration 060s Switch off watchdog alarm with watchdog function and switch on again after restoring the control 8 5 Messages Each relay can be assigned a particular message either...

Page 10: ...output port pp ipp f9 ayyyyy Program message for port pp e g ipp message port pp Start new line with special character Tel 123 CRLF To output message Response ipp P48 Message port pp Tel 123 CRLF To...

Page 11: ...ty 50 V 0 5 A Trigger inputs Optocoupler 4 to 30 V Input current 2 mA Analog outputs Electrically isolated switchable OA 8006 R02 4 00 to 10 0 V 0 5 mV digit Load 100 kW 0 0 to 20 0 mA 1 A digit Load...

Page 12: ...mp connectors ZA 8006 RTA3 Mains adapter with ALMEMO connector 12 V 1 A ZA 1312 NA8 Options 2 additional relays maximum 10 including 1 ALMEMO clamp connector OA 8006 SH2 2 additional normally closed r...

Page 13: ...nection diagram 2 2 contact assignment 8 3 8 Current consumption 11 1 11 Device configuration 8 4 8 Display and operating controls 8 7 display illumination 8 4 8 driven inversely 9 10 Driving the anal...

Page 14: ...Power supply 5 4 Power supply 11 1 11 Product overview 11 2 12 Programming via the device interface 9 10 Relay 11 1 11 relays 8 3 7 screw connector 6 4 5 Showing all elements 8 2 7 Showing single elem...

Page 15: ...Index trigger source 8 3 8 variant 8 3 7 voltage capacity 6 1 4 Watchdog 8 4 9 8 4 8 ALMEMO 8006 RTA3 15...

Page 16: ...11 Appendix 11 4 your contact 16 ALMEMO 8006 RTA3...

Reviews: