background image

 

How To Configure an Aqua Trac 

1.

 

 Go to the AgSense users page, click on the unit that you want to set up, then click the 
main configuration button. 

2.

 

 Select the type of probe from the drop down menu.  Choose AquaCheck or Sentek.  
(Acclima should not be chosen at this time). 

3.

 

Add the probe ID if known otherwise leave blank. 

4.

 

Add the sensor depths for the AquaCheck or Sentek probe in the spaces provided.  If the 
depths are unknown they may be left blank.  The graph will automatically drop in valves 
of 4”, 8”, 16” 24” 32” and 40”. 

5.

 

If using a Watermark sensors, choose Watermark 200SS-V in the sensor drop downs.  
Choose the Sensor number that corresponds with the location in the Aqua Trac that was 
used to wire in the sensor.  When you choose Watermark a space will be provided to the 
right for the sensor depth if known. 

6.

 

If using a Temperature sensor, choose thermistor in the Sensor 5 drop down menu. 

7.

 

If using a Rain Bucket, choose Tipping Bucket in the Tipping Bucket 1 drop down menu. 

8.

 

Save configuration 

Main Page Display 

Once configured, Watermark sensor information will have a WM displayed by it.  The 
AquaCheck and Sentek probes both display the sensors in a column with the soil moisture value 
just to the right.  Some Sentek sensors will also have an additional column displaying salinity. 
Below the sensor readings is a display of the soil type in the general area where the probe is 
located.  It is based on GPS location and is there for information value only. 
The latitude and longitude of the Aqua Trac can be found under the readings button on the main 
page for each unit. 
 

General information 

1.

 

 The board runs on 7-34v DC.  It is solar only and cannot run on AC voltage. 

2.

 

The board communicates only by cellular modems at this time.  There is no radio to radio 
communication at this time. 

3.

 

As with all AgSense solar units, the unit stays “awake” only long enough to take a 
reading and then goes back to sleep.  Most Aqua Tracs are set to take a reading every half 
hour. 

4.

 

The 5V/12V Jumper must be across the 5V only. If the jumper is missing the unit will 
output 40vDC which will damage the sensors. 

5.

 

A temperature sensor or rain bucket can be added to the board but 

not

 a pressure 

transducer, anemometer or humidity sensor. 

6.

 

The 5V/12V out light (located by the GPS and modem light) will come on before a 
reading and shut off when the reading is complete. Also, the lights by each sensor PWR 
terminal will come on when a reading is being taken.  Only those sensors chosen on the 
Main Configuration page will be given power for a reading to be taken. 

Page 16 

Summary of Contents for Aqua Trac Pro

Page 1: ...2015 18 Aqua Trac Pro Wiring Manual Revised January 1 2018...

Page 2: ...g the EnviroPro Probe Page 12 Connecting the Greenshield Probe Page 13 Connecting the Waterscout SM100 Sensor Page 14 Connecting the AgSense Rain Bucket Page 15 Connecting the AgSense Temperature Sens...

Page 3: ...act your AgSense Dealer to finish setup and configuration of this unit to read the sensors that you have installed Note 2 The pins marked SENSOR POWER as shown above should have a jumper connecting th...

Page 4: ...olar panel Find the group of terminals 2 with the group label PWR 1 Connect the Black Wire from the solar panel to the terminal marked GND as shown above 2 Connect the White or Red Wire from the solar...

Page 5: ...of terminals 3 with the group label WM 1 1 Connect the Red wire from the Watermark sensor to the terminal marked PWR as shown above 2 Connect the Black wire from the Watermark sensor to the terminal m...

Page 6: ...wire from the Decagon 10HS GS1 sensor to the terminal marked PWR as shown above 2 Connect the Bare wire from the Decagon 10HS GS1 sensor to the terminal marked GND as shown above 3 Connect the Red wi...

Page 7: ...f terminals 3 with the group label SDI 1 Connect the Blue wire from the AquaCheck probe to the terminal marked SIG as shown 2 Connect the Yellow Green stripe wire from the AquaCheck probe to the termi...

Page 8: ...the Blue wire from the Sentek probe to the terminal marked SIG as shown above 2 Connect the Yellow wire from the Sentek probe to the terminal marked GND as shown above 3 Connect the Red wire from the...

Page 9: ...e group of terminals 3 with the group label SDI 1 Connect the Red wire from the Decagon Sensor to the terminal marked SIG as shown above 2 Connect the Bare wire from the Decagon Sensor to the terminal...

Page 10: ...nals 3 with the group label SDI 1 Connect the White wire from the Sentek probe to the terminal marked SIG as shown above 2 Connect the Green wire from the Sentek probe to the terminal marked GND as sh...

Page 11: ...abel SDI 1 Connect the Green wire from the CS Sensor to the terminal marked SIG as shown above 2 Connect the Clear Black and Orange wires from the CS Sensor to the terminal marked GND as shown above a...

Page 12: ...s 3 with the group label SDI 1 Connect the Blue wire from the Sensor to the terminal marked SIG as shown above 2 Connect the White wire from the Sensor to the terminal marked GND as shown above 3 Conn...

Page 13: ...nals 3 with the group label SDI 1 Connect the Blue wire from the Sensor to the terminal marked SIG as shown above 2 Connect the Black wire from the Sensor to the terminal marked GND as shown above 3 C...

Page 14: ...als 3 with the group label SDI 1 Connect the Green wire from the Sensor to the terminal marked SIG as shown above 2 Connect the Yellow wire from the Sensor to the terminal marked GND as shown above 3...

Page 15: ...the Sensor to the terminal marked SIG as shown above 2 Connect the Black wire from the Sensor to the terminal marked GND as shown above 3 Connect the White wire from the Sensor to the terminal marked...

Page 16: ...se Rain Bucket Find the group of terminals 2 with the group label RAIN 1 Connect the Green wire from the AgSense Rain Bucket to the terminal marked GND as shown above 2 Connect the Red wire from the A...

Page 17: ...Sense Temp Sensor Find the group of terminals 2 with the group label TEMP 1 Connect the Green wire from the AgSense Temp sensor to the terminal marked GND as shown above 2 Connect the Brown wire from...

Page 18: ...moisture value just to the right Some Sentek sensors will also have an additional column displaying salinity Below the sensor readings is a display of the soil type in the general area where the prob...

Page 19: ...sensors Page 13 Watermark 200TS Temperature Sensor Page 14 Tank Monitoring Liquid Level Sensor Also included in this section is a new overview picture of the unit Page 10 showing slight changes to the...

Page 20: ...our AgSense Dealer to finish setup and configuration of this unit to read the sensors that you have installed Note 2 The pins marked SENSOR POWER as shown above should have a jumper connecting the mid...

Page 21: ...Jumper Settings Note you cannot mix ETape Watermark Decagon 10HS GS1 5v sensors and 12v Tank Monitor Acclima TDR Sensors only 1 type may be used at a time Page 19...

Page 22: ...p label 1 1 Connect one Green wire from the Watermark sensor to the terminal marked GND as shown above 2 Connect the other Green wire from the Watermark sensor to the terminal marked SIG as shown abov...

Page 23: ...termark Temp Sensor 200TS Find the group of terminals 2 with the group label TEMP 1 Connect one Red wire from the 200TS Temp sensor to the terminal marked GND as shown above 2 Connect the second Red w...

Page 24: ...marked PWR as shown above 2 Connect the Red wire from the ETape Sensor to the terminal marked GND as shown above 3 Connect the White wire from the ETape Sensor to the terminal marked SIG as shown abo...

Page 25: ...to the terminal marked PWR as shown above 2 Connect the Black wire from the Tank Monitor sensor to the terminal marked GND as shown above 3 Connect the White wire from the Tank Monitor sensor to the...

Page 26: ...as shown above 5 Connect the Black wire from the Pressure Transducer to the terminal marked GND as shown above 6 Connect the White wire from the Pressure Transducer to the terminal marked SIG as shown...

Page 27: ...ON Closed Connection 1 Connect one wire from the Pressure Switch or Float Switch to the terminal marked PWR as shown above 2 Connect the second wire from the Pressure Switch or Float Switch to the te...

Page 28: ...ank Monitor sensor to the terminal marked GND as shown above 3 Connect the Yellow wire from the Tank Monitor sensor to the terminal marked SIG as shown above Notes Green wire not used Repeat steps 1 3...

Page 29: ...eing used in extremely explosive liquids fuels an explosion proof sensor is available contact your dealer to get information and pricing and availability of this sensor from AgSense How To Configure a...

Page 30: ...air on any unit that fails due to defect in materials or workmanship AgSense labor and parts would be provided free of charge during the warranty period This does not include dealer labor What is not...

Page 31: ...onsibility for the reliability of this technology Customer acknowledges that AgSense does not have the ability to control the reliability of GPS Satellite and Internet Technology AgSense specifically...

Page 32: ...AgSense LLC 259 Dakota Ave S PO Box 53 Huron SD 57350 605 352 8350 www AgSense net...

Reviews: