Layer sensor
WGA-ES4
Electronic unit
WGA 01 D
Sludge sensor
WGA-ES8
Damming sensor
WGA-R6-S
WGA 01 D is an Intrinsically Safe (Ex)
grease and oil separator alarm compris-
ing of a central alarm control unit that can
accept up to three independent alarm sen-
sors from three separate alarm points.
The IP65 enclosure housing the alarm con-
trol is designed to be mounted onto a wall
or a suitably flat surface.
Note:
This central alarm unit must only
be mounted in a “safe-area” and never
installed in an area where there a risk of an
explosion.
•
WGA-ES4
Capacitance type layer (Ex)
sensor for raising the alarm when the
layer of oil or grease exceeds the alarm
value.
•
WGA-ES8
Ultrasonic type sludge (Ex)
sensor for raising the alarm when sand
or particles in the separator exceed a
predefined level.
•
WGA-R6-S
Thermistor type (Ex) dam-
ming sensor for indication of a high
level.
WGA 01 D
is an Intrinsically Safe (Ex)
central alarm control unit approved for
use with the listed Ex sensors. The central
alarm control unit has two individually pro-
grammable voltage free relay outputs
(R1 and R2) that can be used to provide
remote alarm monitoring or activation of
secondary external alarms.
The central alarm control unit is program-
mable by navigation of the membrane key-
pad and displays the settings and alarms in
a text format.
Functional description