12
6. Close junction box and tight the screws
5.3 Connection to the PV Generator (DC)
CAUTION!
Unit Disconnection From Load
Disconnect circuit breakers and switches on both DC and AC sides.
5.3.1 Conditions for the DC Connection
• The connected PV modules must meet following requirements
– Same type
– Same model
– Identical alignment
– Identical tilt
• The following limit values at the DC input of the inverter must not be exceeded (connecting to a higher
voltage will destroy the device):
Type
Maximum input voltage [Vd.c]
Maximum input current [Ad.c]
BNT012KTL
1000
22+11
BNT013KTL
1000
22+11
BNT015KTL
1000
22+11
5.3.2 Assembling the DC Plug Connector
In order to connect to the inverter, all connection cables of the PV modules must be equipped with the DC
plug connectors provided. You will find the necessary DC plug connector for DC connection in the package.