Page 23 of 36
SK2014-SON-002-TechMnl-SWC-003
c)
The slave units can be set individually for timer ON/OFF function by handset or wall pad. The handset cannot
override the wall pad timer and clock setting.
C.3.2.
Master – Slave Network Setup
1)
Disconnect the communication plug from the SK-NCSWC-001
2) Communication plug
A, B, A, B is printed on the main PCB. When you connect the wires, please ensure connection of A to A and B to B.
3) Connection wire
3.1)
If the total length of wire is more than 1000m, please use shielded wire in order to protect the signal transmission.
3.2)
Complete wire connection
3.3)
Wire connection check
3.3.1) After the wire connection is completed, please check that the wire colours correspond.
First unit
Middle unit
Last unit
First unit
Middle unit
Last unit