Aertesi ECOELEGANT SERIES Installation And Operation Manual Download Page 15

Page 15 of 36

 

SK2014-SON-002-TechMnl-SWC-003

 

5.

 

Mode configuration: 

DIPA-S1 

Model 

SW7 

SW8 

Model setting 

Cool-Heat 

Cool-Heat + booster heater 

Cooling only 

Cool + primary heater 

 

6.

 

Unit ON/OFF 

 

There are 3 ways to turn the system on or off: 
a)  By the ON/OFF button on the handset or wired wall pad. 
b)  By the programmable timer on the handset or wired wall pad. 
c)   By the manual control button on the air conditioner. 

7.

 

Auto-Restart 

The system uses a non-volatile memory to save the present operation parameters when system is turned off or in 
case of system failure or cessation of power supply. 
The restored parameter data-set depends on the type of user interface.  

a) Handset only user interface: 

When the power on signal is received by the air conditioner and no wired wall-pad is installed, the Mode, 
Fan Speed, Set temperature and Louver/Swing setting will be the same as the handset  setting before the 
last power off. 

b) Wall-pad only OR wall-pad and handset user interface: 

When the power on signal is received by the air  conditioner and  a wired wall-pad is installed, the Mode, 
Fan Speed, Set temperature, Louver/Swing setting and Timer ON/OFF weekly program will be the same as 
the wall pad setting before the last power off. 

C.1.5.

 

Control Logics for 2-Pipe System 

 

C.1.5.1.

 

With Thermoelectric Valve Configuration 
COOL MODE 
a)

 

  MTV2, AUX1 and electric heater are always off. 

b)

 

If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated and MTV1 and 
AUX2 are turned on. Indoor fan runs at set speed. 

c)

 

  If Tr < Ts, then cool operation is terminated and MTV1 and AUX2 are turned off. Indoor fan runs at set 

speed. 

d)

 

The range of Ts is 16 - 30ºC 

e)

 

  Indoor fan speed can be adjusted to low, medium, high and auto. 

f)

 

  When turned on, MTV1 requires 30 seconds before it is fully open. 

g)

 

  When turned off, MTV1 requires 120 seconds before it is fully closed. 

h)

 

When the unit is turned off, the indoor fan will shut down after 5 seconds. 

 

LOW TEMPERATURE PROTECTION OF INDOOR COIL 
 
a)

 

  If Ti1 ≤ 2 ºC for 2 minutes, then MTV1 and AUX2 are turned off. If indoor fan is set for low speed, then it 

will  run  at  medium  speed.  If  it  is  set  at  medium  or  high  speed,  then  it  will  keep  running  at  the  same 
speed. 

b)

 

If Ti1 ≥ 5ºC for 2 minutes, then MTV1 and AUX2 are turned on. Indoor fan runs at set speed. 

 
FAN MODE 
 
a)

 

  Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off. 

b)  Indoor fan speed can be adjusted to low, medium and high. 
 
HEAT MODE 

Without Electrical Heater 

Summary of Contents for ECOELEGANT SERIES

Page 1: ...NA version 2 1 Revised Feb 17 2014 AER MIU HWNEC GB 01 04 14 AERTESI srl Via della tecnica 6 35020 Conselve PD ITALY www aertesi com ECOELEGANT SERIES INSTALLATION AND OPERATION MANUAL HWN EC SERIES...

Page 2: ...stage in the manufacturing of our products Throughout the production process we maintain strict control starting with our extensive resources in research and development through to the design and manu...

Page 3: ...1 C 1 2 Definition of Input Output 11 C 1 3 Wiring Diagram EBWPCGH EC 13 C 1 4 Configuration Settings 14 C 1 5 Control Logics for 2 Pipe System 15 C 1 6 Control Logics for 4 Pipe System 17 C 1 7 Auto...

Page 4: ...models Tabs located on the front of the unit can be unsnapped allowing the filter to be easily slid downward and removed No tools are required nor any dismantling of the equipment Air Grille Distribu...

Page 5: ...ectric Heater Capacity 1 FCCOP e Rating 176 216 248 230 Class B B B B Sound Sound PressureLevel Outlet dB A 27 24 23 37 30 26 37 30 26 43 34 29 Sound Power Level Outlet e 38 35 33 48 40 35 48 40 35 53...

Page 6: ...PressureLevel Outlet dB A 46 40 34 40 35 30 45 35 30 Sound Power Level Outlet e 57 52 45 52 46 41 56 46 41 Electrical Fan Motor Power e H W 30 41 60 M 20 24 24 L 13 18 18 Fan Motor Apparent Power H 8...

Page 7: ...obstructions The air should flow freely 2 The wall where the unit is to be mounted should be solid firm enough not to resonate and produce noise 3 The location should allow easy access to install the...

Page 8: ...t use shielded sensor cables 11 Install a noise filter if the power supply creates any disruptive noises B 1 2 Mounting Plate Dimensions HWN 25 30 40 EC B 1 3 Installing the Mounting Plate 1 Select th...

Page 9: ...if it is securely fixed 3 While pushing the unit toward the wall lift it slightly from beneath to hook it up on the mounting plate by the lower hooks 4 Make sure the unit firmly rests on the hooks of...

Page 10: ...B 2 2 Removing Front Cover Assembly 1 Set the horizontal louver to the horizontal position 2 Remove the screw caps below the louver and then remove the mounting screws 3 Open the lift up grille cover...

Page 11: ...water outlet valve B 2 4 Wiring Connections Unit components are wired to the terminal block of the indoor unit Wiring can be accessed from the terminal block inside the control box B 3 Pipe Connectio...

Page 12: ...wer supply to the PCB and all the loads connected to the voltage outputs Max length 5 m Earth PE1 Power supply to the PCB and all the loads connected to the voltage outputs Max length 5 m Voltage outp...

Page 13: ...Page 13 of 36 SK2014 SON 002 TechMnl SWC 003 C 1 3 Wiring Diagram EBWPCGH EC...

Page 14: ...ault DIP Switch Settings DIPA S1 DIPB S2 2 Thermoelectric Valve Configuration On board DIP switch SW3 of DIPB is used for this configuration 3 Unit Configuration On board DIP Switches of DIPB are used...

Page 15: ...mer ON OFF weekly program will be the same as the wall pad setting before the last power off C 1 5 Control Logics for 2 Pipe System C 1 5 1 With Thermoelectric Valve Configuration COOL MODE a MTV2 AUX...

Page 16: ...E a MTV2 AUX1 and heater are always off b If Tr 25 C then MTV1 and AUX2 will be ON for 3 minutes and then OFF for 4 minutes c If 16 C Tr 25 C then MTV1 and AUX2 will be ON for 3 minutes and then OFF f...

Page 17: ...the indoor fan runs at set speed POST HEAT a AUX1 is turned off Electrical heater is turned off b Indoor fan will shut down after the unit has been turned off for 20 seconds LOW TEMPERATURE PROTECTIO...

Page 18: ...or 28 C depending on DIP setting then MTV2 and AUX1 are turned on Indoor fan runs at 200RPM b If Ti1 38 C or 30 C depending on DIP setting then MTV2 and AUX1 are turned on Indoor fan runs at set spee...

Page 19: ...ODE a SLEEP mode can only be set when the unit is in COOL or HEAT mode b In COOL mode after SLEEP mode is set the indoor fan will run at low speed and Ts will increase by 2 C over 2 hours c In HEAT mo...

Page 20: ...he system is switched on again the same operations as previously set will function C 1 11 Operation Of Control Panel On High Wall Unit C 1 11 1 On Off Switch a This is a tactile switch to select Cool...

Page 21: ...eck if sensor s resistance is correct or not Return air sensor failure Green LED blinks 3 times stops for 3 secs Room sensor unplugged or damaged 1 Check if Tr plug is connected or not 2 Check if sens...

Page 22: ...19 failure RED LED blinks 19 times stops for 3 secs Check unit 19 communication plug and fix it Unit 20 failure RED LED blinks 20 times stops for 3 secs Check unit 20 communication plug and fix it Uni...

Page 23: ...WC 001 2 Communication plug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B 3 Connection wire 3 1 If the total length of wire is more than 1...

Page 24: ...the slave unit will beep once Using Wall pad to Set Master Control Unit a Connect all the units PCBs according to the wire color and type of connector b Select the master unit by setting DIPA S1 SW6...

Page 25: ...SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave 0 0 0 1 1 0 07 Slave 0 0 0 1 1 1 08 Slave 0 0 1 0 0 0...

Page 26: ...Page 26 of 36 SK2014 SON 002 TechMnl SWC 003 C 3 4 Unit Network Wiring Scheme Wiring diagram for a master slave network connection...

Page 27: ...is selected the unit is not receiving power R 2 Med R 3 Hi Power input Phase L Power supply to the PCB and all the loads connected to the voltage outputs Max length 5 m Neutral N Power supply to the P...

Page 28: ...0 10VDC S2 S4 Speed selection EH CONTROL SIGNAL CN5 CN4 4 3 2 1 ON DIPs1 s4 RY 10A T CN3 GREEN RED _ BLUE Auto speed signal 230V 50HZ 0 5VDC 0 10VDC S1 closed SM2 SM1 EC MOTOR GREY P11 Unit wiring sc...

Page 29: ...700 600 HWN EC 30 0 1 1 1150 800 700 HWN EC 40 1 0 0 1300 1100 900 Default RPM 1 1 1 Set by customer requirement C 4 4 Control Logics Specification 1 Power On Setting When any fan speed is selected th...

Page 30: ...iption For all units Operation LED light Green Item Blink Reason Remedy Indoor coil sensor 1 failure Green LED blinks 4 times stops for 3 secs Ti1 sensor connection is unplugged or damaged 1 Check if...

Page 31: ...D User Interface D 1 Remote Control Handset Attention When unit with handset is the master unit settings are automatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe...

Page 32: ...Page 32 of 36 SK2014 SON 002 TechMnl SWC 003 D 2 Wired Wall Pad D 2 1 Wall Pad Display...

Page 33: ...ess TI M ER button again and OFF symbol blinking indicates OFF timer programming mode The setting method is the same as the ON timer setting above Press TI M ER button again to exit the ON OFF timer s...

Page 34: ...setting The Sleep function is valid in cool or heat modes only i Temperature setting Press or to enter into temperature setting mode The temperature display area blinks indicating the current set temp...

Page 35: ...the wall pad backlight changes to the color red Should there be multiple units having problems addresses and error codes will be shown one after another Error code definition Error Error code Electric...

Page 36: ...ltage Check fuse on board Place in the ON position Check the room control Check fan motor Filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficien...