Congratulations on your purchase of the Aermec WMT10

 

control panel with 

thermostat.  Made of materials of superior quality in strict compliance with 
the safety regulations, the WMT10 is easy to use and will have a long life.

 CHARACTERISTICS

FUNCTIONS

The thermostat maintains the temperature set for the room.

The 

WMT10

 control panel has the following functions:

- cursor to choose the Cooling functioning mode, Off or 

Heating;

- manual season change;
- manual choice of the ventilation speed;
- desired room temperature selection (+10°C÷30°C)
- operation of systems with 2 pipes
- operation of systems with 4 pipes
- operation of systems with 2 pipes (cooling) + electric heater 

(heating)

- thermostat-controlled ventilation; 
- continuous ventilation; 
- continuous ventilation in Cooling mode and thermostat-

controlled ventilation in Heating mode; 

- when it switches on, it starts the fan coil keeping the settings 

that were active before the previous switch-off;

- after a power failure, the fan coil restarts keeping the settings 

that were active before the switch-off;

- air temperature probe incorporated in the panel;

MANUAL

 

CHANGE OVER

Manual selection of the desired functioning mode (Cooling or 
Heating) with the cursor.
For correct operation, before selecting a functioning mode, 
check that the water circulating in the system is at a suitable 
temperature for the desired functioning mode. 
In case of heating with electric heater, the fan coil must be 
electrically powered.

VENTILATION

Three-speed ventilation check, can be selected manually.

The ventilation mode is set in the installation phase, by 
operating the circuit card mobile Jumper (see the image).

CONTINUOUS VENTILATION

The ventilation continues to work even if the set temperature 
is reached, so the temperature is therefore checked by opening 
and closing the water valve(s) fitted in the system.

Do not use this setting in systems without water shut-off 
valves, as ventilation will be continuous, and not controlled 
by the thermostat.

THERMOSTAT-CONTROLLED VENTILATION

The ventilation switches off automatically when the set 
temperature is reached.

CONTINUOUS VENTILATION IN COOLING MODE AND 
THERMOSTAT-CONTROLLED VENTILATION IN HEATING 
MODE

Ventilation in cooling functioning mode is adjusted differently 
from ventilation in the heating mode:
- Cooling (Continuous Ventilation)
- Heating (Thermostat-controlled Ventilation)

The 

WMT10

 regulating thermostat is a control panel for fan 

coils, to be mounted on the wall.
Controls the operating functions of the fan coil according to 
the set mode. The panel must be wall-mounted; it is used in 
systems with 4 tubes, 2 tubes and 2 tubes with resistance, with 
the possibility of connecting two On-Off valves to shut off the 
water feeding the coils.
The panel is electrically protected by an internal fuse.
The ventilation mode operation is chosen in the installation 
phase with Jumper.

Each panel can directly control a single fan coil.
The control panel only consists of mains voltage (230V) 
electrical circuits; all the inputs must therefore be properly 
insulated for this voltage.
The valve servo controls must also be suitable for 230V.
WMT10 must only be installed by expert personnel.
Disconnect the power supply before beginning any installation 
or maintenance operation. Risk of electrocution if live 
components are touched. 

CONNECTION CABLES SPECIFICATIONS
Use H05V-K or N07V-K type cables with 300/500 V with 
insulation, piped or ducted.
Use cables with double H05W-F type insulation for 
installations with cable in sight.

TECHNICAL SPECIFICATIONS:

Power supply: 230V (± 10%)
Input power: 1.5VA
Adjustable temperature range: 10°C - 30°C 
Differential: 1°C
Ambient working conditions: 0°C ÷ 60°C with relative 
humidity 10% ÷ 90%, without condensation.
Ambient storage conditions: -18°C ÷ 60°C with relative 
humidity 10% ÷ 90%, without condensation.
Material: ABS UL94 V0
Colour: RAL9016
Complies with:
Low Voltage directives 73/23 (EN 60730-1, EN 60730-2-9, EN 
60335-1);
Electromagnetic compatibility 89/336 (EN 61000-4-1, EN 
55011, 55022, 55014);
ITS UL783.

Summary of Contents for WMT 10

Page 1: ...ANDE ELECTRONIQUE POUR VENTILO CONVECTEURS INSTALLATION MURALE ELEKTRONISCHE BEDIENTAFEL F R GEBL SEKONVEKTOREN ZUR WANDMONTAGE TABLERO DE MANDOS ELECTR NICO PARA FAN COILS INSTALACI N DE PARED MANUAL...

Page 2: ...racteristics Use Installation Wiring diagrams INDEX 9 10 11 18 Caract ristiques Utilisation Installation Sch mas lectriques TABLE DES MATI RES 12 13 14 18 Technische Daten Verwendung Installation Scha...

Page 3: ...es as ventilation will be continuous and not controlled by the thermostat THERMOSTAT CONTROLLED VENTILATION The ventilation switches off automatically when the set temperature is reached CONTINUOUS VE...

Page 4: ...cted to fan coils for only sensitive cooling TEMPERATURE ADJUSTMENT Select the desired temperature with the knob to increase it turn the knob anticlockwise to decrease it turn it clockwise The values...

Page 5: ...and device is made up of an electronic control panel to be secured to the wall Avoid installing the control panel in places directly exposed to sun rays draughts heat sources and fan coil flow Install...

Page 6: ...tre vie caldo freddo Three way valves heat cool Vanne trois voies chaud froid Dreiwegeventil Heinz K hl V lvula agua de 3 v as calor fr o VF Valvola a tre vie freddo Three way valves cool Vanne trois...

Page 7: ...es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPL NE ESQUEMA...

Reviews: