Heat recovery units with refrigeration circuit -
URX_CF
-
30
Selection and installation manual
GB
10. The compressor does not start due
• Pressure switch out of order
• Check and replace
to the intervention of the
• Machine completely empty
• See point 11)
low pressure switch
• Poor air flow
• Check the air duct and the state of
the filters.
• Blocked refrigerant filter
• Check and replace
•The thermal expansion valve does not
• Check, clean or if necessary
function correctly
replace it.
11. Lack of gas
• Leak in the refrigerating circuit
• Check the refrigerating circuit
with a leak detector
12. Hot liquid pipe
• Lack of refrigerant
• See point 11)
13. The refrigerating circuit functions
• Lack of refrigerant
• See point 11)
correctly but with insufficient
• Presence of humidity or incondensable
• Replace the filter and if necessary
proficiency
in the refrigerating circuit
drain and refill the circuit
14. Compressor suction tube
• Thermal expansion valve
• Check the valve and
frosted
if it is not working
correctly replace it
• Poor air flow
• Check filters, fans and ducts.
• Lack of refrigerant
• See point 11)
• Blocked liquid filter
• Clean or replace
15. Abnormal noise in the system
• Vibrations in the pipes
• Secure the pipes
• Noisy compressor
• Check electrical phases connection
• Noisy thermostatic valve
• Check and add refrigerant
16. Evaporator coil
• Lack of refrigerant in the circuit:
• Check for leaks and eliminate them
before bubbles visible in the indicator.
topping up with refrigerant .
• Thermostatic expansion valve over .
• Reduce the overheating of the
closed: suction pipe too hot
thermostatic expansion valve
turn the valve stem and
check the suction pressure .
• Thermostatic expansion valve over .
• Change the valve or free the
closed: expansion valve bulb
control pipe.
partially blocked or pressure intake pipe
blocked
• Filter-drier blocked: bubbles in the
• Change the filter-drier.
flow indicator and liquid pipe colder
at the filter drier outlet
• The manifold feed pipes are
• Remove the obstruction; clean or change
blocked or oil has accumulated in the
the evaporator.
coil: not all of the evaporator circuits
are working
17. Compressor too hot
•Thermostatic expansion valve
• Reduce the overheating of the
over closed: excessive overheating
thermostatic valve
of the evaporator discharge gas
18. Compressor to cold and noisy
• Expansion valve over open:
• Measure and reset the overheating
the system works with the overheating
by closing the valve
to low (return of liquid to the compressor).
• Thermostatic valve out of order: the stem or • Replace the valve or free the
the seat of the expansion valve is
pressure inlet pipe
corroded. Pressure inlet pipe blocked.
• Foreign objects between the stem and the seat • Clean the stem and the holes of the
of the thermostatic valve: abnormal function thermostatic valve
of the thermostatic valve