17
Air conditioning unit -
TDA range
Selection, installation, use and maintenance manual
AIR CONDITIONING
TDA 15
Temp. of inlet water: 7 °C
Temp. of outlet water: 12 °C
3-row coil (version P)
4-row coil (version /4)
P (m³/h)
Tia (*C)
UmRel(%)
Qtot (kW)
Qsen (kW)
WtrFlow (l/h)
WtrDP (kPa)
Qtot (kW)
Qsen (kW)
WtrFlow (l/h)
WtrDP (kPa)
600
24
50
2.1
2.1
366
1
2.8
2.4
477
2
600
26
50
2.8
2.3
483
1
4.3
3.0
733
4
600
28
50
4.3
2.9
740
3
5.7
3.5
979
7
600
30
50
5.8
3.4
990
5
7.0
4.0
1198
10
600
32
50
7.0
3.8
1211
7
8.2
4.3
1405
13
600
34
50
8.2
4.1
1418
10
9.4
4.7
1621
17
800
24
50
2.6
2.6
453
1
3.2
3.0
551
2
800
26
50
3.2
2.8
549
2
5.8
4.0
1001
7
800
28
50
5.8
3.8
1003
5
7.4
4.6
1280
11
800
30
50
7.3
4.3
1261
8
8.9
5.1
1536
15
800
32
50
8.8
4.7
1516
11
10.5
5.6
1806
20
800
34
50
10.4
5.2
1783
15
12.2
6.1
2090
26
1000
24
50
3.0
3.0
514
2
5.0
4.1
860
5
1000
26
50
5.0
3.8
865
4
7.2
4.9
1236
10
1000
28
50
7.1
4.6
1226
8
8.9
5.5
1529
15
1000
30
50
8.7
5.1
1498
11
10.8
6.2
1852
21
1000
32
50
10.5
5.6
1803
15
12.7
6.8
2188
29
1000
34
50
12.3
6.2
2123
21
14.7
7.3
2530
37
1200
24
50
3.3
3.3
568
2
5.9
4.8
1020
7
1200
26
50
6.1
4.6
1049
6
8.3
5.7
1425
13
1200
28
50
8.1
5.3
1398
10
10.3
6.5
1777
20
1200
30
50
10.0
5.9
1718
14
12.5
7.2
2156
28
1200
32
50
12.0
6.5
2070
20
14.8
7.9
2551
38
1200
34
50
14.1
7.0
2426
26
17.3
8.6
2968
49
1400
24
50
4.2
4.2
726
3
7.0
5.6
1210
10
1400
26
50
7.0
5.2
1205
7
9.3
6.5
1601
16
1400
28
50
9.0
5.9
1554
12
11.6
7.3
2004
24
1400
30
50
11.2
6.6
1920
17
14.1
8.1
2426
34
1400
32
50
13.4
7.2
2304
24
16.7
8.9
2872
47
1400
34
50
15.8
7.9
2716
32
19.6
9.8
3375
62
1600
24
50
4.8
4.8
831
4
7.8
6.3
1339
12
1600
26
50
7.7
5.7
1325
9
10.3
7.2
1771
19
1600
28
50
9.9
6.5
1700
14
12.9
8.1
2220
29
1600
30
50
12.2
7.2
2104
20
15.7
9.0
2694
41
1600
32
50
14.7
7.9
2532
28
18.6
9.9
3195
56
1600
34
50
17.4
8.7
2989
38
–
–
–
–
AIR CONDITIONING
TDA 15
Temp. of inlet water: 5 °C
Temp. of outlet water: 10 °C
3-row coil (version P)
4-row coil (version /4)
P (m³/h)
Tia (*C)
UmRel(%)
Qtot (kW)
Qsen (kW)
WtrFlow (l/h)
WtrDP (kPa)
Qtot (kW)
Qsen (kW)
WtrFlow (l/h)
WtrDP (kPa)
600
24
50
2.8
2.3
484
1
3.9
2.9
677
4
600
26
50
3.8
2.7
652
2
5.4
3.5
935
6
600
28
50
5.4
3.3
934
5
6.7
4.0
1145
9
600
30
50
6.6
3.7
1138
7
7.8
4.4
1349
12
600
32
50
7.9
4.1
1355
9
9.0
4.7
1552
16
600
34
50
9.0
4.5
1555
12
10.3
5.1
1766
20
800
24
50
3.2
2.8
554
2
5.6
4.0
961
7
800
26
50
5.5
3.7
939
5
7.1
4.6
1220
10
800
28
50
7.1
4.3
1218
8
8.6
5.1
1481
14
800
30
50
8.4
4.7
1453
10
10.1
5.6
1732
19
800
32
50
9.9
5.2
1702
14
11.6
6.1
2001
25
800
34
50
11.4
5.6
1965
18
13.3
6.6
2280
31
1000
24
50
4.7
3.7
807
4
6.9
4.9
1194
10
1000
26
50
6.8
4.5
1169
7
8.6
5.6
1482
14
1000
28
50
8.4
5.1
1443
10
10.4
6.2
1784
20
1000
30
50
10.0
5.6
1728
14
12.2
6.8
2098
27
1000
32
50
11.8
6.2
2027
19
14.1
7.4
2419
35
1000
34
50
13.6
6.7
2344
25
16.1
7.9
2766
44
1200
24
50
5.8
4.5
991
5
8.1
5.8
1394
13
1200
26
50
7.9
5.3
1357
9
10.0
6.5
1723
19
1200
28
50
9.6
5.9
1655
13
12.1
7.2
2077
26
1200
30
50
11.5
6.5
1983
18
14.2
7.9
2446
35
1200
32
50
13.5
7.1
2329
25
16.5
8.6
2835
46
1200
34
50
15.7
7.6
2696
32
18.8
9.2
3227
58
1400
24
50
6.7
5.1
1154
7
9.1
6.5
1568
16
1400
26
50
8.8
5.9
1510
11
11.3
7.4
1951
23
1400
28
50
10.8
6.6
1852
16
13.6
8.2
2339
33
1400
30
50
12.8
7.2
2210
22
16.2
9.0
2779
44
1400
32
50
15.1
7.9
2594
30
18.7
9.8
3224
58
1400
34
50
17.5
8.5
3004
39
–
–
–
–
1600
24
50
7.5
5.7
1297
9
10.1
7.2
1732
19
1600
26
50
9.6
6.5
1651
13
12.5
8.2
2154
28
1600
28
50
11.8
7.2
2029
19
15.1
9.1
2597
39
1600
30
50
14.1
7.9
2428
27
17.8
9.9
3065
53
1600
32
50
16.6
8.6
2855
36
20.7
10.8
3561
69
1600
34
50
19.2
9.3
3310
46
–
–
–
–