15
The following pages are related
to the tables concerning the
performance of the heat exchange
coils for the typical combinations of
heat vector fluid temperature and
hygrothermometric characteristics of
the incoming air.
The values for the direct expansion
coils refer to operation with R407C
refrigerant.
Key:
P
Air flow rate [m³/h]
Tia
Temperature of incoming air [°C]
UmRel
Relative humidity (%)
Qtot
Total heating capacity [kW]
Qsen
Sensible heating capacity [kW]
WtrFlow
Water flow rate [l/h]
WtrDP
Water side pressure drops [kPa]
RefrDP
Refrigerant side pressure drops [kPa]
Tables showing heat exchange coil output
Electric heat exchange coils
TDA 09
TDA 15
TDA 21
TDA 28
TDA 37
Electric coil output
kW
4
6
8
10
12
Voltage - Phases
V - n.
230V~
400V / 3 ~
400V / 3 ~
400V / 3 ~
400V / 3 ~
No. of stages
no.
1
1
1
2
2
Table showing operating limits
Temperature of coil inlet air (summer)
min
21 °C
max
34 °C
Temperature of coil inlet air (winter)
min
-5 °C (*)
max
24 °C
Relative humidity (summer-winter)
min
20%
max
90%
Temperature of coil inlet water (H
2
O Cold)
min
4 °C
max
12 °C
Heat range (H
2
O Cold)
min
5 °C
max
8 °C
Temperature of coil inlet water (H
2
O Hot)
min
40 °C
max
80 °C
Heat range (H
2
O Hot)
min
5 °C
max
25 °C
Evaporation temperature
min
2 °C
max
12 °C
(*) envisage anti-freeze protection
Air conditioning unit -
TDA range
Selection, installation, use and maintenance manual