background image

13

GB

COIL ROTATION

If for plumbing reasons it is necessary to rotate the coils,
after removing the mobile section, proceeds as follows:
– remove the electrical connections from the terminal strip;
– remove the screws fixing the basin and remove it;
– remove the screws fixing the coil and remove it;
– remove the partially cut parts from the right-hand side;
– rotate the coil and fix it with the previously removed

screws;

– refit the basin fixing it in position with the screws, insert

the plastic caps supplied, in the holes left free by the
plumbing connections;
all the basins can be used for drainage on both sides. 

N.B.: Before connecting the condensate drainage pipe,

push in the diaphragm off the basin (if present) on the
plumbing attachment side, seal the drainage not used
with the cap provided.

– slide out the electrical connection from the right-hand

sided, remove the partially cut section and move the
cable fairlead from the right-hand side to the left;

– move the motor cable on the left hand side and pass it

through the cable fairlead ;

– move the terminal block and the U-bolt of the ground on

the left-hand side;

– restore the motor wire electrical connections;

L

N

Follow the wiring diagram with the equipment and shown
in this document when making the connections.

To protect the unit against short circuits, fit an omnipolar
thermal-magnetic trip 2A 250V (IG) to the power line with
a minimum contact opening distance of 3 mm.
Each control panel can control a single fan coil.

ELECTROSTATICALLY PRE-CHARGED AIR FILTER

Fire Resistance Class 2 (UL 900). 
Easy to remove, it is supplied in a sealed box only to be
opened when it is to be used.
The electrostatically precharged filter is combined to the
normal mechanical filtration of the air that passes through
the filter, also electrostatic attraction of the dust will noti-
ceably increase its filtration.
The electrostatic precharge of the filter is spent after two
years of the box being opened, after this period it behaves
like a normal filter. 
For this reason replacement over two years with a new one
is recommended (available as a spare part from Aermec
after-sales centres).
Cleaning frequently, removing the dust that has built up
using a vacuum, the use of water and cleaning substances
considerably speeds up the electrostatic precharge deterio-
ration.

Summary of Contents for Omnia UL P

Page 1: ...horizontale ou verticale et avec Ventilo coffrage Gebläsekonvektor zur horizontal oder vertikal kanalisierten Installation und Installation mit Schalungssystem Fan coil de instalación en canal horizontal o vertical y con Ventilcassaforma Omnia UL P Sostituisce Replace Remplace Ersetzt 6904705_01 0504 MANUALE D USO E INSTALLAZIONE USE AND INSTALLATION MANUAL MANUEL D UTILISATION ET D INSTALLATION B...

Page 2: ... 14 Remedy Wiring diagram 15 Dimensions 17 Description de l unité Omnia UL P Emploi Caracteristiques de fonctionnement Emballage Installation de l unité Connexions electriques 20 Filtre d air à précharge électrostatique Rotation batterie 21 Informations importantes sur la maintenance 22 Solution Schemas electriques 23 Dimensions 25 Beschreibung des Gerätes Omnia UL P Gebrauch Betriebsmerkmale Verp...

Page 3: ...nia UL auquel cette déclaration fait référence est conforme aux normes harmonisées suivantes EN 60335 2 40 EN 55014 1 EN 55014 2 EN 61000 6 1 EN 61000 6 3 satisfaisant ainsi aux conditions essentielles des directives suivantes Directive LVD 2006 95 CE Directive compatibilité électromagnétique 2004 108 CE Directive Machines 98 37 CE OMNIA UL PLUS ACCESSOIRES Il est interdit de faire fonctionner l a...

Page 4: ...e drainage with the consequent spil ling of liquid The fancoils used for the cooling must be attached to a con densate draining system The assembly site must be chosen in such a way that the maximum and minimum ambient temperature limits are respected 0 45 C 85 U R To install the unit proceed as follows The filter is fitted in a sealed package to prevent the loss of its electrostatic charge open t...

Page 5: ...l block and the U bolt of the ground on the left hand side restore the motor wire electrical connections L N Follow the wiring diagram with the equipment and shown in this document when making the connections To protect the unit against short circuits fit an omnipolar thermal magnetic trip 2A 250V IG to the power line with a minimum contact opening distance of 3 mm Each control panel can control a...

Page 6: ...tandards of hygiene CLEANING PERIODICALLY THE FILTER Frequently cleaning the filter guarantees greater operating efficiency Check whether the filter is very dirty in this case repeat the operation more often Cleaning frequently removing the dust that has built up using a vacuum the use of water and cleaning substances conside rably speeds up the electrostatic precharge deterioration When the filte...

Page 7: ...r See control panel settings Control the power supply Please check up the boiler or the chiller Check up the thermostat settings Increase the water temperature beyond the minimum limits indicated in the technical booklet For anomalies don t hesitate contact the aftersales service immediately PROBLEM AND REMEDY WIRING DIAGRAMS READING KEY M 1 2 3 4 5 L 6 N 7 M 1 8 MAX 9 MED 10 MIN PE PE IG MV BL NE...

Page 8: ... 2 3 4 GR 5 L 6 N 7 M 1 NE 8 MAX MA 9 MED RO 10 MIN PE PE IG MV BL NE MA RO Sez 1 5 mm2 1 230V 50Hz OMNIA UL PX2 SW SC Y1 V3 V2 V1 M EX N N PE L N M SA M SW T C OFF VEL BL GR RO MA NE E X SA M 1 2 3 4 5 L 6 N 7 M 1 8 MAX 9 MED 10 MIN PE PE IG MV BL NE MA RO Sez 1 5 mm2 VCH 1 230V 50Hz OMNIA UL P PXL2E Wiring diagrams may change for updating It is therefore necessary to refer always to the wiring d...

Page 9: ...male Mod Omnia UL 11 P Omnia UL 16 P Omnia UL 26 P Omnia UL 36 P 3 R 1 2 1 2 1 2 1 2 DIMENSIONS mm 145 196 80 E C B D 13 6 5 10 10 6 5 14 5 60 465 86 Mod UL 10 P UL 15 P UL 25 P UL 35 P B 384 494 725 945 C 360 5 470 5 701 5 921 5 D 288 398 629 849 E 394 504 735 955 GB ...

Page 10: ...18 DIMENSIONS mm GB 30 mm 400mm 200mm 100mm ...

Reviews: