HL L DIPSWITC
H CONFIGURATION
Sw 1
ON
OFF
Sw 2
Dipswitch 1 (Default OFF)
Thermostatic temperature control:
- for operation at modulated power, set to OFF
- for 3-level operation, set to ON
Dipswitch 2 (Default OFF)
Adjustment band:
- for standard, set to OFF
- for extended, set to ON
Dipswitch 3 (Default ON)
Louver control:
- for manual control, set to OFF
- for motorised control, set to ON
Dipswitch 4 (Default OFF)
Probe correction:
- for dynamic correction of values, set to OFF
- for fixed correction of values, set to ON
Dipswitch 5 (Default OFF)
Enable heating mode according to water temperature:
- for normal heating mode (39°C), set to OFF
- for reduced Heating (35°C), set to ON
Dipswitch 6 (Default OFF)
Enable cooling mode according to water temperature:
- for normal cooling mode (17°C), set to OFF
- for reduced cooling (22°C), set to ON
SETTING OF THE CONTROL PANEL DIP-SWITCH
Configuration of dipswitches must only be carried out by qualified personnel during unit installation.
Always disconnect the power supply before performing this operation.
Adjust the dipswitches inside the thermostat for the following functions:
DRIVER BOARD DIP-SWITCH CONFIGURATION
Power the unit down. Configuration of dipswitches must only be carried out by qualified personnel during unit installation.
Dip 1 (Default OFF )
Dip 2 (Default OFF )
Preset in factory
Fin opening management:
-Complete opening (wall-mount installations), OFF.
-Reduced opening (recess installations), ON.
Sw 2
Dip 1 (Default OFF )
Preset in factory
Dip 2 (Default OFF )
Preset in factory
Dip 3 (Default OFF)
Preset in factory
Dip 4 (Default OFF)
Preset in factory
*
*
*
*
*
*
ON
OFF
1
2
3 4
5
6
Sw 1
*
*
*
*
ON
OFF
1
2
3 4
Sw 2
*
*
ON
OFF
1
2
Sw
=
*
Thermostatic control with Modulated Power
Normal regulation band
Normal Cooling Enabling (water 17°C)
Normal Heating Enabling (water 39°C)
Dynamic Probe Correction
Manual slat management
Pre-calibrated in the factory
Pre-calibrated in the factory
Pre-calibrated in the factory
Pre-calibrated in the factory
Wide regulation band
Motorised slat management
Fixed probe correction Warm (4°C)
Reduced Heating Enabling (water 35°C)
Reduced Cooling Enabling (water 22°C)
Three step thermostat control
Factory settings
Reduced opening of the slat (recess installation)
Complete opening of the slat (wall-mounted installation)
Pre-calibrated in the factory
Driver Card
Summary of Contents for Omnia HL 11 CM
Page 28: ...28 ACCESSORIES DATA DRIP TRAY BC10 DRIP TRAY BC20 ...
Page 40: ...40 INSTALLATION DIAGRAMS L N OMNIA HL ...
Page 41: ...41 L N INSTALLATION DIAGRAMS OMNIA HL L L N OMNIA HL C ...
Page 42: ...42 INSTALLATION DIAGRAMS L N OMNIA HL S L N OMNIA HL PC ...
Page 47: ...47 ...
Page 48: ......
Page 49: ......