Water flow [l/h]
The pressure drops in the charts above refer to an average water temperature of 10 °C. The following table shows the cor-
rections to apply to the pressure drops with a variation in average water temperature.
Average water temperature
°C
5
10
15
20
50
60
70
Correction factor
1,03
1
0,96
0,91
0,78
0,75
0,72
TAV.9
COIL PRESSURE DROP
Coil pressure drop (kPa)
HL 36
HL 26
HL 16
HL 11