![AERMEC Omnia HL 11 CM Technical And Installation Booklet Download Page 19](http://html.mh-extra.com/html/aermec/omnia-hl-11-cm/omnia-hl-11-cm_technical-and-installation-booklet_2862018019.webp)
19
Tw [°C]
∆∆
t
Ta b.u. [°C]
Pc
Ps
Pc
Ps
Pc
Ps
Pc
Ps
Pc
Ps
Pc
Ps
21°C Ta b.s.
23°C Ta b.s.
25°C Ta b.s.
27°C Ta b.s.
29°C Ta b.s.
30°C Ta b.s.
15
-
-
-
-
-
-
-
-
-
-
-
-
17
805
659
1109
909
1563
1281
1962
1608
2341
1919
2708
2219
3
19
995
582
1222
916
1595
1286
1968
1613
2348
1924
2714
2224
21
-
-
2463
990
2431
1280
2483
1588
2618
1907
2817
2226
23
-
-
-
-
3782
1316
3756
1601
3737
1896
3718
2187
15
-
-
-
-
-
-
-
-
-
-
-
-
17
-
-
-
-
-
-
-
-
-
-
-
-
13
5
19
647
449
895
670
1180
967
1466
1202
1756
1439
2193
1797
21
-
-
1147
602
1292
905
1501
1191
1759
1441
2199
1802
23
-
-
-
-
2019
810
2032
1108
2223
1426
2547
1805
15
-
-
-
-
-
-
-
-
-
-
-
-
17
-
-
-
-
-
-
-
-
-
-
-
-
7
19
-
-
-
-
-
-
-
-
-
-
-
-
21
-
-
761
473
1006
771
1260
1033
1543
1265
1830
1499
23
-
-
-
-
1305
618
1447
923
1640
1216
1865
1491
15
-
-
-
-
-
-
-
-
-
-
-
-
17
-
-
-
-
-
-
-
-
-
-
-
-
3
19
543
411
811
665
1148
941
1588
1302
1981
1623
2354
1929
21
-
-
1048
574
1363
944
1672
1296
1984
1626
2360
1934
23
-
-
-
-
2714
1002
2701
1296
2701
1592
2798
1903
15
-
-
-
-
-
-
-
-
-
-
-
-
17
-
-
-
-
-
-
-
-
-
-
-
-
15
5
19
-
-
-
-
-
-
-
-
-
-
-
-
21
-
-
659
440
903
726
1180
967
1466
1202
1781
1460
23
-
-
-
-
1183
586
1325
889
1524
1178
1807
1472
15
-
-
-
-
-
-
-
-
-
-
-
-
17
-
-
-
-
-
-
-
-
-
-
-
-
7
19
-
-
-
-
-
-
-
-
-
-
-
-
21
-
-
-
-
-
-
-
-
-
-
-
-
23
-
-
-
-
776
461
1019
760
1270
1028
1543
1265
Tw [°C]
= Inlet water temperature
Ta w.b.[°C]
= Inlet wet bulbe air temperature
Ta b.s.[°C]
= Dry bulbe air temperature
Pc [W]
= Total cooling capacity
Ps [W]
= Sensible cooling capacity
NOTE: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification In this case
consider only the values of sensible capacity.
Cooling capacities are referred to high speed.
To obtain values for other speed, multiply the values read by following factors:
MOD.
HL 36
Medium speed
total capacity
0,82
sensible capacity
0,87
Minimum speed
total capacity
0,61
sensible capacity
0,63
Summary of Contents for Omnia HL 11 CM
Page 28: ...28 ACCESSORIES DATA DRIP TRAY BC10 DRIP TRAY BC20 ...
Page 40: ...40 INSTALLATION DIAGRAMS L N OMNIA HL ...
Page 41: ...41 L N INSTALLATION DIAGRAMS OMNIA HL L L N OMNIA HL C ...
Page 42: ...42 INSTALLATION DIAGRAMS L N OMNIA HL S L N OMNIA HL PC ...
Page 47: ...47 ...
Page 48: ......
Page 49: ......