EN - 9
NLC_A COD: 1606.4037360_00
9.
ELECTRICAL DATA TABLE
L1
L2
L3
PHASE
EARTH (PE)
Power Supply:
Model
Vers.*
Power
No.
Compressors No. Fans
Total absorption
Recommended cable sec. for Lmax = 50 m / 1 968,50 Inch
LRA
MCA
MOP
Fuse
(recommended No. Phases No. cables
per phase
Sec. Phase
Sec. PE
IL
[A]
[A]
[A]
[A]
[mm²]
[mm²]
[A]
NLC0750
A
575/3/60
4
6
223,7
121,6
145,3
125
3
1
50
25
200