background image

8 - EN

EN

NLC_A cod: 1606.4037360_00

8. 

ELECTRICAL WIRINGS

The NLC units are fully wired in the factory and only 

require connection 

to the electrical mains and the wiring of the flow switch (see the wiring 

diagram supplied)

, downstream of a unit switch, as provided for by the reg-

ulations in force in the country of installation. 

It is also suggested to check:

1.  the characteristics of the electrical network are suitable for the ab-

sorptions indicated in the electric data table. The unit should only be 

powered when the installation work has finished (hydraulic and elec-

tric).

2.  Respect the connection indications of the phase and earth wires.

3.  The power supply line will have a relevant protection upstream against 

short circuits and dispersions to earth that isolate the system with re-

spect to other utilities.

4.  The voltage must be within a tolerance of ± 10% of the nominal power 

supply voltage of the machine (for unbalanced three-phase unit max 

3% between the phases). If these parameters are not respected, con-

tact the energy supplier. 

5.  For electrical wirings use isolated double cables according to the 

standards in force in the different countries.

MANDATORY

1.  It is necessary to use a omnipolar thermomagnetic switch, in compli-

ance with the CEI-EN standards (contact opening of at least 3 mm), 

with adequate switch capability and differential protection based on 

the followed electrical data table, installed as close as possible to the 

machine.

2.  It is necessary to carry out an efficient earth connection. The manufac-

turer can not be held responsible for any damage caused by the lack or 

ineffective earthing of the appliance.

3.  For units with three-phase power supply check the correct connection 

of the phases. 

The cable sections indicated in the table are advised for a maximum length 

of 50 m.

For higher lengths or different types of cable installation, it will be the DE-

SIGNERS responsibility to carefully measure the line main switch, the supply 

power line and the earthing protection connection, and the working con-

nection cables:

• 

the length

• 

the type of cable

• 

Absorption of the unit and its physical position, and room tempera-

ture.

CONNECTION OF THE POWER SUPPLY TO THE MAINS

Before connecting the unit to the power supply mains, make sure that the 

isolating switch is open.

Open the front panel.

Use the holes in the bottom part of the framework for the main electric 

power supply cable and for the cables of the other external connections 

under the responsibility of the installer.

It is prohibited to access positions with electric cables not specifically 

indicated in this manual.

Avoid direct contact with the non-insulated copper piping and with the 

compressor. 

Provide electrical connection as per wiring diagram supplied with the unit.

Put back the inspection panels.

Make sure that all the protections removed for the electrical connection 

are put back before powering up the unit.

Set the master switch (on the outside of the appliance) to “ON”.

WARNING

All electrical operations must be carried out BY QUALIFIED PERSONNEL, 

IN ACCORDANCE WITH THE CORRESPONDING REGULATIONS, trained 

and informed about the risks related to such operations.

The characteristics of electric lines and related components must be 

established by PERSONNEL AUTHORISED TO DESIGN ELECTRIC 

INSTALLATIONS,  following international regulations and the national 

regulations of the country in which the unit is installed, in compliance with 

the legislative regulations in force at the moment of installation

.

For installation requirements, refer to the wiring diagram supplied with 

the unit.  The wiring diagram together with the manuals must be kept in 

good conditions and readily ACCESSIBLE FOR FUTURE OPERATIONS ON 

THE UNIT.

IT IS compulsory to check the machine sealing before connecting the 

electrical wiring. The machine should only be powered once the hydraulic 

and electric operations are completed.

It is forbidden to use the water pipes to earth the appliance.

 

Check that all power cables are correctly secured to the terminals when 

switched on for the first time and after 30 days of use. Afterwards, check 

them every six months. 

Slack terminals could cause the cables and components to overheat.

WARNING

Before carrying out any work, make sure the 

electricity supply is unplugged.

B

B

A

A

Condensate discharge pipe

Electrical cables inlet

The condensate discharge 

tubes are supplied with the 

unit, and must be screwed to 

the two fittings mounted on 

the tray.

The voltage should be within a tolerance of ± 10% 

of the rated supply voltage of the machine (for 

unbalanced three-phase units max 3% between 

the phases). 

WIRING OF THE FLOW SWITCH IN THE ELECTRICAL PANEL

Connect the flow switch (accessory) to the J5 terminal board of 

the pCO5+ electronic regulation (refere to the wiring diagram 

supplied).

Summary of Contents for NLC

Page 1: ...Installation Manual IT EN FR Chiller Air Water Indoor Installation 1606 4037360_00 NLC 0750 A...

Page 2: ...g top quality materials and advanced technologies We constantly monitor the quality level and as a result AERMEC products are synonymous with Safety Quality and Reliability Aermec reserves the right t...

Page 3: ...rical wirings 8 9 Electrical data table 9 10 Electronic regulation pCO5 10 11 Loading the system 16 12 System discharge 16 13 Draining the machine 16 14 Control and first start up 17 15 Calibration of...

Page 4: ...not modify or tamper with the chiller as this may cause dangerous situations and the manufacturer will not be liable for any damage caused The warranty shall not be valid if the indications mentioned...

Page 5: ...ric part is allowed 4 MINIMUM TECHNICAL CLEARANCES 500 mm 19 69 in 800 mm 31 50 in 800 mm 31 50 in 1000 mm 39 37 in 5 OPERATION OF THE NLC UNIT The chillers and the heat pumps of the NLC range are air...

Page 6: ...rameter fans max Volts V 0750 69000 40611 866 6 6 8 3 7 5 8 7 8 3 9 2 9 2 9 6 10 0 10 0 400 WARNING The weight of the piping must not be borne by the appliance WARNING Remove the safety protections be...

Page 7: ...TALLER 3 Air drain valve 4 Pump 5 Safety valve obligatory 6 Water filter obligatory 7 Anti vibration joints 8 Pressure gauge 9 Flow switch obligatory 10 Water drain cock 11 Expansion tank 12 Electric...

Page 8: ...n the front panel Use the holes in the bottom part of the framework for the main electric power supply cable and for the cables of the other external connections under the responsibility of the instal...

Page 9: ...PE Power Supply Model Vers Power No Compressors No Fans Total absorption Recommended cable sec for Lmax 50 m 1 968 50 Inch LRA MCA MOP Fuse recommended No Phases No cables per phase Sec Phase Sec PE I...

Page 10: ...ctical Heater OFF ON Temperature 5 C 4 C Circulating Pump OFF ON Temperature 5 C 4 C Only for pure water not added with glycol WATER FLOW ALARM If the water ow rate is not su cient this safety stops t...

Page 11: ...KIT PGD1 Accessory S90CONN cavo di collegamento telephone cable External Alarm J15 N08 C8 NC8 Circulating Pump J12 N01 CP01 Remote Control PGD1 Circulating Pump J22 N018 CP02 External Circuit Breaker...

Page 12: ...meter Key Fucntion ALARM key Displays the list of active and historical alarms red LED on active alarm MENU ACTIVATION key Pressing this key activates the navigation between menus orange LED on winter...

Page 13: ...ERforchange Language Timeshowmask English ESCtoconfirm 20 A Remaining time for software loading this value shows the remain ing time to starting the software loaded on the unit and passing the to syst...

Page 14: ...ded that these parameters are only modi ed by personnel quali ed in the installation and con guration of the unit Menu structure and navigation Index Icon Menu Menu function A MAIN The screens in this...

Page 15: ...he procedure 1 it is possible to move between the screens using the arrow keys the key to move to the previous parameter and the key to move to the next parameter c When the desired parameter is seen...

Page 16: ...onding terminals 13 DRAINING THE MACHINE WARNING During the winter if the system is shut down the water in the heat exchanger could freeze causing irreparable damage to the heat exchanger itself To av...

Page 17: ...tween the evaporator inlet and outlet and then calculate the flow rate with the evaporator pressure drop diagram in the this documentation Make sure the flow switches are working correctly installatio...

Page 18: ...ff NLC A 0750 Compressor magnetothermic switches calibrations MTC1 A 24 MTC1A A 24 MTC2 A 27 MTC2A A 27 Calibration fan thermomagnetic switch MTV1 A 4 8 MTV2 A 4 8 MTV2A A 4 8 High pressure safety val...

Page 19: ...check its efficiency MECHANICAL CONTROLS CONTROL The tightening of the screws the compressors and the electrical box and the exterior panelling of the unit If they are poorly tightened they produce a...

Page 20: ...erating limits Check the operating limits using the graphics Pressure switch malfunctioning Replace the component Circuit breaker protection intervention Check the power supply voltage and calibra tio...

Page 21: ...ot kg XG mm YG mm P P P P P P 0750 00 2156 2312 534 195 9 207 10 627 29 664 31 224 10 238 11 428 MACHINE WHEN OPERATING 1 2 3 4 5 6 AVX NLC A Vers Ptot kg XG mm YG mm P P P P P P 0750 00 2177 2251 547...

Page 22: ...A ESTONIA raigo vesiroos com FINLAND AERMEC SUOMI OY Hautakorventie 9 90620 Oulu Ph 358 40 149 3449 keijo ojala aermec fi AERMEC SUOMI OY Microkatu 1 70210 kuopio Ph 358 40 674 2509 ilpo laitinen aerm...

Page 23: ...11070 Novi Beograd Ph 381 113187383 Fax 381 113187387 akting eunet rs SLOVAKIA KLIMA TEAM s r o Trnavska 63 82101 Bratislava Ph 421 2 43293969 Fax 421 2 43420079 mail klimateam sk SLOVENIA BOSSPLAST...

Page 24: ...pier AERMEC S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 www aermec com Aermec reserves the right to make all modification deemed necessary for improving the prod...

Reviews: