OPERATING LIMITS

Maximum water inlet temperature

.................176°F / 80 °C

Maximum working pressure

...........................115psi / 8 bar

The assembling place must be chosen so that the max. and
min. room temperature limit is respected 32÷113°F /
0÷45°C (<85% U.R.).

Average minimum water temperature

To prevent the formation of condensation on the exterior of
the unit while the fan is operating. the average water tempe-
rature should not drop beneath the limits shown in the table
below. determined by the ambient conditions. 
These limits refer to unit operation with fan at minimum
speed. 
Note that condensation may form on the exterior of the unit
if cold water circulates through the coil while the fan is off
for prolonged periods of time. so it is advisable to fit the
additional three-way valve . 

Water flow limits for 1-row coil:

Limites de débit pour batterie à 1 rangs:

MOD.

FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX 102

Minimum water flow

• Débit minimum

l/h

50

50

50

50

50

100

100

100

gpm 0.22

0.22

0.22

0.22

0.22

0.44

0.44

0.44

Minimum water flow

• Débit minimum

l/h

400

400

400

400

400

900

900

900

gpm 1.76

1.76

1.76

1.76

1.76

3.96

3.96

3.96

Water flow limits for 3-row coil:

Limites de débit pour batterie à 3 rangs:

MOD.

FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62

FCX82 FCX 102

Minimum water flow

• Débit minimum

l/h

100

100

100

150

150

300

300

300

gpm 0.44

0.44

0.44

0.66

0.66

1.32

1.32

1.32

Maximum water flow

• Débit maximum

l/h

750

750

750

1100

1100

2200

2200

2200

gpm 3.3

3.3

3.3

4.84

4.84

9.68

9.68

9.68

Water flow limits for 4-row coil:

Limites de débit pour batterie à 4 rangs:

MOD.

FCX 24 FCX 34 FCX 44 FCX 54 FCX 64

FCX84

Minimum water flow

• Débit minimum

l/h

150

150

150

150

300

300

gpm

0.66

0.66

0.66

0.66

1.32

1.32

Minimum water flow

• Débit minimum

l/h

1100

1100

1100

1100

2200

2200

gpm

4.84

4.84

4.84

4.84

9.68

9.68

LIMITES DE FONCTIONNEMENT

Température maximale d’entrée de l’eau

......176°F / 80 °C

Pression maximale de fonctionnement

..........115psi / 8 bar

Lors du choix du lieu de montage, s'assurer que la plage de
température ambiante maximum et minimum est respectée,
à savoir 32÷113°F / 0÷45°C (<85% U.R .).

Température moyenne minimale de l'eau

Pour éviter des phénomènes de condensation sur la structu-
re extérieure de l'appareil, la température moyenne de l'eau
ne doit pas être inférieure aux limites indiquées dans le
tableau ci-dessous, qui dépendent des conditions thermo-
hygrométriques de l'air ambiant.
Les limites précitées se rapportent au fonctionnement à la
vitesse minimale.
En cas de longue période avec ventilateur éteint  et passage
d'eau froide dans la batterie la formation de condensas à
l'extérieur de l'appareil est possible , il est conseillé d'insérer
l'accessoire vanne 3 voies.

MINIMUM AVERAGE WATER TEMPERATURE

TEMPÉRATURE MINIMUM MOYENNE DE L’EAU

Dry bulb temperature °F / °C

Température bulbe sèche  °F / °C

70 / 21

73 / 23

77 / 25

80 / 27

84 / 29

88 / 31

59 / 15

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

Wet bulb temperature 

°F / °C

62.6 / 17

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

66.2 / 19

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

37.4 / 3

Température bulbe humide °F / °C

69.8 / 21

48.2 / 6

41 / 5

39.2 / 4

37.4 / 3

37.4 / 3

37.4 / 3

73.4 / 23

-

46.4 / 8

44.6 / 7

42.8 / 6

41 / 5

41 / 5

Summary of Contents for FCX US

Page 1: ...U A L IT Y S Y S T E M IFCXUSLN 0508 4033600_03 FAN COIL VENTILO CONVECTEURS FCX US VERTICAL WALL INSTALLATION INSTALLATION VERTICALE SUR PAROI Replace Remplace le n 4033600_02 0505 DIRECTION FOR USE AND INSTALLATION MANUEL DE FONCTIONNEMENT ET D INSTALLATION ...

Page 2: ...EEC 93 68 EEC Directive basse tension 73 23 EEC Direttiva compatibilità elettromagnetica EMC 89 36 EEC KONFORMITÄTSERKLÄRUNG Wir Unterzeichner dieser Bescheinigung bestätigen daß diese Geräte den Vorschriften Vorschrift Geräte 89 392 EWG und entersprechende ergänzungen 91 368 EWG 93 44 EWG 93 68 EWG Niederspannung Vorschrift 73 23 EWG Funkentstörung Vorschrift EMC 89 36 EWG DECLARACION DE CONFORMI...

Page 3: ... 7 Direct expansion coil Batterie à détente directe 8 Operation limits Limites de fonctionnement 9 Wiring diagrams Schemas eléctriques 10 INSTALLATION INSTALATION Packing Unit installation Electrical connections l Emballage Installation de l unité Raccordements electriques 12 SAFETY MEASURES MISURES DE SECURITE Carriage Transport Safety symbol Simboles de securite 14 IMPROPER USES ENTRETIEN MANITE...

Page 4: ...66 8 66 8 66 8 66 8 66 8 66 D inches 3 94 3 94 3 94 3 94 3 94 3 94 3 94 3 94 E inches 1 97 1 97 1 97 1 97 1 97 1 97 1 97 1 97 Weight lbs 28 66 33 07 44 09 52 91 52 91 74 96 74 96 74 96 Poids 3 R 1 2 F 1 2 F 1 2 F 3 4 F 3 4 F 3 4 F 3 4 F 3 4 F Metric system Systéme métrique A mm 487 487 487 487 487 590 590 590 B mm 640 750 980 1200 1200 1320 1320 1320 C mm 220 220 220 220 220 220 220 220 D mm 100 1...

Page 5: ...US FCX 84US A inches 22 56 31 65 40 31 40 31 45 60 45 60 B inches 20 55 29 65 38 31 38 31 44 17 44 17 C inches 17 32 26 42 35 08 35 08 43 39 43 39 Weight Poids lbs 29 76 41 89 50 71 50 71 78 26 78 26 4 R 3 4 F 3 4 F 3 4 F 3 4 F 3 4 F 3 4 F C B 13 78 9 76 0 55 0 55 8 50 1 61 4 21 1 26 9 96 21 97 A 35 x 0 79 4 33 1 54 5 55 8 50 3 78 2 36 21 97 C 1 97 1 97 B A 35 x 0 79 15 28 8 50 1 61 3 98 1 93 5 67...

Page 6: ...0 FCX 62 FCX 82 FCX 102 FCX 24 FCX 34 FCX 44 FCX 54 FCX 64 FCX 84 US measure system Systéme de mesure US inches A 15 91 15 91 15 91 15 91 15 91 20 71 20 71 20 71 B 10 24 10 24 10 24 10 24 10 24 10 75 10 75 10 75 C 6 02 6 02 6 02 6 02 6 02 6 69 6 69 6 69 D 1 61 1 61 1 61 1 61 1 61 1 61 1 61 1 61 E 5 59 5 59 5 59 5 59 5 59 5 83 5 83 5 83 F 7 64 7 64 7 64 7 64 7 64 7 64 7 64 7 64 Metric system Metric...

Page 7: ... FCX 34 FCX 44 FCX 54 FCX 64 FCX 84 US measure system Systéme de mesure US inches A 16 06 16 06 16 06 16 06 20 43 20 43 B 12 72 12 72 12 72 12 72 14 88 14 88 C 6 02 6 02 6 02 6 02 6 69 6 69 D 3 78 3 78 3 78 3 78 3 78 3 78 E 6 10 6 10 6 10 6 10 6 14 6 14 F 7 64 7 64 7 64 7 64 7 64 7 64 Metric system Metric system mm A 408 408 408 408 519 519 B 323 323 323 323 378 378 C 153 153 153 153 170 170 D 96 ...

Page 8: ...0 Ø 1 3 8 3 8 Ø 2 1 2 5 8 Cooling connections on all FCX models fitted with direct expansion coil are located on the right side of the unit the control panel must therefore be positioned on the left side The coil cannot be rotated on these models Dans tous les modèles FCX équipés d une batterie à déten te directe les raccordements frigorifiques se trouvent à droite l éventuel panneau de commande d...

Page 9: ... 84 4 84 9 68 9 68 9 68 Water flow limits for 4 row coil Limites de débit pour batterie à 4 rangs MOD FCX 24 FCX 34 FCX 44 FCX 54 FCX 64 FCX84 Minimum water flow Débit minimum l h 150 150 150 150 300 300 gpm 0 66 0 66 0 66 0 66 1 32 1 32 Minimum water flow Débit minimum l h 1100 1100 1100 1100 2200 2200 gpm 4 84 4 84 4 84 4 84 9 68 9 68 LIMITES DE FONCTIONNEMENT Température maximale d entrée de l ...

Page 10: ...nts not supplied Composants non fournis Optional components Composants en option On site wiring Raccordements à effectuer in situ BL Blue Bleu MA Brown Marron NE Black Noir RO Red Rouge WIRING DIAGRAMS SCHEMAS ELECTRIQUES N V1 V2 V3 V4 M 1 VF N VC M L MV BL NE MA RO MIN MED MAX POWERSUPPL Y IG L N N L READING KEY LEGENDE FCX US universal vertical wall or horizontal wall installation no controls FC...

Page 11: ...11 NE NE NE N V1 V2 V3 N M 1 VC MAX MED MIN M L MV BL POWERSUPPL Y V4 VF BL RO RO NE NE MA RO F IG L N N L RE TSRM TSR CRE CRE 14 11 24 21 C 2 C 1 A1 A2 WIRING DIAGRAMS SCHEMAS ELECTRIQUES FCX US R ...

Page 12: ...e doivent être exé cutés que par des personnes en possession de la qualification technico professionnelle requise pour l habilitation à l installa tion la transformation le développement et l entretien des installations et en mesure de vérifier ces dernières aux fins de la sécurité et de la fonctionnalité ATTENTION l installation électrique doit être en confor mité avec le Code Electrique National...

Page 13: ...13 A A B B A B Fig 2 Fig 1 Fig 3 7 9 4 5 6 3 8 10 11 Fig 4 ...

Page 14: ...control the packing for the arrow position to know the num ber of machines that can be stacked Empilement vérifier sur l emballage la position de la flèche pour con naître le nombre d appareils pouvant être empilés Do NOT trample NE PAS marcher sur cet emballage DO NOT handle the machine alone if its weight is over 77 lbs 35 Kg NE PAS transporter tout seul l appareil si son poids dépasse 77 lbs 35...

Page 15: ... unit It could result in electrical shock or damage to the product Do not use hot water abrasive powders or strong solvents to clean the unit use a soft cloth MAINTENANCE Le convecteur soufflant AERMEC est construit avec des technolo gies modernes qui garantissent son efficacité et son fonctionne ment pour longtemps C est pourquoi le seul entretien qu il requiert est le nettoyage du filtre à air p...

Page 16: ...mprovement of the product Aermec partecipa al Programma di Certificazione EUROVENT I prodotti interessati figurano nella Guida EUROVENT dei Prodotti Certificati Aermec is partecipating in the EUROVENT Certification Programme Products are as listed in the EUROVENT Directory of Certified Products Aermec partecipe au Programme de Certification EUROVENT Les produits figurent dans l Annuaire EUROVENT d...

Reviews: