![AERMEC FCLI 122 Technical Manual Download Page 46](http://html.mh-extra.com/html/aermec/fcli-122/fcli-122_technical-manual_2862000046.webp)
46
IFCLITY1106 - 5773010_01
- Choose the place for unit installation
according to the layout of the room, the
number of units to be installed, and any
limitations imposed by the architecture.
Check the chosen place is suitable for
installation and maintenance work on
the unit.
- Install four M8 threaded rods into the
ceiling to hold the frame.
To install the FCLI unit, proceed as
follows:
- open the cardboard box
- upturn the box of the FCLI cassette-type
fan coil
- remove the box
- remove the packaging shells used to
protect the unit during transport
- fix the 4 installation brackets to the unit
(see the figure)
- if it is necessary to fit any accessories
(electric heaters, kit for fresh air or
delivery to an adjacent room, hot water
valve), carry out these operations before
installing the machine on the ceiling
WARNING:
consult the relevant
manuals of the accessories
- Do not handle the unit using the
water connections; use the specific
brackets for this purpose.
- lift the unit carefully by means of
the brackets and, keeping it slightly
inclined, attach it to the 4 threaded
bars using 8 nuts (4 of which are self-
locking). Use the nuts to adjust the
height of the unit; finally, check that the
unit is installed in a horizontal position
- feed the hydraulic pipes through the
suspended ceiling to the attachment
plate on the unit
- make the plumbing connections as
described in the relative chapter
- Take the condensate discharge piping to
the relative fitting on the attachment plate
- make the condensate drainage
connection as described in the relative
chapter
- drain the system; the drain valves are on
the outside, on the attachment plate
- bring the power supply and command
cables close to the electric box; ensure
the cables are long enough to follow
the movement of the electric box on
the guides during the assembly and
disassembly phases
- The electric box is supplied with the
grille accessories (GLL20)
- consult the manuals of the grille
accessories; the instructions for
assembling and connecting the electric
box can be found in the manual
supplied with the accessory
- After completing the connections and
inserting the electric box in its seat in
the FCLI unit, fix it with the two screws.
-
The grille frame must be positioned so
that the glass with the AERMEC logo is
in line with the corner of the electric
box
.
- Fix the grille with the 4 screws.
WARNING!! Tighten the screws with
a maximum tightening torque of 0.45
Nm. You are advised to use a
screwdriver. Do not use non-calibrated
electric screwdrivers. The tray will be
irreparably damaged if tightened too far.
-
WARNING: fix one snap-hook of
the safety wire to the grille frame, and
the other to the fan protection grille.
-
Fasten the suction grille to the
safety wire.
- adjust the position of the unit from the
support bracket - by means of the nuts
- so the unit is level and the frame rests
slightly on the suspended ceiling
- start the fan coil unit and carry out
an operation test; the functions are
described in the User Manual
INSTALLING THE "MODULE 840" UNIT