FCLI 4-pipe versions
FCLI
34
44
64
124
Heating
Heating output 70°C
Speed 4
W
-
3070
3800
12500
Speed 3
W
2600
2730
3380
10400
Speed 2
W
2190
2290
2990
9300
Speed 1
W
1950
1960
2640
7050
Water fl ow rate
Speed 4
l/h
-
264
327
1075
Speed 3
l/h
224
235
291
894
Speed 2
l/h
188
197
257
800
Speed 1
l/h
168
169
227
606
Pressure drop (VL)
Speed 4
kPa
-
14
21
29
Speed 3
kPa
11
12
17
21
Speed 2
kPa
8
8
14
17
Speed 1
kPa
6
6
11
10
Cooling
Cooling capacity
Speed 4
W
-
3650
4610
8800
Speed 3
W
1900
3000
3640
7270
Speed 2
W
1470
2340
2970
6220
Speed 1
W
1160
1810
2460
4570
Sensible cooling capacity
Speed 4
W
-
2920
3530
6770
Speed 3
W
1520
2180
2600
5520
Speed 2
W
1250
1680
2100
4670
Speed 1
W
990
1270
1720
3370
Water fl ow rate
Speed 4
l/h
-
628
793
1514
Speed 3
l/h
327
516
626
1250
Speed 2
l/h
253
402
511
1070
Speed 1
l/h
200
311
423
786
Pressure drop (VL)
Speed 4
kPa
-
22
31
38
Speed 3
kPa
10
15
21
27
Speed 2
kPa
7
10
14
20
Speed 1
kPa
4
6
10
12
Common data
Fans
no.
1
1
1
1
Air fl ow rate
Speed 4
cu.m/h
-
700
880
1750
Speed 3
cu.m/h
600
530
660
1350
Speed 2
cu.m/h
410
360
500
1100
Speed 1
cu.m/h
300
260
380
750
Sound power
Speed 4
dB(A)
-
53
61
60
Speed 3
dB(A)
46
46
54
54
Speed 2
dB(A)
38
38
47
50
Speed 1
dB(A)
35
35
41
44
Sound pressure
Speed 4
dB(A)
-
44
52
51
Speed 3
dB(A)
37
37
45
45
Speed 2
dB(A)
29
29
38
41
Speed 1
dB(A)
26
26
32
35
Input power
Speed 4
W
-
75
83
175
Speed 3
W
45
47
53
125
Speed 2
W
31
32
37
105
Speed 1
W
21
22
26
55
Input current (max speed)
A
0.22
0.33
0.37
0.75
Starting current
A
0.66
0.99
1.11
2.25
Power supply
V / Hz
230 ~ 50Hz
Maximum protection level
IP
20
20
20
20
Heat exchanger water content
L
1.2
1.5
2.1
4.5
Water connections (cold circuit)
Ø gas
3/4”
3/4”
3/4”
3/4”
Water connections (hot circuit)
Ø gas
1/2”
1/2”
1/2”
1/2”
Kvs (3-way valve, standard version)
2.5
2.5
2.5
4
Kvs (2-way valve, V2 version)
2.5
2.5
2.5
2.5
Level of sound pressure (A-weighted) measured in the room with
volume V = 100 m
3
, reverberation time t = 0.5 s; direction factor
Q = 2; distance r = 2.5m
Cooling:
• External air temperature 27°C D.B. ; 19°C W.B.
•
Water inlet temperature 7°C ;
t water 5°K
Heating 50°C:
• External air temperature 20°C
•
Water inlet temperature: 50°C;
t water 10°K
Heating 70°C:
• External air temperature 20°C
•
Water inlet temperature: 50°C;
t water 10°K
The leakage current to earth of several
devices placed under the same circuit
breaker is summed, so attention should be
paid to the calibration of the circuit breaker
and possibly consider the division of the
installation into several circuits each of
which protected by its own circuit breaker.
TECHNICAL DATA
= Performance certified EUROVENT 6/3 - Sound tests certified EUROVENT 8/2 (ISO 3741/2001)
Performance values refer to the following conditions: