AERMEC FCLI 122 Technical Manual Download Page 1

T E C H N I C A L   M A N U A L

CASSETTE-TYPE FAN COIL WITH INVERTER

IFCLITY1106 - 5773010_01

FCLI

FCLI 32 (600x600)
FCLI 34 (600x600)
FCLI 42 (600x600)
FCLI 44 (600x600) 
FCLI 62 (600x600)
FCLI 64 (600x600)

FCLI 82 (840x840)
FCLI 122 (840x840)
FCLI 124 (840x840)

Replace 5773010_00 / 1006

Summary of Contents for FCLI 122

Page 1: ...ASSETTE TYPE FAN COIL WITH INVERTER IFCLITY1106 5773010_01 FCLI FCLI 32 600x600 FCLI 34 600x600 FCLI 42 600x600 FCLI 44 600x600 FCLI 62 600x600 FCLI 64 600x600 FCLI 82 840x840 FCLI 122 840x840 FCLI 124 840x840 Replace 5773010_00 1006 ...

Page 2: ...AERMEC is involved in the Eurovent programme FCU Products covered by the programme can be found on the site www eurovent certification com ...

Page 3: ...use of automatic ladders scaffolding or any other lif ting system necessary for carrying out repairs under warranty AERMEC S p A declines all liability for any damage due to improper use of the machine or the partial or superficial reading of the information contained in this manual This manual contains the following number of pages 60 REMARKS DECLARATION OF CONFORMITY 4 Transport Safety symbols 5...

Page 4: ...LI auquel cette déclaration fait référence est conforme aux normes harmonisées suivantes EN 60335 2 40 EN 55014 1 EN 55014 2 CEI EN 61000 6 1 CEI EN 61000 6 2 CEI EN 61000 6 3 CEI EN 61000 6 4 satisfaisant ainsi aux conditions essentielles des directives suivantes Directive LVD 2006 95 CE Directive compatibilité électromagnétique 2004 108 CE FCLI PLUS ACCESSOIRES Il est interdit de faire fonctionn...

Page 5: ...durante el transporte Sovrapponibilità controllare sull imballo per conoscere il numero di macchine impilabili Stacking control the packing to know the number of machines that can be stacked Empilement vérifier sur l emballage pour connaître le nombre d appareils pouvant être empilés Stapelung DieAnzahl der stapelbaren Geräte wird durch die Symbole auf denVerpackungen ermittelt Apilamiento observe...

Page 6: ...outer or inner surfaces of the fan coil this might cause short circuits CLEAN THE FILTER PERIODICALLY Cleaning the filter frequently guarantees enhanced operating efficiency Check whether the filter is very dirty in this case clean it more often Clean frequently remove the accumulated dust with a vacuum cleaner Once the filter is clean refit it on the fan coil following the removal instructions bu...

Page 7: ...age but above all so is the sensation of effective sound e g if in a bedroom the traditional fan coil alternates minimum speed cycles and fan off cycles we don t perceive the average noise but the noise when running at minimum speed remains imprinted Energy savings through the use of the brushless motor that allows for greater efficiency even under normal conditions For comparison we have made an ...

Page 8: ...inium fins They are designed to offer the maximum heat exchange surface All batteries are provided with air bleed pipes and water drain valves located respectively on the highest and lowest point of the battery circulation INTERNAL THREE WAY VALVE Standard on standard versions Internal all or nothing type 3 way valve with fast connection actuator and visual signalling of the position assembled as ...

Page 9: ...alarm will stop the flow of water to the battery allowing only the fan to function HYDRAULIC CONNECTIONS The attachment plate groups together the water connections and the vent of the coil s primary circuit for 2 pipe and 4 pipe systems The plates contain raised symbols that identify the input IN and output OUT water connections for the water GLLI10 GLLI20 Obligatory accessory Intake and delivery ...

Page 10: ... multiplying the values obtained from the chart at maximum speed by the corrective factors indicated The pressure level and sound power of the fan coils at different speeds is shown in the tables A wide range of accessories is available for the FCLI fan coils but in certain cases some of them cannot be used simultaneously Check the accessories are compatible with the fan coil chosen The manual con...

Page 11: ... 41 39 44 Sound pressure Speed 4 dB A 44 52 41 51 Speed 3 dB A 37 37 45 36 45 Speed 2 dB A 29 29 38 34 41 Speed 1 dB A 26 26 32 30 35 Input power Speed 4 W 75 83 150 175 Speed 3 W 45 47 53 105 125 Speed 2 W 31 32 37 80 105 Speed 1 W 21 22 26 45 55 Input current max speed A 0 22 0 33 0 37 0 70 0 75 Starting current A 0 66 0 99 1 11 2 10 2 25 Power supply V Hz 230V 50Hz Maximum protection level IP 2...

Page 12: ...ure Speed 4 dB A 44 52 51 Speed 3 dB A 37 37 45 45 Speed 2 dB A 29 29 38 41 Speed 1 dB A 26 26 32 35 Input power Speed 4 W 75 83 175 Speed 3 W 45 47 53 125 Speed 2 W 31 32 37 105 Speed 1 W 21 22 26 55 Input current max speed A 0 22 0 33 0 37 0 75 Starting current A 0 66 0 99 1 11 2 25 Power supply V Hz 230 50Hz Maximum protection level IP 20 20 20 20 Heat exchanger water content L 1 2 1 5 2 1 4 5 ...

Page 13: ...048 1417 2040 1592 2044 1771 2048 1861 21 2587 1239 2579 1417 2575 1595 2571 1773 2567 1860 23 3145 1410 3141 1590 3133 1767 3129 1855 7 3 15 1185 1093 1201 1201 1266 1266 1417 1417 1567 1567 1641 1641 17 1631 1093 1627 1271 1621 1448 1620 1620 1649 1649 1670 1670 19 2108 1085 2104 1265 2100 1444 2092 1618 2090 1794 2084 1880 21 2614 1254 2606 1432 2092 1618 2595 1785 2593 1873 23 3156 1417 3153 1...

Page 14: ...562 751 751 925 925 1008 1008 17 154 154 308 308 562 562 754 754 926 926 1009 1009 19 159 159 310 310 569 569 755 755 928 928 1012 1012 21 588 374 754 603 892 821 1020 1020 1080 1080 23 1377 644 1377 818 1404 1002 1426 1096 15 3 15 304 304 477 477 638 638 794 794 945 945 1022 1022 17 305 305 477 477 639 639 796 796 948 948 1023 1023 19 445 334 538 533 650 650 797 797 949 949 1026 1026 21 1001 536 ...

Page 15: ...10 4250 3681 4259 3870 21 5377 2576 5361 2946 5353 3316 5345 3686 5336 3866 23 6538 2931 6529 3305 6513 3674 6505 3857 7 3 15 2463 2273 2497 2497 2633 2633 2947 2947 3258 3258 3411 3411 17 3391 2273 3382 2643 3371 3010 3368 3368 3428 3428 3473 3473 19 4382 2256 4374 2631 4365 3002 4349 3365 4345 3731 4333 3908 21 5435 2607 5419 2977 4349 3365 5394 3712 5390 3895 23 6562 2946 6554 3320 6538 3688 65...

Page 16: ...561 1923 1923 2096 2096 17 321 321 641 641 1168 1168 1567 1567 1926 1926 2098 2098 19 331 331 644 644 1182 1182 1569 1569 1929 1929 2104 2104 21 1222 777 1567 1254 1855 1708 2121 2121 2245 2245 23 2862 1339 2862 1701 2918 2083 2964 2279 15 3 15 633 633 991 991 1326 1326 1650 1650 1965 1965 2124 2124 17 634 634 993 993 1329 1329 1654 1654 1971 1971 2127 2127 19 925 693 1118 1109 1352 1352 1657 1657...

Page 17: ...1 3564 7 3 15 2276 2101 2307 2307 2433 2433 2723 2723 3010 3010 3152 3152 17 3133 2100 3125 2443 3115 2781 3112 3112 3167 3167 3209 3209 19 4049 2085 4042 2431 4034 2774 4019 3109 4015 3447 4004 3612 21 5022 2409 5007 2751 4019 3109 4984 3430 4980 3599 23 6064 2723 6056 3068 6041 3408 6033 3577 5 15 1879 1872 2043 2043 2281 2281 2582 2582 2877 2877 3021 3021 17 2723 1891 2713 2230 2749 2583 2828 2...

Page 18: ...2 1777 1777 1936 1936 17 297 297 593 593 1079 1079 1448 1448 1780 1780 1939 1939 19 306 306 595 595 1092 1092 1450 1450 1782 1782 1944 1944 21 1129 718 1448 1159 1714 1578 1960 1960 2075 2075 23 2645 1238 2645 1572 2697 1925 2739 2106 15 3 15 585 585 916 916 1226 1226 1525 1525 1816 1816 1962 1962 17 586 586 917 917 1228 1228 1529 1529 1821 1821 1965 1965 19 854 641 1033 1025 1249 1249 1531 1531 1...

Page 19: ...1 4650 7 3 15 3105 2741 3148 3148 3319 3319 3715 3715 4107 4107 4300 4300 17 4275 2740 4264 3187 4250 3629 4246 4070 4321 4321 4378 4378 19 5525 2721 5514 3172 5504 3619 5483 4057 5478 4498 5462 4712 21 6852 3143 6832 3589 5483 4057 6800 4475 6795 4696 23 8273 3552 8263 4003 8242 4447 8232 4667 5 15 2563 2442 2788 2788 3113 3113 3523 3523 3926 3926 4122 4122 17 3715 2467 3701 2909 3751 3370 3858 3...

Page 20: ...68 2424 2424 2642 2642 17 405 405 809 809 1472 1472 1975 1975 2428 2428 2645 2645 19 417 417 812 812 1490 1490 1979 1979 2432 2432 2653 2653 21 1540 937 1975 1512 2339 2059 2674 2593 2831 2831 23 3608 1615 3608 2051 3680 2512 3737 2748 15 3 15 798 798 1250 1250 1672 1672 2080 2080 2478 2478 2678 2678 17 800 800 1251 1251 1676 1676 2086 2086 2485 2485 2681 2681 19 1166 836 1410 1337 1704 1704 2089 ...

Page 21: ...1 4308 7 3 15 2875 2539 2914 2914 3073 3073 3439 3439 3802 3802 3980 3980 17 3957 2539 3947 2953 3934 3362 3931 3771 4000 4000 4053 4053 19 5114 2521 5105 2939 5095 3353 5076 3758 5071 4167 5056 4366 21 6343 2912 6324 3325 5076 3758 6295 4146 6290 4351 23 7659 3291 7649 3709 7630 4120 7620 4324 5 15 2373 2262 2581 2581 2881 2881 3261 3261 3634 3634 3815 3815 17 3439 2285 3426 2695 3472 3123 3571 3...

Page 22: ...22 2244 2244 2446 2446 17 375 375 749 749 1363 1363 1828 1828 2248 2248 2449 2449 19 386 386 752 752 1380 1380 1832 1832 2251 2251 2456 2456 21 1426 868 1828 1401 2165 1907 2475 2402 2621 2621 23 3340 1496 3340 1900 3406 2327 3459 2546 15 3 15 739 739 1157 1157 1548 1548 1926 1926 2294 2294 2479 2479 17 740 740 1158 1158 1551 1551 1931 1931 2300 2300 2482 2482 19 1079 775 1305 1239 1578 1578 1934 ...

Page 23: ... 9880 5126 7 3 15 3742 3021 3793 3520 3999 3999 4476 4476 4949 4949 5181 5181 17 5151 3021 5138 3513 5121 4000 5116 4487 5206 4991 5275 5229 19 6656 2999 6644 3496 6631 3990 6606 4472 6600 4958 6581 5195 21 8256 3465 8231 3956 6606 4472 8193 4933 8187 5177 23 9968 3916 9955 4413 9930 4902 9918 5145 5 15 3089 2692 3359 3248 3750 3750 4244 4244 4730 4730 4966 4966 17 4476 2719 4459 3207 4519 3715 46...

Page 24: ... 2921 3183 3183 17 488 488 974 974 1774 1774 2380 2380 2925 2925 3187 3187 19 503 464 979 979 1795 1782 2384 2384 2930 2930 3196 3196 21 1856 1033 2380 1667 2818 2270 3222 2858 3411 3143 23 4347 1780 4347 2261 4433 2769 4502 3029 15 3 15 961 961 1505 1505 2015 2015 2506 2506 2985 2985 3226 3226 17 963 963 1508 1508 2019 2019 2513 2513 2994 2994 3230 3230 19 1405 922 1699 1474 2053 2025 2517 2517 2...

Page 25: ...14 10337 7 3 15 6859 6093 6954 6954 7332 7332 8206 8206 9073 9073 9498 9498 17 9443 6092 9419 7085 9388 8067 9380 9049 9545 9545 9671 9671 19 12203 6048 12180 7051 12157 8046 12111 9018 12100 9999 12065 10476 21 15136 6987 15090 7979 12111 9018 15021 9949 15010 10440 23 18274 7897 18252 8899 18206 9886 18183 10376 5 15 5662 5429 6158 6158 6875 6875 7781 7781 8671 8671 9104 9104 17 8206 5484 8175 6...

Page 26: ...47 5355 5355 5836 5836 17 894 894 1786 1786 3252 3252 4363 4363 5363 5363 5843 5843 19 922 922 1794 1794 3292 3292 4371 4371 5371 5371 5859 5859 21 3402 2083 4363 3362 5166 4577 5906 5764 6253 6253 23 7970 3590 7970 4559 8127 5583 8253 6108 15 3 15 1762 1762 2760 2760 3693 3693 4595 4595 5473 5473 5914 5914 17 1766 1766 2764 2764 3701 3701 4607 4607 5489 5489 5922 5922 19 2575 1858 3114 2973 3764 ...

Page 27: ...262 7 3 15 5488 4870 5563 5563 5866 5866 6565 6565 7258 7258 7598 7598 17 7554 4869 7535 5663 7510 6448 7504 7233 7636 7636 7737 7737 19 9762 4834 9744 5636 9726 6431 9689 7208 9680 7992 9652 8373 21 12108 5585 12072 6377 9689 7208 12017 7952 12008 8344 23 14620 6312 14601 7113 14565 7902 14546 8294 5 15 4530 4339 4927 4927 5500 5500 6225 6225 6937 6937 7283 7283 17 6565 4383 6540 5169 6628 5989 6...

Page 28: ...284 4668 4668 17 715 715 1429 1429 2602 2602 3490 3490 4290 4290 4675 4675 19 738 738 1435 1435 2633 2633 3497 3497 4297 4297 4687 4687 21 2722 1665 3490 2687 4133 3658 4725 4607 5002 5002 23 6376 2869 6376 3644 6502 4463 6603 4882 15 3 15 1410 1410 2208 2208 2955 2955 3676 3676 4379 4379 4731 4731 17 1413 1413 2211 2211 2961 2961 3686 3686 4391 4391 4738 4738 19 2060 1485 2492 2376 3011 3011 3692...

Page 29: ...r inlet temperature air inlet temperature Ph Heating capacity kW FCLI 32 HEATING CAPACITY CORRECTION FACTORS Water flow rate l h t C water inlet temperature air inlet temperature Ph Heating capacity W FCLI 62 0 0 5 1 1 5 2 2 5 3 3 5 4 4 5 Water flow rate l h t C water inlet temperature air inlet temperature Ph Heating capacity W FCLI 64 The heat yields refer to the maximum speed For the rest of th...

Page 30: ... inlet temperature air inlet temperature Heating capacity kW FCLI 124 HEATING OUTPUT Modulo 840 300 400 500 600 700 800 900 1000 1100 1200 2 4 6 8 10 12 14 16 18 30 C 40 C 50 C 60 C 70 C 20 C Water flow rate l h t C water inlet temperature air inlet temperature Heating capacity kW FCLI 82 HEATING CAPACITY CORRECTION FACTORS The heat yields refer to the maximum speed For the rest of the speeds the ...

Page 31: ...0 234 37 160 77 147 11 75 68 37 57 2100 255 89 175 53 160 61 82 62 41 02 2200 278 24 190 86 174 64 89 84 44 60 2300 301 42 206 76 189 19 97 32 48 32 2400 325 41 223 22 204 25 105 07 52 17 2500 350 23 240 24 219 82 113 08 56 15 Pressure drops kPa Heating with 70 C water Water flow rate l h FCLI34 FCLI44 FCLI64 FCLI124 50 0 74 0 70 0 71 0 12 100 2 58 2 44 2 49 0 40 150 5 34 5 06 5 16 0 84 200 8 97 8...

Page 32: ...78 59 58 56 42 28 04 14 32 88 78 60 34 28 04 21 38 1200 103 83 69 68 65 99 32 80 16 74 103 83 70 57 32 80 25 01 1300 119 93 80 48 76 21 37 88 19 34 119 93 81 51 37 88 28 88 1400 137 04 91 96 87 09 43 29 22 10 137 04 93 14 43 29 33 01 1500 155 16 104 12 98 61 49 01 25 02 155 16 105 45 49 01 37 37 1600 174 27 116 95 110 75 55 05 28 10 174 27 118 44 55 05 41 97 1700 194 37 130 43 123 52 61 39 31 34 1...

Page 33: ...DE 0 6 0 7 0 8 0 9 1 0 1 1 1 2 6 7 8 9 10 11 12 13 14 15 16 17 C Medium glycol water temperature Correction factor 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 6 7 8 9 10 11 12 13 14 15 16 17 18 C Medium glycol water temperature Correction factor 30 40 50 60 70 80 90 C 0 8 0 9 1 0 1 1 1 2 1 3 1 4 Medium glycol water temperature Correction factor 0 8 0 9 1 0 1 1 1 2 1 3 1 4 30 40 50 60 70 80 90 ...

Page 34: ...9 4 48 41 FCLI82 Speed 4 Super Maximum 57 3 49 5 46 2 46 3 39 0 28 3 18 1 59 50 Speed 3 56 4 42 6 42 1 40 1 25 2 7 5 12 9 57 45 Speed 2 55 3 41 2 41 0 35 0 27 8 9 9 12 5 56 43 Speed 1 Minimum 51 5 35 3 36 6 25 9 30 4 11 0 12 2 52 39 FCLI122 FCLI124 Speed 4 Super Maximum 63 1 60 1 56 3 55 1 52 5 46 3 36 6 66 60 Speed 3 58 8 53 3 49 8 50 1 45 9 37 0 23 5 61 54 Speed 2 59 6 48 3 46 6 46 2 34 6 21 8 1...

Page 35: ...ral suction and lateral air delivery fins all within a frame and include an electric box for FCLI versions NB The GLLI10 and GLLI20 grille units have to be combined with a 0 10V output control panel to control ventilation speed see WMT20 The GLLI10N and GLLI20N grille units have to be combined with a VMF range control panel see VMF E4 Cold water circuit Hot water circuit FCLI VMF System Accessorie...

Page 36: ... N area thermostat allows communication with a central system supervisor VMF E5 GLLI 10 N GLLI 20 N The GLLI_N includes the electric box with incorporated VMF System thermostat board with bayonet coupling to the connector bound to the unit s load bearing structure The GLLI_N needs to be interfaced with a VMF E4 external control panel if installed on a single FCLI unit or with a Master function in ...

Page 37: ...ration of the electrostatic charge GLLI 10 GLLI 20 The GLLI includes the electric box with bayonet coupling to the connector bound to the unit s load bearing structure The GLLI needs to be interfaced with an external control panel not included with thermostat and ventilation speed control with a 0 10V output FEL10 ELECTROSTATICALLY PRE CHARGED AIR FILTER GLLI10 GLLI20 INTAKE AND DELIVERY GRILLE UN...

Page 38: ...nal fan The fresh air is directly introduced from the fin corresponding to the flange position The air is not extracted by the fan so is not mixed inside the unit with air that has already been treated Ø 150 KFLD20 KFLD20 Suction flange for connection to a duct to introduce fresh air into the room via an external fan The fresh air is directly introduced from the fin corresponding to the flange pos...

Page 39: ...g battery in 4 pipe systems Obligatory accessory in 4 pipe systems with variable flow rates VHL2 VHL22 2 WAY VALVES KIT VHL1 VHL20 Motor driven three way valve for the heating battery in 4 pipe systems Obligatory accessory for 4 pipe systems VHL1 VHL20 3 WAY VALVES KIT ACCESSORIES ...

Page 40: ...tional output Adjustment with ON OFF actuators control Range of setpoint knob different for heating and cooling Special functions economy dirty filter warning window contact Input for centralised summer winter selection Selectable power supply 230V or 24V VMF SW1 WATER TEMPERATURE PROBE FOR COLD WATER CIRCUIT IN 4 PIPE SYSTEMS ACCESSORIES WATER TEMPERATURE PROBES FOR VMF SYSTEM SW4 WATER TEMPERATU...

Page 41: ...p Supervisor controlled operating mode VMF E5 See the accessories manual for complete information on its features VMF E4 FCLI GLLI10N FCLI GLLI20N VMF E4 VMF E4 FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N MAX 30m FCLI GLLI10N FCLI GLLI20N VMF E5 VMF E4 VMF E4 VMF E4 MASTER 1 MASTER 2 MASTER 3 FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GL...

Page 42: ... hydronic system consisting of Fan coils up to 64 fan coil zones comprising 1 master maximum 5 slaves Chiller heat pump equipped with controls Modu_Control GR3 and pCO2 PCO required accessory RS 485 interface respectively MODU 485A AER485 AER485P2 AER485P1 Circulators maximum of 12 configurable zone circulators Boiler boiler consensus management for hot water production Heat recovery units consent...

Page 43: ... or kitchens where the oil vapours mixed with the treated air can be deposited on the exchange coils reducing their performance or on the parts inside the unit damaging the plastic parts Choose a position at the centre of the room whenever possible adjusting the air output allows air to be distributed optimally within the room Generally the best position of the fins is that which allows the launch...

Page 44: ...the outside of the attachment plate The drain valve for the heat circuit of 4 pipe systems is inside to access it remove the polystyrene tray make the condensate drainage connection as described in the relative chapter The electric box is supplied with the grille accessory GLLI GLLI_N bring the power supply and command cables close to the electric box ensure the cables are long enough to follow th...

Page 45: ...45 IFCLITY1106 5773010_01 1 2 3 INSTALLING THE MODULE 600 UNIT INSTALLING NEAR A WALL If the unit is to be installed near a wall the corresponding delivery outlet can be closed using the gasket supplied ...

Page 46: ...ensate discharge piping to the relative fitting on the attachment plate make the condensate drainage connection as described in the relative chapter drain the system the drain valves are on the outside on the attachment plate bring the power supply and command cables close to the electric box ensure the cables are long enough to follow the movement of the electric box on the guides during the asse...

Page 47: ... in particular the protection grille Installing near a wall If the unit is to be installed near a wall the corresponding delivery outlet can be closed using the gasket supplied 1 2 3 Maintenance of the electric box If you need to access the electric box for maintenance purposes observe the fol lowing indications open the filter grille make a turn of the two bolts remove the screw that blocks the c...

Page 48: ... an alarm the float device interrupts the flow of water in the coil The tray is fitted with an overflow hole to ensure that the condensate water runs off if the floating pump device is not working In this case dripping can be seen from the grille The pump allows a maximum head of 80cm from the level of the suspended ceiling if this is not high enough you will have to use an auxiliary device You ar...

Page 49: ...tion if inside a tube or raceway Use cables with double H5vv F type insulation for visible cable installation For all the connections follow the wiring diagrams supplied with the device and shown in this documentation The electric box is supplied with obligatory accessories GLLI GLLI_N Connect the Inverter to the electric box using the cables supplied WARNING Do not modify the settings of the Inve...

Page 50: ...Before installing the electric box the configuration of the electronic board dip switches needs to be checked in order to adjust the board to the system The diagram for configuring dip switches is included in the GLLI_N accessories manual Connect the VMF E4 control panel supervision network cable TTL network cable and probe and valve cables based on system requirements For the connections refer to...

Page 51: ... off power supply before cleaning filter and or unit DANGER Couper la tension avant de commencer les opérations de nettoyagedu filtre et ou de l unité GEFAHR Vor der Reinigung des Filters und oder des Gerätes die Stromversorgung abschalten PELIGRO Quitar la tensión antes de iniciar las operaciones de limpieza del filtro o de la unidad INSTALLAZIONE E SOSTITUZIONE DEL FILTRO Modulo 840 INSTALLATION...

Page 52: ...21 0 22 22 5 FCLI_V2 kg 20 5 21 0 20 5 21 0 20 5 21 21 22 5 FCLI_VL kg 20 0 20 5 20 0 20 5 20 0 20 5 21 5 22 273 616 587 16 30 9 587 KFLD KFL DATI DIMENSIONALI DIMENSIONS DONNÉES DES LES DIMENSIONS ABMESSUNGEN DATOS DIMENSIONALES mm FCLI 32 FCLI 34 FCLI 36 FCLI 42 FCLI 44 FCLI 62 FCLI 64 GLLI10 GLLI10N ...

Page 53: ...0 307 965 307 53 10 IN OUT FCLI 82 122 124 FCLI_ kg 36 36 36 FCLI_V2 kg 36 36 36 FCLI_VL kg 35 35 35 500 820 210 110 38 500 820 210 110 820 846 13 13 IN OUT OUT KFLD20 KFL20 KFLD20 DATI DIMENSIONALI DIMENSIONS DONNÉES DES LES DIMENSIONS ABMESSUNGEN DATOS DIMENSIONALES mm FCLI 82 FCLI 122 FCLI 124 GLLI20 GLLI20N ...

Page 54: ... CODES ALARM TYPE INDICATIONS IRREGULARITY Notes High temperature ALARM LED flashes 3sec ON 0 5sec OFF The LED if permanently ON after 1 5min Motor off Auto Restart Alarm If the conditions persist after 1 5min the alarm becomes permanent the Alarm LED stays on the system turns off Overvoltage Undervoltage Overcurrent Overload ALARM LED flashes 0 5sec ON 0 5sec OFF Speed reduction Power limitation ...

Page 55: ...AERMEC is involved in the Eurovent programme FCU Products covered by the programme can be found on the site www eurovent certification com ...