18
Aermec code 6755521_01 11.11
ANK 025-085H
Model
020
030
040
045
050
085
UNIT PROTECTION RATING
IP
24
24
24
24
24
24
SCROLL COMPRESSOR
Quantity/circuit
ALL
n°/n°
1/1
1/1
1/1
1/1
1/1
1/1
Capacity control
ALL
%
0-100
0-100
0-100
0-100
0-100
0-100
LOADS The declared data can be amended any time Aermec considers it necessary
R410A Refrigerant
ALL
kg
2.87
4.32
4.32
5.55
5.96
5.96
Oil
ALL
kg
0.9
0.9
0.9
0.9
1.2
1.2
SYSTEM SIDE HEAT EXCHANGER
Quantity
ALL
n°
1
1
1
1
1
1
Electric resistances
ALL
n°/W
1/40
1/40
1/40
1/40
1/40
1/40
Water content
ALL
dm
3
Hydraulic connections (Victaulic)
ALL
Ø
1" 1/4
1" 1/4
1" 1/4
1" 1/4
1" 1/4
1" 1/4
SYSTEM SIDE HYDRONIC KIT
STORAGE TANK
Storage tank
l
50
100
100
100
100
100
Storage tank resistances
n°/W
1/200
1/200
1/200
1/200
1/200
1/200
EXPANSION VESSEL
Expansion vessel
n°/l
1/2
1/5
1/5
1/5
1/5
1/5
Expansion vessel calibration
bar
1.5
1.5
1.5
1.5
1.5
1.5
PUMP
Input power
kW
0.16
0.17
0.18
0.31
0.33
0.34
Input current
A
0.83
0.88
0.90
1.55
1.65
1.70
SAFETY VALVE
Safety valve
n°/bar
1/6
1/6
1/6
1/6
1/6
1/6
AXIAL FANS
Quantity
ALL
n°
1
2
2
2
2
2
Air flow rate in cooling mode
ALL
m
3
/h
3500
8000
8000
7500
7500
7500
Input current
ALL
A
0.66
1.32
1.32
1.32
1.32
1.32
Input power
ALL
kW
0.15
0.3
0.3
0.3
0.3
0.3
SOUND DATA
Sound pressure
dB(A)
37
39.5
39.5
39.5
39.5
39.5
Sound power
dB(A)
68
70.5
70.5
70.5
70.5
70.5
DIMENSIONS WEIGHTS unit without packaging
Height mm
1028
1281
1281
1281
1281
1281
Width
H-HP
mm
1000
1000
1000
1000
1000
1000
HA
mm
1358
1450
1450
1450
1450
1450
Depth
mm
400
450
450
450
450
450
Empty weight
H
kg
118
149
152
165
172
174
HP
kg
123
154
157
175
182
184
HA
kg
160
211
214
232
238
241
Sound power
Aermec determines sound power values on the basis of meas-
urements made in compliance with the ISO 9614-2 Standard,
in agreement with that requested by Eurovent certification.
Sound pressure
Sound pressure in free field conditions on reflective surface
(directivity factor Q=2) at 10 mt from the external surface of
unit, in compliance with ISO 3744 regulations.
technical data