APPENDIX H
APPENDIX H
(cont.)
__________________________
Table H-2. BMS II Standard Holding Register Address Mapping
Modbus Data
Address (Hex)
Menu Item
Units and Range
Default/Comments
0x004C
Offset Off Time
Sat. – Minutes
0 to 59 Minutes
Default = 0
0x004D
Offset Off Time
Sun. – Hours
0 to 23 Hours
Default = 0
0x004E
Offset Off Time
Mon. – Hours
0 to 23 Hours
Default = 0
0x004F
Offset Off Time
Tue. – Hours
0 to 23 Hours
Default = 0
0x0050 Offset
Off
Time
Wed. – Hours
0 to 23 Hours
Default = 0
0x0051
Offset Off Time
Thu. – Hours
0 to 23 Hours
Default = 0
0x0052
Offset Off Time
Fri. – Hours
0 to 23 Hours
Default = 0
0x0053
Offset Off Time
Sat. – Hours
0 to 23 Hours
Default = 0
0x0054 (Reserved)
0x0055 Not
Applicable
0x0056
Remote Signal
0 or 1
0 = 4 – 20 Ma
1 = Network
Default = 0
(4 – 20 Ma)
0x0057
RS232 Mode
0 or 1
0 = Normal
1 = Modbus
Default = 1
(Modbus)
0x0058
RS232 Baud Rate
0=2400, 1=4800, 2=9600,
3=14400, 4=19200
2 = 9600
0x0059
Number Of Network
Boilers
0 to 32
Default = 2
0x005A
Min Slave Address
0 to 127
Default = 0
**0x005B
Max Slave Address 0 to 127,
Default = 0
**0x005C
Net Boiler 1
Address
Address for Network Boiler 1 Default = 1
**0x005D
Net Boiler 2
Address
Address for Network Boiler 2 Default = 2
H-9
Summary of Contents for BOILER MANAGEMENT SYSTEM II 5R5-384
Page 8: ......
Page 12: ......
Page 16: ...INSTALLATION ...
Page 17: ...INSTALLATION 2 5 ...
Page 21: ...INSTALLATION ...
Page 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Page 46: ......
Page 64: ......
Page 70: ......
Page 72: ......
Page 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Page 74: ......
Page 76: ......
Page 84: ......
Page 88: ...APPENDIX H H 4 A _ ...
Page 98: ......