![Aerco BOILER MANAGEMENT SYSTEM II 5R5-384 Installation, Operation & Maintenance Instructions Manual Download Page 22](http://html.mh-extra.com/html/aerco/boiler-management-system-ii-5r5-384/boiler-management-system-ii-5r5-384_installation-operation-and-maintenance-instructions-manual_2861530022.webp)
INSTALLATION
3. DO NOT terminate the shields to the Ground (
G
) terminal at the Boiler end of the RS485 loop.
Connect the shields of the incoming and outgoing leads together. The RS485 loop shield should only
be terminated at terminal 3 of the BMS II.
4. Activate the BIAS1, BIAS2 and TERM switches on the last boiler in the daisy-chain loop.
5. DO NOT activate the bias switches on the BMS II.
Figure 2-7. RS485 (Modbus) Wiring For Benchmark Series Boilers