APPENDIX A
APPENDIX A
_____________________________
BMS II MENUS
- Continued
AVAILABLE CHOICES OR LIMITS
MENU LEVEL & OPTION
MINIMUM
MAXIMUM
DEFAULT
RS485 MENU
RS485 BAUDRATE
2400, 4800,
9600, 19200
9600
MIN SLAVE ADDR
000
127
000
MIN SLAVE ADDR
000
127
000
NUMBER NETW BLRS
00
32
02
MODBUS CNTL TYPE
ROUND ROBIN,
BROADCAST
ROUND ROBIN
NETW BOILER 01
ADDRESS =
000 127 001
NETW BOILER 02
ADDRESS =
000 127 002
NETW BOILER 03
ADDRESS =
000 127 000
Etc., Up To:
NETW BOILER 32
ADDRESS =
000 127 000
FIELD ADJUST MENU
HEADER SET MODE
CONSTANT SETPOINT,
OUTDOOR RESET,
REMOTE SETPOINT
CONSTANT
SETPOINT
HDR HIGH LIMIT
040°F
220°F
200°F
HDR LOW LIMIT
040°F
220°F
040°F
INTERNAL SETPT
040°F
220°F
160°F
RESET RATIO
(Displayed Only if
HDR SET MODE =
OUTDOOR RESET)
0.3 3.0 1.2
BLDG REF TEMP
(Displayed Only If
HDR SET MODE =
OUTDOOR RESET)
40°F 220°F 70°F
REMOTE SIGNAL
(Displayed Only If HDR SET MODE
= REMOTE SETPT
4 – 20 mA,
MODBUS
4 - 20 mA
A-2
Summary of Contents for BOILER MANAGEMENT SYSTEM II 5R5-384
Page 8: ......
Page 12: ......
Page 16: ...INSTALLATION ...
Page 17: ...INSTALLATION 2 5 ...
Page 21: ...INSTALLATION ...
Page 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Page 46: ......
Page 64: ......
Page 70: ......
Page 72: ......
Page 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Page 74: ......
Page 76: ......
Page 84: ......
Page 88: ...APPENDIX H H 4 A _ ...
Page 98: ......