![Aerco BOILER MANAGEMENT SYSTEM II 5R5-384 Installation, Operation & Maintenance Instructions Manual Download Page 63](http://html.mh-extra.com/html/aerco/boiler-management-system-ii-5r5-384/boiler-management-system-ii-5r5-384_installation-operation-and-maintenance-instructions-manual_2861530063.webp)
APPENDIX B
B-1
APPENDIX B
_____________________________
STATUS AND FAULT MESSAGES
DISPLAY MESSAGES
DESCRIPTION
STATUS MESSAGES:
FAIL SAFE MODE
ACTIVATED
The system is running in the Constant Setpt mode due to loss of the
Remote signal or Outdoor Air sensor input.
NETWORK DISABLED
MODBUS LISTEN
“Forced Listen Only Mode” has been activated. All Modbus commands
except “restart Communications Options” will be ignored. The BMS II will
operate in the Fail Safe Mode.
OUTSIDE AIR TEMP
NOT CONNECTED
The Outdoor Air Temperature Sensor is not installed and connected.
RETURN TEMP
NOT INSTALLED
The Boiler Return Temperature Sensor is not installed.
FAULT MESSAGES
OUTDOOR SENSOR
ERROR
The Outdoor Air Temperature Sensor signal is out of range.
HEADER SENSOR
ERROR
The Header Temperature Sensor signal is out of range or disconnected.
RETURN SENSOR
ERROR
The Return Temperature Sensor signal is out of range.
INTERLOCK 1
ERROR
Interlock 1 input is open.
INTERLOCK 2
ERROR
Interlock 2 input is open.
4 – 20 mA INPUT
ERROR
The 4 – 20 mA Remote Input signal is lost.
MODBUS TIMEOUT
ERROR
The Modbus remote input information was not received within the
network timeout period.
Summary of Contents for BOILER MANAGEMENT SYSTEM II 5R5-384
Page 8: ......
Page 12: ......
Page 16: ...INSTALLATION ...
Page 17: ...INSTALLATION 2 5 ...
Page 21: ...INSTALLATION ...
Page 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Page 46: ......
Page 64: ......
Page 70: ......
Page 72: ......
Page 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Page 74: ......
Page 76: ......
Page 84: ......
Page 88: ...APPENDIX H H 4 A _ ...
Page 98: ......