APPENDIX E
xv
BOILER DEFAULT SETTINGS
INDOOR /OUTDOOR RESET MODE
MENU LEVEL
& CODE
DESCRIPTION OF CODE
DEFAULT
VALUE
PRIMARY MENU
tout
OUTLET TEMPERATURE
ACTUAL
Pct
PERCENTAGE OF FIRE RATE
ACTUAL
SEtP
UNIT’S SETPOINT TEMPERATURE
120
Airt
OUTSIDE AIR TEMPERATURE
ACTUAL
Auto
AUTO\MANUAL MODE
AUTO ON
SECONDARY MENU
Func
MODE OF OPERATION
OART
rEFt
BUILDING REFERENCE TEMPERATURE
70
rr
RESET RATIO
1.5
OASt
OUTSIDE AIR SENSOR FEATURE
OFF
OAt
OUTSIDE AIR TEMP
0
LLt
LOW LIMIT TEMPERATURE
40
HLt
HIGH LIMIT TEMPERATURE
220
Pb1
PROPORTIONAL GAIN
70
Int
INTEGRAL
1
drt
DERIVATIVE
0 (off)
Addr
ADDRESS
32
LOrE
LOCAL/REMOTE
LOC
SECURE MENU
SECr
SECURITY LEVEL
3
Func
MODE OF OPERATION
OART
gAin
GAIN
1
Pb3
PROPORTIONAL BAND
5000
LoFi
LOW FIRE
29
LFti
LOW FIRE TIMER
0
Purg
PURGE
100
O2-O
STOP LEVEL
20%
O2-C
START LEVEL
25%
FLti
FAULT TIMER
40 SEC.
dFiL
DISPLAY FILTER
5
ArUP
ANTI RESET WINDUP
ON
PEA
PEAK
ACTUAL
VAL
VALLEY
ACTUAL
InPC
INPUT CORRECTION
0
InPt
INPUT TIMER
0.2
FiLt
SENSOR FILTER
2
Unit
UNIT OF DISPLAY
F
Addr
ADDRESS
32
bAUd
BAUD RATE
9600
InP
INPUT
CAL
Summary of Contents for Benchmark G-00-711
Page 62: ...APPENDIX C ix Temperature Sensor Resistance Chart Balco ...
Page 69: ...APPENDIX F xvi ...
Page 70: ...APPENDIX F xvii ...
Page 71: ...APPENDIX F xviii ...
Page 72: ...APPENDIX F xix ...
Page 73: ...APPENDIX F xx ...
Page 74: ...APPENDIX G xviii ...
Page 75: ...APPENDIX G xix ...
Page 76: ...APPENDIX H xxi ...